| 2007-07-26 10:40:45 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3)FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 4) SPECIFY THE TRUSS BOTTOM CORD LIVE LOAD ON THE |
| | PLANS. TABLE R301.5 REQUIRES 10 PSF FOR ATTICS WITHOUT |
| | STORRAGE AND 20 PSF FOR ATTICS WITH STORAGE. |
| | |
| | 5) THE WALL SECTION ON A1.2 SPECIFIES 8" MINIMUM ABOVE |
| | GRADE. WITH THE 18" FOOTER, THIS LEAVES 10" FROM GRADE |
| | TO THE BOTTOM OF THE FOOTER. SEE FBC R403.1.4 MINIMUM |
| | DEPTH. |
| | ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 |
| | INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| | |
| | 6) SPECIFY ALL NEW WINDOW AND DOOR TYPES AND SIZES ON |
| | THE PLANS. |
| | |
| | 7) AT LEAST ONE WINDOW IN EVERY SLEEPING ROOM IS |
| | REQUIRED TO COMPLY WITH R310.1 FOR EMERGENCY ESCAPE AND |
| | RESCUE. |
| | |
| | 8) SHOW COMPLIANCE WITH THE FOLLOWING: |
| | 311.4.1 EXIT DOOR REQUIRED. |
| | NOT LESS THAN ONE EXIT DOOR CONFORMING TO THIS SECTION |
| | SHALL BE PROVIDED FOR EACH DWELLING UNIT. THE REQUIRED |
| | EXIT DOOR SHALL PROVIDE FOR DIRECT ACCESS FROM THE |
| | HABITABLE PORTIONS OF THE DWELLING TO THE EXTERIOR |
| | WITHOUT REQUIRING TRAVEL THROUGH A GARAGE. ACCESS TO |
| | HABITABLE LEVELS NOT HAVING AN EXIT IN ACCORDANCE WITH |
| | THIS SECTION SHALL BE BY A RAMP IN ACCORDANCE WITH |
| | SECTION R311.6 OR A STAIRWAY IN ACCORDANCE WITH SECTION |
| | R311.5 .SHOWR311.4.2 DOOR TYPE AND SIZE. |
| | THE REQUIRED EXIT DOOR SHALL BE A SIDE-HINGED DOOR NOT |
| | LESS THAN 3 FEET (914 MM) IN WIDTH AND 6 FEET 8 INCHES |
| | (2032 MM) IN HEIGHT. OTHER DOORS SHALL NOT BE REQUIRED |
| | TO COMPLY WITH THESE MINIMUM DIMENSIONS. ONE LEAF OF |
| | DOUBLE DOORS MUST COMPLY. |
| | |
| | 9) SHOW COMPLIANCE WITH R322.1, WHICH REQUIRES AT LEAST |
| | ONE BATHROOM TO HAVE A DOOR WITH A 29" CLEAR OPENING, |
| | MEASURED FROM THE FACE OF THE DOOR TO THE OPPOSITE STOP |
| | WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 10) PROVIDE DETAILS FOR THE CONCRETE BEAM AT THE |
| | COVERED REAR PORCH AND ITS REINFORMENT. |
| | |
| | 11) PROVIDE DETAILS FOR THE TWO COLUMNS SUPPORTING THE |
| | CONCRETE BEAM AT THE REAR PORCH. |
| | |
| | 12) PROVIDE DETAILS FOR THE ARCH OPENING AT THE FRONT |
| | ENTRY. |
| | |
| | 13) THE WALL SECTION ON A1.2 SPECIFIES A 3:12 ROOF |
| | SLOPE AND THE NOTES ON SHEET A1.4 SPECIFY A 5:12 SLOPE. |
| | PLEASE CORRECT. NOTE: FBC R905.2.7 REQUIRES ROOFS WITH |
| | SOPES LESS THAN 4:12 TO HAVE TWO LAYERS OF |
| | UNDERLAYMENT. |
| | |
| | 14) REVISE THE ROOF SHEATHING FASTENING NOTES ON A1.3 |
| | TO COMPLY WITH R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC |
| | RESIDENTIAL CODE.WHICH REQUIRES WOOD STRUCTURAL PANEL |
| | SHEATHING TO BE FASTENED TO ROOF FRAMING WITH 8D |
| | RING-SHANK NAILS IN ALL ROOF ZONES AND THE SPACING OF |
| | RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN |
| | NAILING ZONE 3. |
| | |
| | 15) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE (2) 2X12 RIM BEAMS TO THE EXISTING STRUCTURE AND |
| | THE NEW CONC. COLUMNS AT THE ENTRY. CLARIFY WHERE THE |
| | META 16 CONNECTORS WILL BE USED. SPECIFY THE NUMBER AND |
| | TYPE OF NAILS TO BE USED WITH THE META 16 CONNECTORS. |
| | SEE THE ENTRY SECTION ON A1.1. |
| | |
| | 16) ON THE ROOF PLAN ON A1.3 CLARIFY THAT THE MTS 12 |
| | CONNECTOR IS REQUIRED TO HAVE 7 NAILS AT EACH END OF |
| | THE STRAP FOR A TOTAL OF 14. |
| | |
| | 17) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE LARGE TRUSSES AT THE REAR ADDITION TO THE EXISTING |
| | WALL AND TO THE EXISTING TRUSSES. |
| | |
| | 18) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS. |
| | IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED |
| | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) |
| | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR |
| | GREATER. |
| | THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22 |
| | INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE |
| | LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE |
| | LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED |
| | HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME |
| | POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3 |
| | FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| | LOCATED IN ATTICS. |
| | |
| | 19) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| | CALCULATIONS PER FBC CHAPTER 13. |
| | |
| | 20)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 21)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 22) SUBMIT PRODUCT APPROVAL FOR THE ROOFING MATERIAL, |
| | THE EXTERIOR DOOR TO THE LAUNDRY ROOM, THE INSWING |
| | FRENCH DOOR AT THE ENTRY (THE ONES THAT WERE SUBMITTED |
| | ARE FOR OUTSWING DOORS) AND THE TRUSS ANCHORS. |
| | |
| | 23) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS THAT |
| | ARE REQUIRED AT NON-IMPACT RATED FRENCH DOORS. SPECIFY |
| | THE MOUNT TYPE, THE FASTENERS, AND THE FASTENER |
| | SPACING. THESE ITEMS CAN BE CIRCLED ON THE NOA. |
| | |
| | 24) THE NOA SUBMITTED FOR THE TRACO IMPACT RATED SINGLE |
| | HUNG WINDOWS HAS BEEN REVISED BY NOA NO. 05-0930.03. |
| | PLEASE SUBMIT THE NEW NOA. |
| | |
| | 25) ARE THE WINDOWS THAT ARE SHOWN ON THE FLOOR PLAN |
| | BETWEEN THE GUEST BATH / DEN AND THE MASTER BEDROOM TO |
| | REMAIN IN THE EXISTING WALL? |
| | |
| | 26) THE VALUE OF THE WORK HAS BEEN INCREASED BASED ON |
| | THE ICC BUILDING VALUATION DATA. ADDITIONAL PERMIT FEES |
| | OF $937.77 ARE DUE. |
| | |