Plan Review Details - Permit 07070372
Plan Review Stops For Permit 07070372
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-08-08 Cont ID  
Sent By mperson Date 2007-08-08 Time 08:28 Rev Time 0.33
Received By mperson Date 2007-08-08 Time 08:28 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-30 Cont ID  
Sent By mperson Date 2007-07-30 Time 15:34 Rev Time 0.45
Received By mperson Date 2007-07-30 Time 15:34 Sent To PC
Notes
2007-07-30 16:00:32DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE CORRESPONDING LENGTHS OF THE CUT SECTIONS ARE
 NOT INDICATED ON THE SUBMITTED ISOMETRIC. PLEASE DO
 THIS ON THE RESUBMITTED ISOMETRIC TO VERIFY THE LONGEST
 LENGTH (TOTAL DEVELOPED LENGTH) OF THE GAS SYSTEM.
  
 2. PLEASE INDICATE THETYPE OF GAS, (LP OR NATURAL)
 ON THE RESUBMITTED ISOMETRIC.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM. PLEASE SEE
 ATTACHED SEARCH CRITERIA INDICATING EXISTING GAS.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE SUBMIT MANUFACTURER SHEETS WITH THE
 FOLLOWING INFORMATION, BTU LOAD AND LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL):
  
 A} NEW COOKTOP
  
 B} IF GAS SYSTEM IS 2 PSI, PLEASE SUBMIT SHEETS FOR MP
 REGULATORS.
  
 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]