| Plan Review Stops For Permit 07070433 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-03 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2008-01-03 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-21 |
Time |
07:32 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-02-21 |
Time |
07:32 |
Sent To |
PC |
|
| Notes |
| 2008-02-21 07:32:41 | REV DATED 1-23-08 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-03 |
Time |
09:53 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-01-03 |
Time |
09:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-03 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2008-01-03 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-19 |
Time |
10:53 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-11-19 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2007-11-19 10:54:30 | SEE FOUNDATION PERMIT FOR NOA AND IMPACT FEES.07070436. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-16 |
Time |
16:44 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-11-16 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2007-11-16 16:45:14 | 1401 BRANYWINE RD | | | TRAINING FACILITY | | | 07070433 2ND REV | | | NOV.16, 2007 | | | BUILDING PLAN REVIEW | | | PERMIT: 07070433 | | | ADD: 1401 BRANYWINE RD | | | CONT: PURDY CONSTRUCTION | | | TEL: (561)718-8080 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)THE NOTICE OF COMMENCEMENT SUBMITTED FOR THE TRAINING | | | CENTER IS OVER 90 DAY OLD, IT WILL NEED TO BE | | | RE-RECORDED.FL S S 713.13NOTICE OF COMMENCEMENT, TO | | | BE FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | | 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) COMPLIED. | | | | | | 4) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) COMPLIED | | | B) COMPLIED. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. AS NOTED ON SHEET A-1, THIS STRUCTURE IS | | | DESIGNED AS A TYPE II-B BUILDING. THE CITY SHALL REVIEW | | | THE STRUCTURE AS DECLARED BY THE DESIGN PROFESSIONAL. | | | THE MINIMUM BUILDING TYPE BY CODE IS A TYPE V-B BY | | | CODE. | | | DECLARING THE BUILDING A TYPE II-B THE DESIGNER NEEDS | | | TO RATE THE ROOFING ASSEMBLY AS STATED IN TABLE 601 | | | FOOTNOTE ( C ) (2) FIRE RETARDANT TREATED WOOD SHALL BE | | | USED IN ALL GIRDERS, TRUSSES AND ROOF SHEATHING. | | | | | | D-G) COMPLIED. | | | | | | 5-12) COMPLIED. | | | | | | | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-01 |
Time |
10:15 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-08-01 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2007-08-01 12:38:54 | 1401 BRANYWINE RD- 07070433 1ST REV | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07070433 | | | ADD: 1401 BRANYWINE RD | | | CONT: PURDY CONSTRUCTION | | | TEL: (561)718-8080 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) PKA DRAFTING PLEASE SEE ATTACHMENT THAT YOU ARE | | | WORKING OUT OF THE SCOPE OF YOUR LICENSE. SEE FL CASE | | | NO 03-0489 1 SET OF PLANS WILL BE KEPT AND SENT TO THE | | | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION, | | | BOARD OF ENGINEERS. | | | | | | 4) 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OF THE CODE UNDER WHICH | | | THE PROJECT IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | | | | 5) PLEASE PROVIDE THE FINISH FLOOR ELEVATION, THIS AREA | | | IS A ?B? ZONE LOMR REQUIRING A FINISH FLOOR ELEVATION | | | OF 16?-6?. | | | | | | 6) PLEASE PROVIDE SOILS REPORT. 