Plan Review Details - Permit 07070433
Plan Review Stops For Permit 07070433
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2008-01-03 Cont ID  
Sent By jwitmer Date 2008-01-03 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2008-01-03 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-02-21 Cont ID  
Sent By jwitmer Date 2008-02-21 Time 07:32 Rev Time 0.77
Received By jwitmer Date 2008-02-21 Time 07:32 Sent To PC
Notes
2008-02-21 07:32:41REV DATED 1-23-08

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-03 Cont ID  
Sent By jwitmer Date 2008-01-03 Time 09:53 Rev Time 2.22
Received By jwitmer Date 2008-01-03 Time 09:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-03 Cont ID  
Sent By jwitmer Date 2008-01-03 Time 10:01 Rev Time 0.00
Received By jwitmer Date 2008-01-03 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By jwitmer Date 2007-11-19 Time 10:53 Rev Time 0.77
Received By jwitmer Date 2007-11-19 Time 10:52 Sent To  
Notes
2007-11-19 10:54:30SEE FOUNDATION PERMIT FOR NOA AND IMPACT FEES.07070436.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-16 Cont ID  
Sent By jwitmer Date 2007-11-16 Time 16:44 Rev Time 2.22
Received By jwitmer Date 2007-11-16 Time 16:44 Sent To  
Notes
2007-11-16 16:45:141401 BRANYWINE RD
 TRAINING FACILITY
 07070433 2ND REV
 NOV.16, 2007
 BUILDING PLAN REVIEW
 PERMIT: 07070433
 ADD: 1401 BRANYWINE RD
 CONT: PURDY CONSTRUCTION
 TEL: (561)718-8080
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE NOTICE OF COMMENCEMENT SUBMITTED FOR THE TRAINING
 CENTER IS OVER 90 DAY OLD, IT WILL NEED TO BE
 RE-RECORDED.FL S S 713.13NOTICE OF COMMENCEMENT, TO
 BE FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) COMPLIED
 B) COMPLIED.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. AS NOTED ON SHEET A-1, THIS STRUCTURE IS
 DESIGNED AS A TYPE II-B BUILDING. THE CITY SHALL REVIEW
 THE STRUCTURE AS DECLARED BY THE DESIGN PROFESSIONAL.
 THE MINIMUM BUILDING TYPE BY CODE IS A TYPE V-B BY
 CODE.
 DECLARING THE BUILDING A TYPE II-B THE DESIGNER NEEDS
 TO RATE THE ROOFING ASSEMBLY AS STATED IN TABLE 601
 FOOTNOTE ( C ) (2) FIRE RETARDANT TREATED WOOD SHALL BE
 USED IN ALL GIRDERS, TRUSSES AND ROOF SHEATHING.
  
 D-G) COMPLIED.
  
 5-12) COMPLIED.
  
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-01 Cont ID  
Sent By jwitmer Date 2007-08-01 Time 10:15 Rev Time 2.22
Received By jwitmer Date 2007-08-01 Time 09:58 Sent To  
Notes
2007-08-01 12:38:541401 BRANYWINE RD- 07070433 1ST REV
  
 BUILDING PLAN REVIEW
 PERMIT: 07070433
 ADD: 1401 BRANYWINE RD
 CONT: PURDY CONSTRUCTION
 TEL: (561)718-8080
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PKA DRAFTING PLEASE SEE ATTACHMENT THAT YOU ARE
 WORKING OUT OF THE SCOPE OF YOUR LICENSE. SEE FL CASE
 NO 03-0489 1 SET OF PLANS WILL BE KEPT AND SENT TO THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION,
 BOARD OF ENGINEERS.
  
 4) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 5) PLEASE PROVIDE THE FINISH FLOOR ELEVATION, THIS AREA
 IS A ?B? ZONE LOMR REQUIRING A FINISH FLOOR ELEVATION
 OF 16?-6?.
  
