Plan Review Details - Permit 07070352
Plan Review Stops For Permit 07070352
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-02-26 Cont ID  
Sent By lursu Date 2008-02-26 Time 08:17 Rev Time 0.00
Received By lursu Date 2008-02-26 Time 08:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-07-14 Cont ID  
Sent By jwitmer Date 2008-07-14 Time 09:11 Rev Time 0.77
Received By jwitmer Date 2008-07-14 Time 09:11 Sent To  
Notes
2008-07-14 09:12:36REVISION# 3ID-2A

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 14:28 Rev Time 0.55
Received By jwitmer Date 2008-04-21 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By jwitmer Date 2007-12-28 Time 15:44 Rev Time 2.22
Received By jwitmer Date 2007-12-28 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By jwitmer Date 2007-11-29 Time 08:01 Rev Time 4.44
Received By jwitmer Date 2007-11-29 Time 08:01 Sent To  
Notes
2007-11-29 08:13:06GOODRICH LLC CITY PL. TOWER SUITE # 1000
 BUILDING PLAN REVIEW
 PERMIT: 07070352
 ADD: 525 OKEECHOBEE BLVD # 1000
 CONT: DAVIS GENERAL CONTRACTING CORP
 TEL: (561) 820-1400
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) NOTE OF REFRENECE ONLY, BASED ON THE DETERMINATION
 OF THE BUILDING OFFICIAL, APPLICATION FOR TENANT
 IMPROVEMENT PRIOR TO C.O. WILL REQUIRE SHOP DRAWING
 REVIEW BY THE BASE BUILDING DESIGN TEAM, THE DESIGNER
 OF RECORD. PLEASE HAVE THE BASE BUILDING DESIGNERS OF
 RECORD REVIEW YOUR PLANS AND IF FOUND SUFFICIENT AFFIX
 THEIR SHOP DRAWING STAMP ON YOUR DOCUMENTS.
 NOTE ALSO THAT A TENANT CAN NOT ACHIEVE A CERTIFICATE
 OF OCCUPANCY BEFORE THE SHELL BUILDING HAS RECEIVED
 THEIR CERTIFICATE OF COMPLETION. FBC 106.1.2*
 ADMINISTRATIVE CODE.
  
 3)NOTE OF REFRENECE ONLY, PLEASE NOTE AT THIS TIME
 THIS BUILDING HAS NOT RECEIVED A CERTIFICATE OF
 COMPLETION, AND THE ENERGY CALCULATIONS ARE BASED ON A
 SHELL BUILDING AND ARE BASED ON 13-101.1.6. UNLESS THE
 BUILDING IS COMPLETED AS PER ALL ASSUMPTIONS MADE IN
 THE ORIGINAL CODE COMPLIANCE SUBMITTAL, REVISED CODE
 SUBMITTALS USING METHOD A, B OR C SHALL BE SUBMITTED
 WHEN THE COMPLETION OF THE BUILDING (OR PART) OF A
 BUILDING IS PERMITTED.
  
 4-6A) COMPLIED.
  
 6B) 2ND REQUEST,SHEET ID-1A ALSO INDICATES THE TENANT
 SEPERATION WALLS TO BE EXISTING DEMISSING WALL.THE
 BASE SHELL BUILDING PLAN DOESN'T INDICATE ANY SUCH WALL
 IN THE MOST RECENT SET OF REVISIONS SHEET A1.07
 REVISION# 15 DATED 6/13/07. SECTION 708.1(5) REQUIRES
 FIRE PARTITIONS BETWEEN TENANTS. 708.3 FIRE RESISTANCE
 RATING WILL REQUIRE A 1-HOUR FIRE RATING.
 FLORIDA STATE STATUTE 481.2131 INTERIOR DESIGNER CAN
 NOT DESIGN PLANS OR PORTIONS OF THAT EFFECT FIRE-RATED
 SEPERATIONS BETWEEN INTERIOR SPACES, THE FIRM IS
 WORKING OUT OF THE SCOPE OF THEIR LOCENSE. SEE
 ATTACHMENT 481.2131. A FLORIDA LICENSED ARCHITECT WILL
 NEED TO DESIGN ALL COMPONENTS THAT WILL REQUIRE FIRE
 RATED WALLS, CEILINGS AS WELL AS THE PENETRATIONS
 THROUGH SUCH RATED ASSEMBLIES.
 SHEET 1D-1A NOW INDICATE A RATED CEILING IN THE IT OR
 SERVER ROOM & THE ELECTRIC ROOM 127 BUT NO ASSEMBLY HAS
 BEEN CALLED OUT, AGAIN WORKING OUT OF THE SCOPE OF
 LICENSURE FL SS 481.2131.
 THIS PERMIT IS A STAND ALONE PERMIT AND THE WORK TO BE
 COMPLETED UNDER THIS PERMIT, EVEN IF THE DEMISSING
 WALLS, FIRE RATED WALLS AND CEILINGS OF THE SERVER ROOM
 AND ELECTRIC ROOM WERE TO BE COMPLETED UNDER THE BASE
 BUILDING PERMIT, THE THROUGH PENETRATIONS OF THE
 VARIOUS TRADES WILL NEED DETAILS INDICATING AS TO WHAT
 SYSTEMS TO BE USED AND OR UL LISTINGS WHICH WOULD AGAIN
 FALL INTO THE WORK TO BE COMPLETED BY THE TRADES THAT
 ARE COVERED UNDER THIS PERMIT. 712.4.1. THROUGH
 PENETRATIONS, HORIZONTAL AND VERTICAL.
  