1802.2.1 QUESTIONABLE | | | SOIL. | | | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN | | | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT | | | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING | | | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION | | | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE | | | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . | | | | | | 7) SHEET A-3 MONOLITHIC SLAB, PLANS INDICATE THE USE OF | | | WIRE MESH:CONCRETE SLABS ON GROUND CONTAINING 6X6 | | | W1.4 ? W1.4 WELDED WIRE REINFORCEMENT FABRIC LOCATED IN | | | THE MIDDLE TO THE UPPER ONE-THIRD OF THE SLAB. WELDED | | | WIRE REINFORCEMENT FABRIC SHALL BE SUPPORTED WITH | | | APPROVED MATERIALS OR SUPPORTS AT SPACINGS NOT TO | | | EXCEED 3 FEET (914 MM) OR IN ACCORDANCE WITH THE | | | MANUFACTURER?S SPECIFICATIONS. WELDED PLAIN WIRE | | | REINFORCEMENT FABRIC FOR CONCRETE SHALL CONFORM TO ASTM | | | A 185, STANDARD SPECIFICATION FOR STEEL WELDED WIRE | | | REINFORCEMENT FABRIC, PLAIN, FOR CONCRETE REINFORCEMENT | | | . | | | | | | 8)SHEET A-3 PLANS INDICATE THE USE OF A HIPPED ROOF | | | WITH WOOD TRUSSES: 1203.2 ATTIC SPACES: THE NET FREE | | | VENTILATING AREA SHALL NOT BE LESS THAN 1 / 150 OF THE | | | AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF THE | | | REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS | | | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE | | | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR | | | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED | | | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. | | | | | | 9) 1209.2 ATTIC SPACES. | | | AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM | | | BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A | | | CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 | | | MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE | | | PROVIDED AT OR ABOVE THE ACCESS OPENING. | | | | | | 10) DISCREPANCY ON SHEET A-3 DETAILS 1& 3 ONE APPEARS | | | TO BE ROOF TILE AS THE PRODUCT APPROVAL SUBMITTED | | | WHEREAS DETAIL # 1 INDICATES THE USE OF SHINGLES. | | | | | | 11) PLANS INDICATE THE USE OF ?? DRYWALL ON THE CEILING | | | PLEASE INDICATE THE DIRECTION OF THE BOARD, TYPE OF | | | FASTENERS TO BE USED, AND LENGTH. TABLE 2508.1- | | | GA-216. | | | | | | 12) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) OVERHEAD OR COIL TYPE DOOR- NO REPORT SUBMITTED | | | B) EXTERIOR METAL SWING DOOR- CURRIES REQUIRES FL COVER | | | SHEET | | | C) ROOFING ASSEMBLIES | | | UNDERLAYMENTS- NO PRODUCT APPROVALS WERE SUBMITTED | | | ROOF TILE- HANSON , REQUIRES FL COVER SHEET, ALSO | | | HIGHLIGHT WHAT TYPE OF FASTENER WILL BE | | | USED. PROVIDE WHAT TYPE OFHIP AND RIDGE BOARD TO | | | BE USED AND TYPE OF FASTENER, 1507.3.7 ATTACHMENT. | | | CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN | | | ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH | | | FRSA/TRI 07320 INSTALLATION MANUAL. | | | | | | 1507.3.8 APPLICATION. | | | TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE | | | FRSA/TRI 07320. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-05 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-05 |
Time |
17:16 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-12-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-19 |
Time |
08:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-19 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-11-19 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2007-11-19 14:55:00 | ** DENIED 2ND REVIEW ** | | | | | | ** AS STATED ON PREVIOUS REVIEW, PLEASE SEE THERE ARE | | | SOME COMMENTS FROM PREVIOUS REVIEW AND SOME NEW | | | COMMENTS BASED ON INFORMATION NOW BEING SUBMITTED. | | | | | | 1) NOTE: PLEASE SHOW ALL LOCATIONS OF SERVICE EQUIPMENT | | | ON PLANS FOR LOCATIONS. | | | CAN NOT VERIFY ITEMS AT THIS TIME FOR TAPPED | | | CONDUCTORS, DISCONNECTING MEANS, CLEARANCES ETC. | | | 240.21, 110.26, 240.24, 225.31ETC | | | AS THE LOCATION OF TRANSFORMER AND MAIN BREAKER PANEL | | | AT THIS DETACHED STRUCTURE FROM SERVICE LOCATION IS NOT | | | SHOWN WE ARE UNABLE TO CONFIRM LOCATIONS. | | | | | | 2) NOTE: PLEASE SEE THE PREVIOUS NOTES FOR DISCONNECTS | | | REQUIRED FOR A/C SYSTEM AHU AND CU> | | | PLEASE SEE THERE ARE BOXES SHOWN ON PLANS WITH CIRCUIT | | | NUMBERS BUT NO DISCONNECTS PER 440.11. | | | | | | 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM | | | AT THIS DETACHED STRUCTURE PER 250.50, 250.32 | | | | | | 4) NOTE: PLEASE CLARIFY CONTINUOUS LOADS AND WHERE | | | THESE ARE SHOWN AT 125%. | | | NO LOAD CALCULATIONS ACTUALLY SHOWN. | | | 215.3, 230.42 ETC. | | | 220.12, 220.14, 220.42, 220.44 ETC. | | | | | | 5) NOTE: PLEASE SEE RISER IS STILL INDICATING A NEUTRAL | | | ON THE LINE SIDE OF THE TRANSFORMER. PLEASE EXPLAIN AS | | | THIS TRANSFORMER IS A SEPARATELY DERIVED SYSTEM AND | | | CREATES ITS OWN NEUTRAL. | | | 250.6, 250.24 ETC. | | | | | | 6) NOTE: PLEASE SEE THE METHOD *A* CALCULATIONS NOW | | | SUBMITTED ARE SIGNED AND SEALED BY AN ARCHITECT WHICH | | | IS NOT THE ARCHITECT OR ENGINEER OF RECORD. | | | PLEASE SEE THE CERTIFICATION SHEET IS REQUIRED TO BE | | | COMPLETED WITH ALL INFORMATION FOR RESPONSIBLE | | | DESIGNERS. | | | PLEASE ALSO SEE MISSING OWNER AGENT. | | | FBC 13-101, FS 471.025 | | | | | | 7) NOTE: PLEASE SEE THE LIGHTING AS SHOWN ON PLANS DOES | | | NOT CORRELATE WITH THE LIGHTING ON THE INPUT DATA | | | REPORT. | | | PLEASE CORRELATE AND SUBMIT. | | | FBC 13-415.1.A, 13-415.2 | | | | | | 8) NOTE: PLEASE SEE 13-413.1.ABC.2.2 AND PLACE NOTE ON | | | PLANS ACCORDINGLY. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-06 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-06 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2007-08-06 15:10:46 | ** DENIED ** | | | | | | | | | 1) NOTE: PLEASE INDICATE THE RELEVANT CODES ON PLANS AS | | | REQUIRED. | | | PLEASE SEE THE FOLLOWING WHICH WERE ADOPTED AS OF | | | DECEMBER 8TH, 2006 SHALL BE ON PLANS. | | | 2004 FBC W/ 2006 REVISIONS. | | | 2005 NFPA-70 (NEC). | | | 2003 NFPA-101 | | | | | | 2) NOTE: PLEASE SEE THE TITLE BLOCK INDICATE THE | | | COMMERCIAL WORK BEING DONE BY A DRAFTING FIRM? PLEASE | | | SEE FLORIDA STATUTES 471.003 AS THE SCOPE OF WORK FOR | | | ELECTRICAL AS SHOWN IS REQUIRED TO BE DONE BY AN | | | ENGINEER. PLEASE ALSO SEE THE ABOVE 471.025 AS PLANS | | | ARE REQUIRED TO BE SIGNED, DATED AND SEALED BY A | | | DESIGNER WITH KNOWLEDGE OF ELECTRICAL SYSTEMS AS | | | DESIGNED. | | | | | | 3) NOTE: PLEASE BE SURE THE ADDRESS OF THE BUILDING IS | | | STATED IN THE TITLE BLOCKS AS REQUIRED. PLEASE KNOW AS | | | THE SITE AND LOCATION STILL NEEDS TO BE REVIEWED BY THE | | | ADDRESSING REVIEWER THE BUILDING/STRUCTURE MAY INDEED | | | BE GIVEN A NEW ADDRESS WHICH WOULD NEED TO BE ON | | | PLANS. | | | FAC 61G15-23.002, 61G1-16.004 | | | | | | 4) NOTE: PLEASE SEE MISSING DISCONNECT FOR CU AND AHU. | | | THERE ARE BOXES ON PLANS HOWEVER UNCLEAR IF THESE ARE | | | THE REQUIRED DISCONNECTS. | | | 440.11 | | | | | | 5) NOTE: PLEASE SEE THE LOCATION OF THE NEW DISCONNECT | | | WHICH IS TAPPED FROM THE EXISTING MAIN IS NOT BEING | | | SHOWN TO VERIFY THE TAPPED CONDUCTORS PER 240.21, | | | 240.4, 310.16. | | | | | | 6) NOTE: PLEASE VERIFY THE CONDUCTORS ON THE RISER WITH | | | THAT IF THE CONDUCTORS SHOWN ON THE PARTIAL LOAD | | | CALCULATIONS. | | | PLEASE SEE DIFFERENCES ON THE GROUNDING ELECTRODE | | | CONDUCTOR. | | | PLEASE SEE THE 4/0 ARE BEING SHOWN TO A 60AMP | | | DISCONNECT. | | | PLEASE