Plan Review Details - Permit 07070447
Plan Review Stops For Permit 07070447
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-03-05 Cont ID  
Sent By rmcdouga Date 2008-03-05 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2008-03-05 Time 10:07 Sent To  
Notes
2008-03-05 10:10:41SHEETS A-4 AND A-5 OF PLANS WERE REVISED.
  
 BUILDING PROVISO
  
 SUBMIT THE LETTER WITH CALCULATIONS FOR THE NEW 2X12
 BEAM AS NOTED ON SHEET A-5 OF THE REVISED PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-02-06 Cont ID  
Sent By rmcdouga Date 2008-02-06 Time 16:57 Rev Time 0.00
Received By rmcdouga Date 2008-02-06 Time 14:22 Sent To  
Notes
2008-02-06 14:23:572004 FBC W/2007 REVISIONS
  
 THE REVISION TO ADD 2 X 6 BEARING WALL AND NEW BEAM IS
 DENIED
  
 1) ON SHEET A-4 THE NEW 2 X 6 BEARING WALL IS SPECIFIED
 AS AN EXISTING WALL ACCORDING TO THE WALL LEGEND.
 PLEASE REVISE. 2004 FBC 106.1.3* CITY AMENDMENTS.
  
 2) ON SHEET A-2 THE 2 X 6 BEARING WALL IS SPECIFIED AS
 A 4" WALL. IT WILL NEED TO BE REVISED. 2004 FBC
 106.1.3* CITY AMENDMENTS
  
 3) ON SHEET A-5 THE NEW ROOF GIRDER BEAM IS SPECIFIED
 AS 3 - 2 X 10S AND IN THE CONNECTOR SCHEDULE A SIMPSON
 LGUM 210-2, WHICH IS FOR A TWO MEMBER GIRDER IS
 SPECIFIED. PLEASE CORRECT. 2004 FBC 106.1.1* CITY
 AMENDMENTS.
  
 4) SUBMIT SIGNED AND SEALED CALCULATIONS FROM THE
 ENGINEER SHOWING THAT THE 3 -2 X 10 GIRDER SPANNING
 MORE THAN 15 FEET IS ADEQUATE TO RESIST THE ROOF LIVE
 AND DEAD LOADS WITH THE CEILING ATTACHED. 2004 FBC
 106.1.2* CITY AMENDMENTS.
  
 5) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE NEW TRUSSES AND RAFTERS TO THE 2 X 6 BEARING WALL.
 2004 FBC 106.1.3* CITY AMENDMENTS.
  
 6)PROVIDE A DETAIL OF THE 2 X 6 BEARING WALL
 SPECIFYING THE CONNECTORS, ANCHOR BOLTS, ETC. THAT WILL
 BE USED TO PROVIDE A CONTINUOUS LOAD PATH. FBC R601.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-01 Cont ID  
Sent By rmcdouga Date 2007-11-01 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2007-11-01 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-26 Cont ID  
Sent By rmcdouga Date 2007-10-26 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2007-11-01 Time 10:31 Sent To  
Notes
2007-10-26 11:38:33DENIED BY BUILDING
  
 1) SUBMIT PRODUCT APPROVAL FOR THE WINDOW MULLIONS THAT
 HAS BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SEE FBC 106.3.3 CITY AMENDMENTS.
  
 2) ADDRESS MECHANICAL REVIEW COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-17 Cont ID  
Sent By rmcdouga Date 2007-10-17 Time 17:41 Rev Time 0.00
Received By rmcdouga Date 2007-10-17 Time 17:41 Sent To  
Notes
2007-10-17 17:41:042004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE PREPARER. SEE FBC 13-103.1.1.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW
 MULLIONS.
  