 6) PLEASE PROVIDE SOILS REPORT. 1802.2.1 QUESTIONABLE
 SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) SHEET A-3 MONOLITHIC SLAB, PLANS INDICATE THE USE OF
 WIRE MESH:CONCRETE SLABS ON GROUND CONTAINING 6X6
 W1.4 ? W1.4 WELDED WIRE REINFORCEMENT FABRIC LOCATED IN
 THE MIDDLE TO THE UPPER ONE-THIRD OF THE SLAB. WELDED
 WIRE REINFORCEMENT FABRIC SHALL BE SUPPORTED WITH
 APPROVED MATERIALS OR SUPPORTS AT SPACINGS NOT TO
 EXCEED 3 FEET (914 MM) OR IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WELDED PLAIN WIRE
 REINFORCEMENT FABRIC FOR CONCRETE SHALL CONFORM TO ASTM
 A 185, STANDARD SPECIFICATION FOR STEEL WELDED WIRE
 REINFORCEMENT FABRIC, PLAIN, FOR CONCRETE REINFORCEMENT
 .
  
 8)SHEET A-3 PLANS INDICATE THE USE OF A HIPPED ROOF
 WITH WOOD TRUSSES: 1203.2 ATTIC SPACES: THE NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN 1 / 150 OF THE
 AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF THE
 REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
  
 9) 1209.2 ATTIC SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 10) DISCREPANCY ON SHEET A-3 DETAILS 1& 3 ONE APPEARS
 TO BE ROOF TILE AS THE PRODUCT APPROVAL SUBMITTED
 WHEREAS DETAIL # 1 INDICATES THE USE OF SHINGLES.
  
 11) PLANS INDICATE THE USE OF ?? DRYWALL ON THE CEILING
 PLEASE INDICATE THE DIRECTION OF THE BOARD, TYPE OF
 FASTENERS TO BE USED, AND LENGTH. TABLE 2508.1-
 GA-216.
  
 12) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS MISSING REPORTS ARE AS
 FOLLOWS:
 A) OVERHEAD OR COIL TYPE DOOR- NO REPORT SUBMITTED
 B) EXTERIOR METAL SWING DOOR- CURRIES REQUIRES FL COVER
 SHEET
 C) ROOFING ASSEMBLIES
 UNDERLAYMENTS- NO PRODUCT APPROVALS WERE SUBMITTED
 ROOF TILE- HANSON , REQUIRES FL COVER SHEET, ALSO
 HIGHLIGHT WHAT TYPE OF FASTENER WILL BE
 USED. PROVIDE WHAT TYPE OFHIP AND RIDGE BOARD TO
 BE USED AND TYPE OF FASTENER, 1507.3.7 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN
 ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH
 FRSA/TRI 07320 INSTALLATION MANUAL.
  
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/TRI 07320.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-02-05 Cont ID  
Sent By dpalmer Date 2008-02-05 Time 17:16 Rev Time 0.00
Received By dpalmer Date 2008-02-05 Time 17:16 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2007-12-19 Time   Rev Time 0.00
Received By dpalmer Date 2007-12-19 Time 08:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-19 Cont ID  
Sent By dpalmer Date 2007-11-19 Time 14:54 Rev Time 0.00
Received By dpalmer Date 2007-11-19 Time 12:23 Sent To  
Notes
2007-11-19 14:55:00** DENIED 2ND REVIEW **
  
 ** AS STATED ON PREVIOUS REVIEW, PLEASE SEE THERE ARE
 SOME COMMENTS FROM PREVIOUS REVIEW AND SOME NEW
 COMMENTS BASED ON INFORMATION NOW BEING SUBMITTED.
  
 1) NOTE: PLEASE SHOW ALL LOCATIONS OF SERVICE EQUIPMENT
 ON PLANS FOR LOCATIONS.
 CAN NOT VERIFY ITEMS AT THIS TIME FOR TAPPED
 CONDUCTORS, DISCONNECTING MEANS, CLEARANCES ETC.
 240.21, 110.26, 240.24, 225.31ETC
 AS THE LOCATION OF TRANSFORMER AND MAIN BREAKER PANEL
 AT THIS DETACHED STRUCTURE FROM SERVICE LOCATION IS NOT
 SHOWN WE ARE UNABLE TO CONFIRM LOCATIONS.
  