 6C) PLEASE NOTE ELECTRICAL COMMENT ABOUT TRANSFORMER
 ABOVE RATED CEILING IN THE ELECTRIC ROOM 127. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 7) COMPLIED.
  
 8) RECONFIGURATION OF TENANT SPACE, CLOSET 133 IS
 MISSING THE DOOR IDENTIFICATION MARKER BUT THE DOOR IS
 MISSING 18" CLEARENCE ON THE LATCH SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 9-13) COMPLIED.
  
 14) 2ND REQUEST,ON THE INTERIOR ELEVATION SHEETS
 QUITE A FEW WALLS INDICATE THE USE OF UPHOLSTERED
 PANELS, SUBMITTED DOCUMENT FOR THE FOAM IS A TEST THAT
 PASSES CAL 117 NOT THE TEST REQUIRED UNDER SECTION
 803.6.1.1 OR 803.1.2.
  
  
 THE TEST REFERED TO IS NOT CAL 117 BUT NFPA 265. WHEN
 RESEARCHING CAL 117 TEST CRITERIA THIS IS NOT SO CLEAR
 SINCE INFORMATION FOUND ON THE WEB FOR THIS TEST IS A
 DRAFT FORM, BUT THE TEST INDICATES THAT TWO PROPOSALS
 ONE A B5 SECOND FLAME TEST, AND THE SECOND PROPOSAL A
 10 SECOND FLAME TEST BUT THE KW OF FIRE OR HEAT APPLIED
 IS NOT PROVIDED. IN ONE AREA OF THE REPORT IT SUGESTED
 THAT OF A BURNIUNG CIGARETTE.THE PAS FAIL CRITERIA
 WAS ALSO A AREA OF QUESTION SINCE THIS IS A DRAFT FORM
 DOCUMENT.
  
 THE TEST LISTED IN SECTIONS 803.6.1.1 AND 603.6.1.2
 REFERENCE NFPA 265 AND THE RESULTS IT TAKES TO PASS
 THIS TEST BY USING METHOD A OR THE MORE RESTRICTIVE
 METHOD B. IN EITHER CASE THE FABRIC, FOAM AND
 "ADHESIVE" ARE TO BE TESTED.BELOW IS THE TEST
 CRITERIA TO BE MET WHICH IS MORE RESTRICTIVE THAN THE
 CAL 117 SUBMITTED.
  
 NFPA 265:9.1 METHOD A 9.2.
 METHOD B PROTOCOL SPECIFIED IN 1.4.1 SHALL BE USED.
 9.2 PROCEDURE.
 THE TEST PROCEDURE SHALL BE AS FOLLOWS:
 (1)ESTABLISH AN INITIAL VOLUMETRIC FLOW RATE OF
 AT LEAST 0.47 M3/S (1000 STANDARD FT3/MIN) THROUGH THE
 DUCT, AND INCREASE THE VOLUME FLOW RATE TO 3.4 M3/S
 (7000 STANDARD FT3/MIN) AS REQUIRED TO KEEP THE OXYGEN
 CONTENT ABOVE 14 PERCENT AND TO CAPTURE ALL EFFLUENTS
 FROM THE BURN ROOM.
 (2)TURN ON ALL SAMPLING AND RECORDING DEVICES,
 AND ESTABLISH STEADY-STATE BASELINE READINGS FOR AT
 LEAST 2 MINUTES.
 (3)IGNITE THE GAS BURNER AND PROCEED AS FOLLOWS:
  
