Plan Review Details - Permit 07070436
Plan Review Stops For Permit 07070436
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-18 Cont ID  
Sent By jwitmer Date 2007-10-18 Time 12:28 Rev Time 0.77
Received By jwitmer Date 2007-10-18 Time 12:28 Sent To  
Notes
2007-10-18 12:32:00BEAR LAKES COUNTRY CLUB
 TRAINING FACILITY
 1400 BRANDYWINE RD
 OCT. 18/2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07070436
 ADD: 1401 BRANDYWINE RD
 CONT: PURDY CONSTRUCTION
 TEL: (561)718-8080
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISOS:
 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECTOR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSURANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH ENGINEERING STANDARDS TO
 PRESERVE THE POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL
 NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE
 ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-09 Cont ID  
Sent By jwitmer Date 2007-10-09 Time 16:13 Rev Time 1.33
Received By jwitmer Date 2007-10-09 Time 16:13 Sent To P
Notes
2007-10-18 12:29:46BEAR LAKES COUNTRY CLUB
 TRAINING FACILITY
 1400 BRANDYWINE RD
 OCT. 18/2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07070436
 ADD: 1401 BRANDYWINE RD
 CONT: PURDY CONSTRUCTION
 TEL: (561)718-8080
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISOS:
 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECTOR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSURANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH ENGINEERING STANDARDS TO
 PRESERVE THE POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL
 NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE
 ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
2007-10-10 09:57:59 
  
  
 BEAR LAKES COUNTRY CLUB
 TRAINING FACILITY
 1400 BRANDYWINE RD
 OCT. 09/2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07070436
 ADD: 1401 BRANDYWINE RD
 CONT: PURDY CONSTRUCTION
 TEL: (561)718-8080
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISOS:
 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECTOR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSURANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH ENGINEERING STANDARDS TO
 PRESERVE THE POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL
 NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE
 ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-15 Cont ID  
Sent By jwitmer Date 2007-08-15 Time 17:15 Rev Time 1.11
Received By jwitmer Date 2007-08-15 Time 17:15 Sent To  
Notes
2007-08-15 17:46:12BUILDING PLAN REVIEW
 PERMIT: 07070436
 ADD: 1401 BRANDYWINE RD
 CONT: PURDY CONSTRUCTION
 TEL: (561)718-8080
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW MONOLITHIC SLAB & PLUMBING
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) LOCATION OF BUILDING ONLY ONE SEALED SURVEY AND A
 SINGLE COPIED SITE PLAN. EITHER PROVIDE 2 SEALED
 SURVEYS OR TO ORIGINAL SIGNED AND SEALED SITE PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) ADDITIONAL INFORMATION WILL BE REQUIRED. 106.1.2*
 THE PERMIT APPLICATION INDICATES THERE IS TO BE
 PLUMBING WITHIN THE BUILDING, IF SANITARY WILL REQUIRE
 PLANS FOR THE FOUNDATION PERMIT.
  
 6) PKA DRAFTING IS WORKING OUT OF THE SCOPE OF THE
 DRAFTSMAN LICENSE, ONLY RESIDENTIAL IF THIS VIOLATION
 CONTINUES PLANS WILL BE FORWARDED TO THE STATE FOR
 REVIEW BY THE ENGINEERING BOARD. SEE 471. AND
 61G15.23.001 . PLEASE SEE CASE NO. 03-0489 DPBR OF
 ARCHITECTURE VS LEEMARIE AND LEE MARIE COMPANY.
  
 7) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 H) FINISH FLOOR HEIGHT.
  
 8) MONOLITHIC SLAB WILL REQUIRE A GROUNDING INSPECTION
 106.3.5.1.2*(STEEL) WITH AN ELECTRICAL PERMIT AN
 PLUMBING ROUGH 106.3.5.1.3* BY PLUMBING CONTRACTOR
 BEFORE THE SLAB INSPECTION. REQUIRED INSPECTIONS.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-18 Cont ID  
Sent By dpalmer Date 2007-10-18 Time 09:30 Rev Time 0.00
Received By dpalmer Date 2007-10-18 Time 09:30 Sent To P
Notes
2007-10-18 09:31:55ELECTRICAL RISER SHEETS FOR FOUNDATION FOOTER/SLAB
 GROUNDIGN ELECTRODE SYSTEM ONLY.
  