 2) NOTE: PLEASE SEE THE PREVIOUS NOTES FOR DISCONNECTS
 REQUIRED FOR A/C SYSTEM AHU AND CU>
 PLEASE SEE THERE ARE BOXES SHOWN ON PLANS WITH CIRCUIT
 NUMBERS BUT NO DISCONNECTS PER 440.11.
  
 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 AT THIS DETACHED STRUCTURE PER 250.50, 250.32
  
 4) NOTE: PLEASE CLARIFY CONTINUOUS LOADS AND WHERE
 THESE ARE SHOWN AT 125%.
 NO LOAD CALCULATIONS ACTUALLY SHOWN.
 215.3, 230.42 ETC.
 220.12, 220.14, 220.42, 220.44 ETC.
  
 5) NOTE: PLEASE SEE RISER IS STILL INDICATING A NEUTRAL
 ON THE LINE SIDE OF THE TRANSFORMER. PLEASE EXPLAIN AS
 THIS TRANSFORMER IS A SEPARATELY DERIVED SYSTEM AND
 CREATES ITS OWN NEUTRAL.
 250.6, 250.24 ETC.
  
 6) NOTE: PLEASE SEE THE METHOD *A* CALCULATIONS NOW
 SUBMITTED ARE SIGNED AND SEALED BY AN ARCHITECT WHICH
 IS NOT THE ARCHITECT OR ENGINEER OF RECORD.
 PLEASE SEE THE CERTIFICATION SHEET IS REQUIRED TO BE
 COMPLETED WITH ALL INFORMATION FOR RESPONSIBLE
 DESIGNERS.
 PLEASE ALSO SEE MISSING OWNER AGENT.
 FBC 13-101, FS 471.025
  
 7) NOTE: PLEASE SEE THE LIGHTING AS SHOWN ON PLANS DOES
 NOT CORRELATE WITH THE LIGHTING ON THE INPUT DATA
 REPORT.
 PLEASE CORRELATE AND SUBMIT.
 FBC 13-415.1.A, 13-415.2
  
 8) NOTE: PLEASE SEE 13-413.1.ABC.2.2 AND PLACE NOTE ON
 PLANS ACCORDINGLY.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By dpalmer Date 2007-08-06 Time 15:10 Rev Time 0.00
Received By dpalmer Date 2007-08-06 Time 12:52 Sent To  
Notes
2007-08-06 15:10:46** DENIED **
  
  
 1) NOTE: PLEASE INDICATE THE RELEVANT CODES ON PLANS AS
 REQUIRED.
 PLEASE SEE THE FOLLOWING WHICH WERE ADOPTED AS OF
 DECEMBER 8TH, 2006 SHALL BE ON PLANS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE TITLE BLOCK INDICATE THE
 COMMERCIAL WORK BEING DONE BY A DRAFTING FIRM? PLEASE
 SEE FLORIDA STATUTES 471.003 AS THE SCOPE OF WORK FOR
 ELECTRICAL AS SHOWN IS REQUIRED TO BE DONE BY AN
 ENGINEER. PLEASE ALSO SEE THE ABOVE 471.025 AS PLANS
 ARE REQUIRED TO BE SIGNED, DATED AND SEALED BY A
 DESIGNER WITH KNOWLEDGE OF ELECTRICAL SYSTEMS AS
 DESIGNED.
  