ALSO VERIFY THE CONDUCTORS FROM THE NEW | | | DISCONNECT TO THE NEW BUILDING AS THESE ARE SHOWN AS | | | #3. | | | THE COMMENT IS FOR THE SIZE OF THE CONDUCTOR WILL NOT | | | FIT UNDER THE LUGS ON THE SIZE OF THE EQUIPMENT AS | | | SHOWN. | | | ** PLEASE SEE OTHER COMMENTS AS THE RISER WILL CHANGE | | | AS SUBMITTED. | | | FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION. | | | | | | 7) NOTE: PLEASE SEE MISSING THE DISCONNECTING MEANS AS | | | THE DETACHED STRUCTURE AS REQUIRED PER 225.31. ( NONE | | | SHOWN ON THE LINE SIDE OF THE TRANSFORMER.) | | | | | | 8) NOTE: PLEASE SEE THE FEEDERS ARE SHOWN TO THE LINE | | | SIDE OF THE TRANSFORMER WHICH CONTAINS A NEUTRAL? | | | PLEASE VERIFY AS THIS IS A SEPARATELY DERIVED SYSTEM. | | | 250.20, 250.30, 250.66 ETC | | | | | | 9) NOTE: PLEASE COMPLETE THE GROUNDING ELECTRODE SYSTEM | | | AND GROUNDING AT THE DETACHED BUILDING PER 250.32 AND | | | ABOVE COMMENT #8. | | | | | | 10) NOTE: PLEASE SHOW THE LOCATION OF ALL SERVICE | | | EQUIPMENT. PLANS DO NOT INDICATE ANY TRANSFORMER SO THE | | | LOCATION CAN NOT BE DETERMINED AT THIS TIME. | | | 240.24, 110.26, 450.9, 450.13 ETC. | | | | | | 11) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR THE NEW | | | PANEL *A* AND LOAD FOR BOTH EXISTING AND NEW. ALL | | | CONTINUOUS LOADS NEED TO BE SHOWN AT 125%. | | | 215.3, 230.42 ETC. | | | PLEASE SEE THE LOADS AS SHOWN ON PLANS WITHOUT THE NEW | | | LOADS ADDED SEEM TO BE VERY CLOSE TO EXCEEDING THE | | | RATING OF THE SERVICE AND EQUIPMENT. | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE | | | EQUIPMENT PER 110.9. | | | FBC 106.1.2 | | | | | | 13) NOTE: PLEASE SUBMIT THE VOLTAGE DROP PER | | | 13-413.1.ABC.1 FOR FEEDERS. PLANS STATE THIS IS | | | REQUIRED HOWEVER CONTAINS NO INFORMATION ON THIS. | | | MAY NOT QUOTE CODE REQUIREMENTS IN LIEU OF DETAIL. | | | | | | 14) NOTE: PLEASE SEE MISSING ENERGY | | | CALCULATIONS/PERFORMANCE CALCULATIONS PER 13-101.1.1 | | | AND TO BE SIGNED, DATED AND SEALED PER 13-101.1.1.1. | | | PLEASE SEE 13-415.1.AB.1.1, 13-415.1.C, 13-415.2 ETC. | | | PLEASE BE SURE ALL DOCUMENTS ARE SIGNED, DATED AND | | | SEALED AS REQUIRED PER 13-103.1.1.1 AND OWNER/AGENT IS | | | SIGNED. | | | | | | 15) NOTE: PLEASE PLACE CONDUCTOR SIZES ON PANEL | | | SCHEDULE AND CORRELATE WITH THE OVER CURRENT PROTECTION | | | AS LISTED ON BRANCH CIRCUITS. | | | 240.4, 310.16, 408.4. | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 16) NOTE: PLEASE SEE MISSING FOOTER STEEL AND POSSIBLE | | | COLD WATER PIPE(WHERE METALLIC). PLEASE SEE THE PERMIT | | | APPLICATION MENTIONS THE SLAB/FOUNDATION IS UNDER A | | | SEPARATE PERMIT. THE FOOTER STEEL IS REQUIRED AND | | | ATTACHMENT MUST BE MADE. | | | 250.50. | | | PLEASE KNOW THAT IF THE SLAB/FOUNDATION PERMIT IS | | | GIVEN, THE ELECTRICAL PERMIT MAY BE DONE SEPARATELY TO | | | ALLEVIATE ANY *CHIPPING* UP OF A POURED FOOTER WITH OUT | | | THIS BEING DONE. | | | | | | 17) NOTE: ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT | | | YET SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW | | | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE | | | AT THIS TIME. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-11-21 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-11-21 |
Time |
12:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-08-30 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-08-30 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2007-08-30 09:09:31 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. PLEASE SHOW ON DRAWING THE SITE PLAN SHOWING | | | STREETS/ROADS AROUND THE SITE WITH NORTH ARROW. | | | 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM | | | 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES. | | | PHONE# 494-1040 | | | 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, | | | 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST | | | FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS. | | | 4. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE | | | DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL | | | PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT, | | | LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE | | | THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED | | | IN STORM WATER QUALITY CALCULATIONS. | | | 6. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM | | | WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE | | | SHOW DETAIL OF THE CONTROL STRUCTURESWITH | | | ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON | | | DRAWINGS, CALCULATION FOR EXFILTRATION TRENCHES, PLEASE | | | SHOW DRY DETENTION/WET DETENTION AREAS IN STORM WATER | | | CALS. | | | 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN. | | | 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM | | | WATER QUALITY CALCULATIONS, | | | 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT | | | FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE | | | SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST & | | | PARTICLES. | | | 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
|
Date |
2008-02-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-20 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-20 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2008-02-20 16:45:26 | *****REVISION APPROVED***** | | | | | | | | | REVISED PLAN SHEET A-1 STAMPED, INITIALED, AND DATED. | | | | | | | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-28 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-28 |
Time |
10:55 |
Sent To |
B |
|
| Notes |
| 2007-12-28 11:07:52 | *****APPROVED***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN | | | ADDRESSED;PLAN SHEET A-1 STAMPED, INITIALED, AND | | | DATED. | | | | | | | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-26 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-26 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2007-11-26 13:39:50 | *****UNSAT***** | | | | | | THE FOLLOWING COMMENTS FORM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 05.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR | | | HINDER EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR | | | VICINITY THEREOF (INCLUDING FIRE LANES).ADD THIS | | | COMMENT TO AN APPROPIATE PLAN SHEET | | | | | | 06.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | | COMMENT TO AN APPROPIATE PLAN SHEET | | | | | | | | | 10.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR | | | THE EXITS, AISLE CORRIDORS, AND ALL OTHER SPACES IN | | | TERRMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY | | | INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II. | | | PLEASE SPECIFY | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDIACTING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-14 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-14 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2007-09-14 17:47:50 | *****DENIED***** | | | | | | | | | | | | 01.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE | | | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 03.FIRE DEPARTMENT ACCESS ROAD TO THIS STRUCTURE | | | SHALLBE CABLE OF SUPPORTING THE IMPOSED LOADS OF FIRE | | | APPARATUS AND SHALL BE PROVIDED WITH A SURFACE SUITABLE | | | FOR ALL-WEATHER DRIVING CAPABILITIES. | | | | | | 04.FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN | | | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT THAN LESS THAN | | | 13 FEET 6 INCHES. | | | | | | 05.