 (A)START THE TIMER ONCE BURNER IGNITION HAS BEEN
 OBSERVED, AND INCREASE GAS FLOW RATE TO PROVIDE A
 BURNER RATE OF HEAT RELEASE EQUAL TO THE REQUIRED HEAT
 OUTPUT FOR THE INITIAL PERIOD. THIS RATE SHALL BE 40 KW
 ? 1 KW FOR 5 MINUTES ? 10 SECONDS.
 (B)CONTINUE THE EXPOSURE AT THAT SAME LEVEL FOR 5
 MINUTES.
 (C)WITHIN 10 SECONDS AFTER THE 5-MINUTE INITIAL
 EXPOSURE, INCREASE THE GAS FLOW RATE TO PROVIDE A RATE
 OF HEAT RELEASE BY THE BURNER EQUAL TO THE FINAL HEAT
 OUTPUT FOR A 10-MINUTE PERIOD. THIS RATE SHALL BE 150
 KW ? 5 KW.
 (D)CONTINUE THE EXPOSURE AT THAT SAME LEVEL FOR
 10 MINUTES ? 10 SECONDS.
 (4)PROVIDE VISUAL DOCUMENTATION IN ACCORDANCE
 WITH 7.1.4.
 (5)PROVIDE A VOICE OR WRITTEN RECORD OF THE FIRE,
 WHICH WILL PROVIDE THE TIMES OF ALL SIGNIFICANT EVENTS,
 SUCH AS TIMES OF IGNITION, ESCAPE OF FLAMES THROUGH THE
 DOORWAY, AND FLASHOVER.
 (6)SHUT OFF THE IGNITION BURNER 15 MINUTES AFTER
 START OF THE TEST, AND TERMINATE THE TEST AT THAT TIME
 UNLESS SAFETY CONSIDERATIONS DICTATE AN EARLIER
 TERMINATION.
 (7)DOCUMENT DAMAGE AFTER THE TEST, USING WORDS,
 PICTURES, AND DRAWINGS.
  
  
 METHOD B:
 1.4.1 THE SAMPLE SHALL BE TESTED BY USING A CORNER TEST
 EXPOSURE WITH THE SPECIMENS MOUNTED ON THREE FULLY
 LINED WALLS OF THE TEST COMPARTMENT (METHOD B).
 1.4.1.1 THESE TEST METHODS SHALL USE A GAS BURNER TO
 PRODUCE A DIFFUSION FLAME TO EXPOSE THE WALLS IN THE
 CORNER OF A ROOM 2.4 M3.7 M2.4 M (8 FT12 FT8
 FT).
 1.4.1.2 THE BURNER SHALL PRODUCE A PRESCRIBED RATE OF
 HEAT OUTPUT OF 40 KW FOR 5 MINUTES FOLLOWED BY 150 KW
 FOR 10 MINUTES, FOR A TOTAL EXPOSURE PERIOD OF 15
 MINUTES.
 1.4.1.3 THE CONTRIBUTION OF THE TEXTILE WALL COVERING
 TO FIRE GROWTH SHALL BE MEASURED BY CONSTANT MONITORING
 OF THE INCIDENT HEAT FLUX ON THE CENTER OF THE FLOOR,
 THE TEMPERATURE OF THE GASES IN THE UPPER PART OF THE
 ROOM, THE RATE OF HEAT RELEASE, THE SMOKE RELEASE, AND
 THE TIME TO FLASHOVER.
 1.4.1.4 THE TEST SHALL BE CONDUCTED WHILE PROVIDING
 NATURAL VENTILATION TO THE ROOM, THROUGH A SINGLE
 DOORWAY OF 0.8 M2.0 M (30 IN.80 IN.).
 1.4.1.5 THE COMBUSTION PRODUCTS SHALL BE COLLECTED IN A
 HOOD FEEDING INTO A CHAMBER THAT IS CONNECTED TO AN
 EXHAUST DUCT IN WHICH MEASUREMENTS OF THE GAS VELOCITY,
 TEMPERATURE, AND CONCENTRATIONS OF SELECTED GASES ARE
 MADE.
 1.4.2 FLASHOVER SHALL BE CONSIDERED TO HAVE OCCURRED
 WHEN ANY TWO OF THE FOLLOWING CONDITIONS HAVE BEEN
 ATTAINED:
 (1)THE HEAT RELEASE RATE EXCEEDS 1 MW.
 (2)THE HEAT FLUX AT FLOOR EXCEEDS 20 KW/M2.
 (3)THE AVERAGE UPPER LAYER TEMPERATURE EXCEEDS
 600?C (1112?F).
 (4)FLAMES EXIT THE DOORWAY.
 (5)AUTOIGNITION OF PAPER TARGET ON FLOOR OCCURS.
  
  
 TEXTILE WALL COVERINGS. TEXTILE WALL COVERINGS SHALL
 HAVE A CLASS A FLAME SPREAD INDEX IN ACCORDANCE WITH
 ASTM E 84 AND BE PROTECTED BY AUTOMATIC SPRINKLERS
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR
 903.3.1.2 OR THE COVERING SHALL MEET THE CRITERIA OF
 SECTION 803.6.1.1 OR 803.6.1.2 WHEN TESTED IN THE
 MANNER INTENDED FOR USE IN ACCORDANCE WITH NFPA 265
 USING THE PRODUCT MOUNTING SYSTEM, INCLUDING ADHESIVE.
  