 3) NOTE: PLEASE BE SURE THE ADDRESS OF THE BUILDING IS
 STATED IN THE TITLE BLOCKS AS REQUIRED. PLEASE KNOW AS
 THE SITE AND LOCATION STILL NEEDS TO BE REVIEWED BY THE
 ADDRESSING REVIEWER THE BUILDING/STRUCTURE MAY INDEED
 BE GIVEN A NEW ADDRESS WHICH WOULD NEED TO BE ON
 PLANS.
 FAC 61G15-23.002, 61G1-16.004
  
 4) NOTE: PLEASE SEE MISSING DISCONNECT FOR CU AND AHU.
 THERE ARE BOXES ON PLANS HOWEVER UNCLEAR IF THESE ARE
 THE REQUIRED DISCONNECTS.
 440.11
  
 5) NOTE: PLEASE SEE THE LOCATION OF THE NEW DISCONNECT
 WHICH IS TAPPED FROM THE EXISTING MAIN IS NOT BEING
 SHOWN TO VERIFY THE TAPPED CONDUCTORS PER 240.21,
 240.4, 310.16.
  
 6) NOTE: PLEASE VERIFY THE CONDUCTORS ON THE RISER WITH
 THAT IF THE CONDUCTORS SHOWN ON THE PARTIAL LOAD
 CALCULATIONS.
 PLEASE SEE DIFFERENCES ON THE GROUNDING ELECTRODE
 CONDUCTOR.
 PLEASE SEE THE 4/0 ARE BEING SHOWN TO A 60AMP
 DISCONNECT.
 PLEASE ALSO VERIFY THE CONDUCTORS FROM THE NEW
 DISCONNECT TO THE NEW BUILDING AS THESE ARE SHOWN AS
 #3.
 THE COMMENT IS FOR THE SIZE OF THE CONDUCTOR WILL NOT
 FIT UNDER THE LUGS ON THE SIZE OF THE EQUIPMENT AS
 SHOWN.
 ** PLEASE SEE OTHER COMMENTS AS THE RISER WILL CHANGE
 AS SUBMITTED.
 FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 7) NOTE: PLEASE SEE MISSING THE DISCONNECTING MEANS AS
 THE DETACHED STRUCTURE AS REQUIRED PER 225.31. ( NONE
 SHOWN ON THE LINE SIDE OF THE TRANSFORMER.)
  
 8) NOTE: PLEASE SEE THE FEEDERS ARE SHOWN TO THE LINE
 SIDE OF THE TRANSFORMER WHICH CONTAINS A NEUTRAL?
 PLEASE VERIFY AS THIS IS A SEPARATELY DERIVED SYSTEM.
 250.20, 250.30, 250.66 ETC
  
 9) NOTE: PLEASE COMPLETE THE GROUNDING ELECTRODE SYSTEM
 AND GROUNDING AT THE DETACHED BUILDING PER 250.32 AND
 ABOVE COMMENT #8.
  
 10) NOTE: PLEASE SHOW THE LOCATION OF ALL SERVICE
 EQUIPMENT. PLANS DO NOT INDICATE ANY TRANSFORMER SO THE
 LOCATION CAN NOT BE DETERMINED AT THIS TIME.
 240.24, 110.26, 450.9, 450.13 ETC.
  
 11) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR THE NEW
 PANEL *A* AND LOAD FOR BOTH EXISTING AND NEW. ALL
 CONTINUOUS LOADS NEED TO BE SHOWN AT 125%.
 215.3, 230.42 ETC.
 PLEASE SEE THE LOADS AS SHOWN ON PLANS WITHOUT THE NEW
 LOADS ADDED SEEM TO BE VERY CLOSE TO EXCEEDING THE
 RATING OF THE SERVICE AND EQUIPMENT.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT PER 110.9.
 FBC 106.1.2
  
 13) NOTE: PLEASE SUBMIT THE VOLTAGE DROP PER
 13-413.1.ABC.1 FOR FEEDERS. PLANS STATE THIS IS
 REQUIRED HOWEVER CONTAINS NO INFORMATION ON THIS.
 MAY NOT QUOTE CODE REQUIREMENTS IN LIEU OF DETAIL.
  
 14) NOTE: PLEASE SEE MISSING ENERGY
 CALCULATIONS/PERFORMANCE CALCULATIONS PER 13-101.1.1
 AND TO BE SIGNED, DATED AND SEALED PER 13-101.1.1.1.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.1.C, 13-415.2 ETC.
 PLEASE BE SURE ALL DOCUMENTS ARE SIGNED, DATED AND
 SEALED AS REQUIRED PER 13-103.1.1.1 AND OWNER/AGENT IS
 SIGNED.
  