 5) THE SOIL REPORT INDICATES THAT THE SOIL IS NOT
 ADEQUATE TO SUPPORT THE ADDITION. PLEASE INDICATE ON
 THE PLANS HOW THE INADEQUATE SOIL WILL BE CORRECTED.
 SPECIFY WHICH ONE OF THE RECOMMENDED METHODS WILL BE
 USED AND PROVIDE PLANS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By rmcdouga Date 2007-07-31 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2007-07-31 Time 11:17 Sent To P
Notes
2007-07-31 14:19:01DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SHOW COMPLIANCE WITH R322.2.2, WHICH REQUIRES AT
 LEAST ONE BATHROOM WITH A DOOR THAT HAS A 29" CLEAR
 OPENING. THE DOOR TO THE WATER CLOSET IN THE NEW MASTER
 BATHROOM DOES NOT COMPLY.
  
 4) ON SHEET A1 THE DESIGN DATA SPECIFIES THE INTERNAL
 PRESSURE COEFFICIENT AS N/A. SEE THE WIND DESIGN DATA
 ON SHEET A5. PLEASE CORRECT.
  
 5) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS
 THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND
 SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION. A 30-INCH (762 MM) MINIMUM
 UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE
 SECTION M1305.1.3 FOR ACCESS REQUIREMENTS WHERE
 MECHANICAL EQUIPMENT IS LOCATED IN ATTICS.
  
 6) SUBMIT ENERGY CALCULATIONS FOR THE ADDITION AS
 REQUIRED BY FBC CHAPTER 13.
  
 7) SOME OF THE NOTES AND PARTS OF THE FOOTING SCHEDULE
 ON SHEET A4 ARE ILLEGIBLE.
  
 8) DETAIL 5 ON A4 SPECIFIES A MINIMUM FOOTING THICKNESS
 OF 16" AND THE FOOTING SCHEDULE SPECIFIES AN 18" THICK
 FOOTING. PLEASE CORRECT.
  
 9) PLEASE UPDATE THE MASONRY NOTES ON A4 TO TMS 402-02
 AND TMS 602-02, WHICH ARE THE EDITIONS REFERENCED BY
 THE 2004 FBC RESIDENTIAL IN CHAPTER 43.
  
 10) REVISE THE ROOF NOTES IN DETAILS 1, 2 AND 3 0N A5
 TO SPECIFY 8D RING SHANK NAILS FOR FASTENING THE ROOF
 SHEATHING.
  
 11) THE UPLIFT PRESSURES FOR ROOF ZONES 1, 2 AND 3
 SPECIFIED ON A5 FOR A 100 SQFT EFFECTIVE WIND AREA ARE
 INCORRECT. SEE TABLE R301.2(2). THE UPLIFT PRESSURES
 FOR ROOFING SHOULD USE THE 10 SQFT EFFECTIVE WIND
 PRESSURES FROM THE TABLE. THE ROOF SLOPE SHOULD BE
 SPECIFIED BECAUSE IT IS REQUIRED TO DETERMINE THE
 PRESSURES.
  
 12) THE WALL COMPONENT AND CLADDING PRESSURE FOR ZONE 4
 ON A5 OF 38.2 SHOULD BE EXPRESSED AS A NEGATIVE INSTEAD
 OF POSITIVE. PLEASE CORRECT.
  
 13) SPECIFY THE LENGTH/EMBED DEPTH OF THE TAPCONS
 SPECIFIED IN DETAIL 4 ON S5. ALSO SPECIFY THAT THE
 MANUFACTURER OF THESE CONNECTORS IS "USP".
  
 14)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 15)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 16) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK AND
 WINDOW MULLIONS.
  
 17) THE WINDOW AND DOOR PRESSURES SPECIFIED ON THE
 ELEVATIONS ON SHEET A3 ARE HIGHER THAN THE MAXIMUM
 PRESSURES SPECIFIED ON SHEET A5. PLEASE CORRECT.
  
 18)FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 19) SPECIFY THE REQUIRED SOIL BEARING CAPACITY FOR THE
 STRUCTURE ON THE PLANS.
  
 20) THE VALUE OF THE PROJECT HAS BEEN INCREASED BASED
 ON ICC VALUATION DATA AND RADON FEES HAVE BEEN ADDED.
 FEES OF $ 56.26 ARE DUE.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 16:48 Rev Time 0.00
Received By btrobaug Date 2007-09-18 Time 15:34 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By btrobaug Date 2007-07-19 Time 07:56 Rev Time 0.00
Received By btrobaug Date 2007-07-19 Time 06:40 Sent To M
Notes
2007-07-19 07:56:22 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND
 CONDUCTOR SIZES.
  