 **PLANS WILL BE ROUTED TO PLUMBING AND BUILDING AS
 THERE ARE NEW SHEETS FOR THE BUILDIGN REVIEWER TO
 STAMP.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 15:15 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 15:09 Sent To PC
Notes
2007-10-14 15:15:29 
 ** DENIED**
  
 1) NOTE:PLEASE BE SURE THE FOLLOWING MINIMUM CODES
 ARE REQUIRED ON PLANS.
 NFPA-70 2005
  
 2) NOTE: PLEASE SUBMIT A GROUNDING ELECTRODE DETAIL FOR
 NEW SLAB/FOUNDATION PER 250.50.
 PLEASE BE SURE TO REFERENCE OF SERVICE UNDER EXISTING
 APPLIED PERMIT FOR MAIN BUILDING.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2007-07-19 Cont ID  
Sent By rchokshi Date 2007-07-19 Time 14:56 Rev Time 0.00
Received By rchokshi Date 2007-07-19 Time 14:56 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 15:10 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 15:10 Sent To E
Notes
2007-10-17 15:11:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 15:15 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 15:15 Sent To  
Notes
2007-10-03 15:15:12TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By jwitmer Date 2007-08-15 Time 17:15 Rev Time 1.11
Received By adarroug Date 2007-07-17 Time 09:55 Sent To PC
Notes
2007-07-17 09:55:39TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-18 Cont ID  
Sent By kstevens Date 2007-10-18 Time 12:11 Rev Time 0.00
Received By kstevens Date 2007-10-18 Time 12:11 Sent To B
Notes
2007-10-18 12:12:40THE TOILET ROOMS SHALL BE ACCESSIBLE AND SHOULD BE
 TAKEN INTO CONSIDERATION AS THE SANITARY PIPING WILL BE
 IN THE SLAB. THE HOLDER OF THE FOUNDATION PERMIT WILL
 BE PROCEEDING AT THEIR OWN RISK AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE REMAINDER OF THE WORK WILL BE
 GRANTED AND THAT CORRECTIONS WILL NOT BE REQUIRED IN
 ORDER TO MEET PROVISIONS OF THE TECHNICAL OR ACCESSIBLE
 CODE. SECTION 105.13.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-13 Cont ID  
Sent By kstevens Date 2007-10-13 Time 06:57 Rev Time 0.00
Received By kstevens Date 2007-10-13 Time 06:57 Sent To E
Notes
2007-10-13 07:06:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE LOCATION OF DRINKING FOUNTAIN AND SHOW
 ON THE SANITARY RISER DIAGRAM.
  
 2. SHT S-1 SANITARY RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENTS. THE TRAPS FOR THE LAVS ARE INDICATED
 UNDERGROUND AS SHOWN ON THE RISER DIAGRAM. SEE THE RED
 LINED EXAMPLE OF A RISER DIAGRAM THAT MEETS CODE AND
 SHOWS THE REQUIRED DRINKING FOUNTAIN.
  
 3. THE TOILET ROOMS SHALL BE ACCESSIBLE AND SHOULD BE
 TAKEN INTO CONSIDERATION AS THE SANITARY PIPING WILL BE
 IN THE SLAB. THE HOLDER OF THE FOUNDATION PERMIT WILL
 BE PROCEEDING AT THEIR OWN RISK AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE REMAINDER OF THE WORK WILL BE
 GRANTED AND THAT CORRECTIONS WILL NOT BE REQUIRED IN
 ORDER TO MEET PROVISIONS OF THE TECHNICAL OR ACCESSIBLE
 CODE. SECTION 105.13.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-19 Cont ID  
Sent By eschneid Date 2007-10-19 Time 12:09 Rev Time 0.00
Received By eschneid Date 2007-10-19 Time 12:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-09 Cont ID  
Sent By choops Date 2007-10-09 Time 08:59 Rev Time 0.00
Received By choops Date 2007-10-09 Time 08:59 Sent To B
Notes
2007-10-09 13:47:27***APPROVED - RESUB #1***
  
 PER MINOR AMENDMENT APPROVAL

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-18 Cont ID  
Sent By choops Date 2007-07-18 Time 11:55 Rev Time 0.00
Received By choops Date 2007-07-18 Time 11:55 Sent To ENG
Notes
2007-07-18 12:01:27***FAILED***
  
  
 1)REQUIRES A MAJOR AMENDMENT.AS PER THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION 94-207(E)(1)(A):
  
 MAJOR AMENDMENTS TO APPROVED PLANNED DEVELOPMENTS SHALL
 ONLY BE DETERMINED BY THE CITY COMMISSION FOLLOWING THE
 PROCEDURE SET OUT IN SECTION 94-32. MAJOR AMENDMENTS
 SHALL INCLUDE THE FOLLOWING REQUESTS:
 A.AN INCREASE IN THE TOTAL SQUARE FOOTAGE OF ANY
 BUILDING BY MORE THAN FIVE PERCENT; THE NUMBER OF
 STRUCTURES, THE NUMBER OF RESIDENTIAL DWELLING UNITS,
 TO THE DENSITIES AS SPECIFIED BY THE ADOPTED MASTER
 PLAN;
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720