 15) NOTE: PLEASE PLACE CONDUCTOR SIZES ON PANEL
 SCHEDULE AND CORRELATE WITH THE OVER CURRENT PROTECTION
 AS LISTED ON BRANCH CIRCUITS.
 240.4, 310.16, 408.4.
 FBC 106.3.5.1.2, 106.1.2
  
 16) NOTE: PLEASE SEE MISSING FOOTER STEEL AND POSSIBLE
 COLD WATER PIPE(WHERE METALLIC). PLEASE SEE THE PERMIT
 APPLICATION MENTIONS THE SLAB/FOUNDATION IS UNDER A
 SEPARATE PERMIT. THE FOOTER STEEL IS REQUIRED AND
 ATTACHMENT MUST BE MADE.
 250.50.
 PLEASE KNOW THAT IF THE SLAB/FOUNDATION PERMIT IS
 GIVEN, THE ELECTRICAL PERMIT MAY BE DONE SEPARATELY TO
 ALLEVIATE ANY *CHIPPING* UP OF A POURED FOOTER WITH OUT
 THIS BEING DONE.
  
 17) NOTE: ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT
 YET SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-11-21 Cont ID  
Sent By rchokshi Date 2007-11-21 Time 12:42 Rev Time 0.00
Received By rchokshi Date 2007-11-21 Time 12:42 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By rchokshi Date 2007-08-30 Time 09:10 Rev Time 0.00
Received By rchokshi Date 2007-08-30 Time 08:59 Sent To  
Notes
2007-08-30 09:09:31***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING THE SITE PLAN SHOWING
 STREETS/ROADS AROUND THE SITE WITH NORTH ARROW.
 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS.
 4. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 6. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE
 SHOW DETAIL OF THE CONTROL STRUCTURESWITH
 ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON
 DRAWINGS, CALCULATION FOR EXFILTRATION TRENCHES, PLEASE
 SHOW DRY DETENTION/WET DETENTION AREAS IN STORM WATER
 CALS.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS,
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status   Date 2008-02-20 Cont ID  
Sent By mawillia Date 2008-02-20 Time 16:57 Rev Time 0.00
Received By mawillia Date 2008-02-20 Time 16:39 Sent To  
Notes
2008-02-20 16:45:26*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 11:08 Rev Time 0.00
Received By mawillia Date 2007-12-28 Time 10:55 Sent To B
Notes
2007-12-28 11:07:52*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEET A-1 STAMPED, INITIALED, AND
 DATED.
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-26 Cont ID  
Sent By mawillia Date 2007-11-26 Time 13:57 Rev Time 0.00
Received By mawillia Date 2007-11-26 Time 12:23 Sent To  
Notes
2007-11-26 13:39:50*****UNSAT*****
  
 THE FOLLOWING COMMENTS FORM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 05.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).ADD THIS
 COMMENT TO AN APPROPIATE PLAN SHEET
  
 06.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TO AN APPROPIATE PLAN SHEET
  
  
 10.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THE EXITS, AISLE CORRIDORS, AND ALL OTHER SPACES IN
 TERRMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
 PLEASE SPECIFY
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDIACTING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By mawillia Date 2007-09-14 Time 18:02 Rev Time 0.00
Received By mawillia Date 2007-09-14 Time 16:56 Sent To  
Notes
2007-09-14 17:47:50*****DENIED*****
  
  
  
 01.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03.FIRE DEPARTMENT ACCESS ROAD TO THIS STRUCTURE
 SHALLBE CABLE OF SUPPORTING THE IMPOSED LOADS OF FIRE
 APPARATUS AND SHALL BE PROVIDED WITH A SURFACE SUITABLE
 FOR ALL-WEATHER DRIVING CAPABILITIES.
  
 04.FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT THAN LESS THAN
 13 FEET 6 INCHES.
  