 3} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
 SMALL APPLIANCE CIRCUITS @ 1500 VA EACH, 2 MINIMUM,
 220.52(A).
  
 4} } PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 5} THE RISER DIAGRAM IS NOT CLEAR. INDICATE IF THERE IS
 A METER/ MAIN OR A DISCONNECT DRAWN AS "2P "A". IF A
 DISCONNECT IS LOCATED AT THE METER, AN EQUIPMENT GROUND
 PER 250.122 MUST BE RAN WITH THE PANEL FEEDER.
  
 6} SEE 250.52(A)(3) FOR FOOTER STEEL, INCLUDE AS PART
 OF THE REQUIRED GEC SYSTEM WHEN RELOCATING THE SERVICE
 AND PUTTING AN ADDITION ON, AS THE FOOTER STEEL IS
 "AVAILABLE".
  
 7} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 10:46 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 10:46 Sent To B
Notes
2008-02-06 10:47:13TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 17:03 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 17:03 Sent To B
Notes
2007-10-30 17:03:48TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 15:57 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 15:57 Sent To M
Notes
2007-10-18 15:58:06TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 09:01 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 09:00 Sent To Z
Notes
2007-09-13 09:01:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 09:39 Rev Time 0.00
Received By jleech Date 2007-07-17 Time 14:02 Sent To  
Notes
2007-07-17 14:03:30TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-19 Cont ID  
Sent By tgordon Date 2008-03-19 Time 13:51 Rev Time 0.35
Received By tgordon Date 2008-03-19 Time 13:51 Sent To  
Notes
2008-03-19 13:52:46REVISION TO MECH. PLAN M-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-10-31 Cont ID  
Sent By tgordon Date 2007-10-31 Time 09:47 Rev Time 0.30
Received By tgordon Date 2007-10-31 Time 09:47 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 08:04 Rev Time 0.40
Received By tgordon Date 2007-10-25 Time 08:04 Sent To B
Notes
2007-10-25 08:14:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 9-19-07 NOTE #2. ENERGY
 CALCULATIONS LINE 15 IS TAKING CEILING FAN CREDIT, SEE
 FBC 13-607.2.A.3.1 CEILING FAN CREDIT MAY BE TAKEN IF
 ONE OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE
 BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED
 IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY
 ROOMS, OR GREAT ROOMS). PLEASE SHOW ON ELECTRICAL PLAN
 EXISTING CEILING FANS IN ALL REQUIRED ROOMS IF THEY
 EXIST OR REMOVE CREDIT FROM ENERGY CAL'S.
  
 2) AS NOTED IN LAST REVIEW 9-19-07 NOTE #3. I COULD NOT
 VERIFY THE A/C EQUIPMENT LISTED ON MECHANICAL PLAN WITH
 THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT ARI LISTING,
 SEE FBC 13-607.1.ABC.3.1.1.
  
 3) THE DUCT DESIGN MUST BE PART OF THE PLAN AND CAN NOT
 BE ADDED BY HAND TO SOME OTHER PLAN, PLEASE SUBMIT A
 PROPER MECHANICAL PLAN (NO PENCIL, PEN, WHITE-OUT, AND
 NO HAND CHANGES), SEE W.P.B. AMEND. 106.1.3..
  
 4) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By tgordon Date 2007-09-19 Time 14:24 Rev Time 0.30
Received By tgordon Date 2007-09-19 Time 14:24 Sent To P
Notes
2007-09-19 15:01:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY THE
 PREPARER, SEE FBC 13-103.1.1.
  