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR | | | HINDER EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR | | | VICINITY THEREOF (INCLUDING FIRE LANES). | | | | | | 06.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 07.INDICATE THE OCCUPANCY TYPE.THE APPLICATION HAS | | | THE CONSTRUCTION OF AN UTILITY BUILDING,WHEREAS PLAN | | | SHEET A-1 SHOWS THE PROPOSED BUIDLING AS A TEACHING | | | BUILDING. | | | | | | 08.PROVIDE OCCUPANT LOAD AS IN NUMBER OF PERSONS FOR | | | WHOM MEANS OF EGRESS ARE REQUIRED BASED UPON THE | | | CHARACTERISTIC OF THE USE OF THE TENANT SPACE. | | | | | | 09.PROVIDE A LIFE SAFETY PLAN SHEET INDICATING TRAVEL | | | DISTANCES TO EXITS, EXIT LIGHTS, EMERGENCY LIGHTING, | | | AND THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S). | | | | | | 10.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR | | | THE EXITS, AISLE CORRIDORS, AND ALL OTHER SPACES IN | | | TERRMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY | | | INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II. | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDIACTING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-02-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-04 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-04 |
Time |
14:36 |
Sent To |
E |
|
| Notes |
| 2008-02-04 14:37:08 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-29 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-29 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2008-02-08 09:30:57 | 2/8/08--MOVED TO "COMM" BD#28 | | 2008-01-29 09:42:57 | TO "COMM" BD#17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-18 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-18 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2007-12-18 10:57:39 | TO "COMM" BD#28 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-25 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-25 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2007-11-13 09:38:03 | TO "COMM" BD#64 | | 2007-10-25 14:49:22 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-14 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-17 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2007-07-27 11:50:26 | TO "COMM" BD#25 | | 2007-07-17 10:12:42 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
P |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-26 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-26 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2007-11-26 17:48:43 | PASS PENDING ACCEPTANCE OF ENERGY CALCULATIONS BY ALL | | | INTERESTED TRADES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-02-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-16 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-16 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-26 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-26 |
Time |
16:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-06 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-05 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2007-08-06 08:43:52 | ---------------DENIED----------------- | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PROVIDE ENERGY CALCULATIONS PER FBC 13-101.1.1 AND | | | FBC 106.3.5.1.4 | | | | | | 2. PROVIDE MEANS OF VENTILATION AND PROVIDE | | | CALCULATIONS BASED ON FBC,M SEC 402 OR 403 PER FBC | | | 106.3.5.1.4 | | | | | | 3. ELECTRICAL PLAN SHOWS CENTRAL A/C SYSTEM. SHOW ALL | | | COMPONENTS, INCLUDING EQUIPMENT SCHEDULE, AND | | | DEMONSTRATE COMPLIANCE WITH FBC,M CHAPTERS 3 AND 6 AS | | | WELL AS FBC CH.13 PER FBC 106.3.5.1.4 | | | | | | 4. MECHANICAL EXHAUST IS REQUIRED FOR TOILET ROOMS PER | | | FBC,M TABLE 403.3. | | | | | | NOTE: A COMPLETE REVIEW IS NOT POSIIBLE AT THIS TIME | | | DUE TO MISSING INFORMATION. ADDITIONAL COMMENTS ARE | | | POSSIBLE ON THE NEXT REVIEW. PROVIDE ALL INFORMATION | | | REQUIRED BY FBC 106.3.5.1.4. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-10 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-10 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2007-12-10 07:52:09 | PASSED/PROVISO--11-4.16.5 FLUSH CONTROLS SHALL BE | | | ON THE WIDE SIDE OF THE TOILET. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-01 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-01 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2007-09-01 16:19:46 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SUBMIT INFORMATION ON OCCUPANCY AND CODE DESIGN ON | | | PLANS. (CODE FBC-2004 W/2005 & 2006 AMENDMENTS) | | | SECTIONS 106.1.1 & 110..1.2(7)(8). | | | | | | 2. SEE BUILDING COMMENT #3 CONCERNING PKA DRAFTING AND | | | WORKING OUT OF THE SCOPE OF LICENSE. | | | | | | 3. THE OCCUPANCY MAY REQUIRE A DRINKING FOUNTAIN AND A | | | SERVICE SINK PER TABLE 403.1. WHEN OCCUPANCY DECLARED | | | MORE INFORMATION MAY BE REQUIRED. | | | | | | 4. SHTS A-1 & A-2 SHOW COMPLIANCE FOR THE ACCESSIBLE | | | TOILET ROOM WITH THE FOLLOWING: | | | __FOR W/C'S | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.5 FLUSH CONTROLS | | | __FOR LAVS | | | A. 11-4.19.5 FAUCETS | | | | | | 5. SHT E-1 SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE | | | SIZES, VALVES & (IF REQUIRED) WATER HAMMER ARRESTORS. | | | SECTIONS 106.3.5.1.3(3)(10)(13) & 604.9. | | | | | | 6. DEPENDNING ON OCCUPANCY AND REQUIREMENT FOR A | | | SERVICE SINK, A HOT WATER SUPPLY MAY BE REQUIRED PER | | | SECTION 607.1. | | | | | | 7. WHEN RESUBMITTING PLEASE INDICATE ALL REVISIONS & | | | REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING COMMENT RESPONSES, | | | DESCRIPTION OF THE REVISION, IDENTIFICATION OF THE | | | SHEET OR SPECIFICATION PAGE WHERE CHANGE CAN BE FOUND | | | WILL HELLP TO EXPEDITE YOUR PERMIT. THANK YOU IN | | | ADVANCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-01-31 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-01-31 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2008-01-31 15:51:20 | REVISION TO REMOVE DOOR AND SIDEWALK, ADD HEDGE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-20 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-20 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2007-12-20 16:56:47 | PER ERIC SCHNEIDER |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-10-29 |
Time |
18:54 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-10-29 |
Time |
18:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-09-06 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-08-06 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2007-09-06 19:02:24 | FAILED | | | | | | 1) ACCESSABLE ROUTE NOT SHOWN ON PLANS. | | | | | | 2) NOTE THE REVISED PLANS SUBMITTED FOR THE MINOR | | | AMENDMENT TO SHOW THE ACCESSABLE ROUTE SHOW COCO PLUMS | | | IN THE 5 FOOT WIDE 4" CONC. WALKWAY.THE PLANTING BED | | | NEEDS TO BE CLEARLY SEPERATED FROM THE ACCESABELE ROUTE | | | AND IRRIGATION FOR THE PLANTING BEDS NEEDS TO BE | | | SHOWN. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. | | 2007-08-06 16:11:19 | REVIEW ON HOLD DUE TO PENDING MINOR AMENDMENT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|