 05.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 06.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 07.INDICATE THE OCCUPANCY TYPE.THE APPLICATION HAS
 THE CONSTRUCTION OF AN UTILITY BUILDING,WHEREAS PLAN
 SHEET A-1 SHOWS THE PROPOSED BUIDLING AS A TEACHING
 BUILDING.
  
 08.PROVIDE OCCUPANT LOAD AS IN NUMBER OF PERSONS FOR
 WHOM MEANS OF EGRESS ARE REQUIRED BASED UPON THE
 CHARACTERISTIC OF THE USE OF THE TENANT SPACE.
  
 09.PROVIDE A LIFE SAFETY PLAN SHEET INDICATING TRAVEL
 DISTANCES TO EXITS, EXIT LIGHTS, EMERGENCY LIGHTING,
 AND THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S).
  
 10.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THE EXITS, AISLE CORRIDORS, AND ALL OTHER SPACES IN
 TERRMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDIACTING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-04 Cont ID  
Sent By adarroug Date 2008-02-04 Time 14:36 Rev Time 0.00
Received By adarroug Date 2008-02-04 Time 14:36 Sent To E
Notes
2008-02-04 14:37:08TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 09:41 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 09:41 Sent To  
Notes
2008-02-08 09:30:572/8/08--MOVED TO "COMM" BD#28
2008-01-29 09:42:57TO "COMM" BD#17

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-18 Cont ID  
Sent By adarroug Date 2007-12-18 Time 10:57 Rev Time 0.00
Received By adarroug Date 2007-12-18 Time 10:57 Sent To  
Notes
2007-12-18 10:57:39TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 14:49 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 14:49 Sent To  
Notes
2007-11-13 09:38:03TO "COMM" BD#64
2007-10-25 14:49:22WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-14 Cont ID  
Sent By mawillia Date 2007-09-14 Time 16:56 Rev Time 0.00
Received By mawillia Date 2007-07-17 Time 10:09 Sent To  
Notes
2007-07-27 11:50:26TO "COMM" BD#25
2007-07-17 10:12:42WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2007-11-26 Cont ID  
Sent By rregueir Date 2007-11-26 Time 17:48 Rev Time 0.00
Received By rregueir Date 2007-11-26 Time 17:27 Sent To  
Notes
2007-11-26 17:48:43PASS PENDING ACCEPTANCE OF ENERGY CALCULATIONS BY ALL
 INTERESTED TRADES.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 10:25 Rev Time 0.00
Received By rregueir Date 2008-02-16 Time 10:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-26 Cont ID  
Sent By rregueir Date 2007-11-26 Time 16:57 Rev Time 0.00
Received By rregueir Date 2007-11-26 Time 16:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By rregueir Date 2007-08-06 Time 08:43 Rev Time 0.00
Received By rregueir Date 2007-08-05 Time 15:43 Sent To  
Notes
2007-08-06 08:43:52---------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE ENERGY CALCULATIONS PER FBC 13-101.1.1 AND
 FBC 106.3.5.1.4
  
 2. PROVIDE MEANS OF VENTILATION AND PROVIDE
 CALCULATIONS BASED ON FBC,M SEC 402 OR 403 PER FBC
 106.3.5.1.4
  
 3. ELECTRICAL PLAN SHOWS CENTRAL A/C SYSTEM. SHOW ALL
 COMPONENTS, INCLUDING EQUIPMENT SCHEDULE, AND
 DEMONSTRATE COMPLIANCE WITH FBC,M CHAPTERS 3 AND 6 AS
 WELL AS FBC CH.13 PER FBC 106.3.5.1.4
  