 2) ENERGY CALCULATIONS LINE 15 IS TAKING CEILING FAN
 CREDIT, SEE FBC 13-607.2.A.3.1 CEILING FAN CREDIT MAY
 BE TAKEN IF ONE OR MORE CEILING FANS ARE INSTALLED IN
 EACH OF THE BEDROOMS AND A MINIMUM OF ONE CEILING FAN
 IS INSTALLED IN ALL PRIMARY LIVING AREAS (LIVING ROOMS,
 FAMILY ROOMS, OR GREAT ROOMS). PLEASE SHOW ON
 ELECTRICAL PLAN EXISTING CEILING FANS IN ALL REQUIRED
 ROOMS IF THEY EXIST OR REMOVE CREDIT FROM ENERGY
 CAL'S.
  
 3) I COULD NOT VERIFY THE A/C EQUIPMENT LISTED ON
 MECHANICAL PLAN WITH THE ARI DIRECTORY WEB-SITE TO
 CHECK SEER AND THAT IT IS A HEAT PUMP, PLEASE SUBMIT
 ARI LISTING AND DETAILED MANUFACTURER'S SPECIFICATION'S
 AND INSTALLATION INSTRUCTIONS FOR A/C SYSTEM.
  
 4) THE MECHANICAL PLAN SUBMITTED HAS TO MUCH FLOOR PLAN
 DETAIL ON IT AND IS DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC
 106.1.1.
  
 5) THE DUCT DESIGN MUST BE PART OF THE PLAN AND CAN NOT
 BE ADDED BY HAND TO SOME OTHER PLAN, PLEASE SUBMIT A
 PROPER MECHANICAL PLAN.
  
 6) AN EXHAUST FAN IS REQUIRED IN THE MASTER BATHROOM
 TUB AND SHOWER AREA, SEE RES.R303.3.
  
 7) THE EXISTING BATHROOM REQUIRES A EXHAUST FAN , SEE
 RES. R303.3.
  
 8) PROVIDE FOR RETURN AIR TO THE EXISTING PART OF THE
 HOUSE IF THE FAMILY ROOM DOORS WERE CLOSED, SEE RES.
 M1602.4.
  
 9) MECHANICAL PLAN WILL NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER AS HIS INFORMATION IS IN THE TITLE BLOCK,
 IF HIS INFORMATION WAS NOT IN THE TITLE BLOCK THEN IT
 WOULD NEED THE PREPARERS INFORMATION AND SIGNATURE, SEE
 WPB 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
 .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By tgordon Date 2007-07-19 Time 09:44 Rev Time 0.30
Received By tgordon Date 2007-07-19 Time 09:44 Sent To P
Notes
2007-07-19 09:52:37*** DENIED ***
 1) MECHANICAL PERMIT 07070449 APPLIED FOR BUT NO
 MECHANICAL PLANS SUBMITTED FOR REVIEW.
  
 2) PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW (BUILDING
 PLANS SHOW A NEW A/C SYSTEM TO BE INSTALLED).
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2.
  
 4) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-12 Cont ID  
Sent By jleech Date 2007-10-12 Time 07:35 Rev Time 0.00
Received By jleech Date 2007-10-12 Time 07:35 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 09:39 Rev Time 0.00
Received By jleech Date 2007-08-02 Time 09:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By choops Date 2007-09-18 Time 08:38 Rev Time 0.00
Received By choops Date 2007-09-18 Time 08:38 Sent To E
Notes
2007-09-18 08:41:38***APPROVED - RESUB #1***
  
 PROVISO:AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50%
 OF THE VALUE OF THE HOME, THE SITES LANDSCAPING SHALL
 BE BROUGHT TO CURRENT REGULATIONS, IF NOT ALREADY.
 PURSUANT TO SECTION 94-442(B)(2)(A):FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-18 Cont ID  
Sent By choops Date 2007-07-18 Time 13:14 Rev Time 0.00
Received By choops Date 2007-07-18 Time 13:14 Sent To E
Notes
2007-07-18 13:17:21***FAILED***
  
  
 1)PLEASE PROVIDE 2 COPIES OF A CURRENT SURVEY
 SHOWING SCOPE OF WORK WITH DIMENSIONS AND SETBACK
 DIMENSIONS TO SIDE AND REAR PROPERTY LINES FROM
 PROPOSED ADDITION.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES ON THE SURVEYS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720