 4. MECHANICAL EXHAUST IS REQUIRED FOR TOILET ROOMS PER
 FBC,M TABLE 403.3.
  
 NOTE: A COMPLETE REVIEW IS NOT POSIIBLE AT THIS TIME
 DUE TO MISSING INFORMATION. ADDITIONAL COMMENTS ARE
 POSSIBLE ON THE NEXT REVIEW. PROVIDE ALL INFORMATION
 REQUIRED BY FBC 106.3.5.1.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-10 Cont ID  
Sent By kstevens Date 2007-12-10 Time 07:50 Rev Time 0.00
Received By kstevens Date 2007-12-10 Time 07:43 Sent To  
Notes
2007-12-10 07:52:09PASSED/PROVISO--11-4.16.5 FLUSH CONTROLS SHALL BE
 ON THE WIDE SIDE OF THE TOILET.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-01 Cont ID  
Sent By kstevens Date 2007-09-01 Time 15:59 Rev Time 0.00
Received By kstevens Date 2007-09-01 Time 15:59 Sent To  
Notes
2007-09-01 16:19:46DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SUBMIT INFORMATION ON OCCUPANCY AND CODE DESIGN ON
 PLANS. (CODE FBC-2004 W/2005 & 2006 AMENDMENTS)
 SECTIONS 106.1.1 & 110..1.2(7)(8).
  
 2. SEE BUILDING COMMENT #3 CONCERNING PKA DRAFTING AND
 WORKING OUT OF THE SCOPE OF LICENSE.
  
 3. THE OCCUPANCY MAY REQUIRE A DRINKING FOUNTAIN AND A
 SERVICE SINK PER TABLE 403.1. WHEN OCCUPANCY DECLARED
 MORE INFORMATION MAY BE REQUIRED.
  
 4. SHTS A-1 & A-2 SHOW COMPLIANCE FOR THE ACCESSIBLE
 TOILET ROOM WITH THE FOLLOWING:
 __FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 __FOR LAVS
 A. 11-4.19.5 FAUCETS
  
 5. SHT E-1 SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE
 SIZES, VALVES & (IF REQUIRED) WATER HAMMER ARRESTORS.
 SECTIONS 106.3.5.1.3(3)(10)(13) & 604.9.
  
 6. DEPENDNING ON OCCUPANCY AND REQUIREMENT FOR A
 SERVICE SINK, A HOT WATER SUPPLY MAY BE REQUIRED PER
 SECTION 607.1.
  
 7. WHEN RESUBMITTING PLEASE INDICATE ALL REVISIONS &
 REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING COMMENT RESPONSES,
 DESCRIPTION OF THE REVISION, IDENTIFICATION OF THE
 SHEET OR SPECIFICATION PAGE WHERE CHANGE CAN BE FOUND
 WILL HELLP TO EXPEDITE YOUR PERMIT. THANK YOU IN
 ADVANCE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-01-31 Cont ID  
Sent By eschneid Date 2008-01-31 Time 15:50 Rev Time 0.00
Received By eschneid Date 2008-01-31 Time 15:50 Sent To  
Notes
2008-01-31 15:51:20REVISION TO REMOVE DOOR AND SIDEWALK, ADD HEDGE.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-20 Cont ID  
Sent By choops Date 2007-12-20 Time 16:56 Rev Time 0.00
Received By choops Date 2007-12-20 Time 16:56 Sent To  
Notes
2007-12-20 16:56:47PER ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-29 Cont ID  
Sent By eschneid Date 2007-10-29 Time 18:54 Rev Time 0.00
Received By eschneid Date 2007-10-29 Time 18:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By eschneid Date 2007-09-06 Time 18:58 Rev Time 0.00
Received By eschneid Date 2007-08-06 Time 16:10 Sent To  
Notes
2007-09-06 19:02:24FAILED
  
 1) ACCESSABLE ROUTE NOT SHOWN ON PLANS.
  
 2) NOTE THE REVISED PLANS SUBMITTED FOR THE MINOR
 AMENDMENT TO SHOW THE ACCESSABLE ROUTE SHOW COCO PLUMS
 IN THE 5 FOOT WIDE 4" CONC. WALKWAY.THE PLANTING BED
 NEEDS TO BE CLEARLY SEPERATED FROM THE ACCESABELE ROUTE
 AND IRRIGATION FOR THE PLANTING BEDS NEEDS TO BE
 SHOWN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
2007-08-06 16:11:19REVIEW ON HOLD DUE TO PENDING MINOR AMENDMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.