 15) COMPLIED.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-15 Cont ID  
Sent By jwitmer Date 2007-08-15 Time 20:06 Rev Time 1.00
Received By jwitmer Date 2007-08-15 Time 20:06 Sent To  
Notes
2007-08-15 21:18:02GOODRICH LLC CITY PL. TOWER SUITE # 1000
 BUILDING PLAN REVIEW
 PERMIT: 07070352
 ADD: 525 OKEECHOBEE BLVD # 1000
 CONT: DAVIS GENERAL CONTRACTING CORP
 TEL: (561) 820-1400
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) BASED ON THE DETERMINATION OF THE BUILDING OFFICIAL,
 APPLICATION FOR TENANT IMPROVEMENT PRIOR TO C.O. WILL
 REQUIRE SHOP DRAWING REVIEW BY THE BASE BUILDING DESIGN
 TEAM, THE DESIGNER OF RECORD. PLEASE HAVE THE BASE
 BUILDING DESIGNERS OF RECORD REVIEW YOUR PLANS AND IF
 FOUND SUFFICIENT AFFIX THEIR SHOP DRAWING STAMP ON YOUR
 DOCUMENTS.
 NOTE ALSO THAT A TENANT CAN NOT ACHIEVE A CERTIFICATE
 OF OCCUPANCY BEFORE THE SHELL BUILDING HAS RECEIVED
 THEIR CERTIFICATE OF COMPLETION. FBC 106.1.2*
 ADMINISTRATIVE CODE.
  
 3)PLEASE NOTE AT THIS TIME THIS BUILDING HAS NOT
 RECEIVED A CERTIFICATE OF COMPLETION, AND THE ENERGY
 CALCULATIONS ARE BASED ON A SHELL BUILDING AND ARE
 BASED ON 13-101.1.6. UNLESS THE BUILDING IS COMPLETED
 AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL CODE
 COMPLIANCE SUBMITTAL, REVISED CODE SUBMITTALS USING
 METHOD A, B OR C SHALL BE SUBMITTED WHEN THE COMPLETION
 OF THE BUILDING (OR PART) OF A BUILDING IS PERMITTED.
  
 4)PLEASE CONTACT LILI URSA AT 822-1239 FOR SUITE
 NUMBER ASSIGNMENT PLEASE PROVIDE THIS INFORMATION IN
 THE TITLE BLOCK, SEE FLORIDA ADMINISTRATIVE CODES
 61G1-15.004 AND 61G15-23.002.
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY, TO BE LISTED IN THE PLAN:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 6A) SHEET ID-1A WALL TYPE "A" IS INDICATED AS AN
 EXISTING CMU DEMISING WALL, PLEASE COORDINATE WITH THE
 BASE BUILDING DESIGNER. ADDITIONAL INFORMATION
 REQUIRED, FBC ADMINISTRATIVE CODE 106.1.2*. THE SHELL
 BUILDING PLAN SHEET A1.06 & A2.06 BOTH INDICATE THIS
 WALL TO BE A DRYWALL AND METAL STUD WALL.
  
 6B) SHEET ID-1A ALSO INDICATES THE TENANT SEPERATION
 WALLS TO BE EXISTING CMU DEMISSING WALL.THE BASE
 SHELL BUILDING PLAN DOESN'T INDICATE ANY SUCH WALL.
 708.1(5) REQUIRES FIRE PARTITIONS BETWEEN TENANTS.
 708.3 FIRE RESISTANCE RATING WILL REQUIRE A 1-HOUR FIRE
 RATING.
 FLORIDA STATE STATUTE 481.2131 INTERIOR DESIGNER CAN
 NOT DESIGN PLANS OR PORTIONS OF THAT EFFECT FIRE-RATED
 SEPERATIONS BETWEEN INTERIOR SPACES, THE FIRM IS
 WORKING OUT OF THE SCOPE OF THEIR LOCENSE. SEE
 ATTACHMENT 481.2131.
  
 7) SHEET ID-1A DOOR# 002IS INDICATED TO BE A SINGLE
 2'-8" DOOR CUT IN HALF, CLOSETS THAT AREDEEPER THAN
 2'-0" WILL REQUIRE A MINIMUM CLEAR WIDE OF 32" WHEN THE
 DOOR OR DOORS ARE OPEN 90 DEGREES TO THE OPENING. SEE
 11-4.13.5
 11-4.13.5 CLEAR WIDTH.
 DOORWAYS SHALL HAVE A MINIMUM CLEAR OPENING OF 32
 INCHES (813 MM) WITH THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE STOP [SEE
 FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C), AND FIGURE
 24 (D)]. OPENINGS MORE THAN 24 INCHES (610 MM) IN DEPTH
 SHALL COMPLY WITH SECTIONS 11-4.2.1 AND 11-4.3.3 [SEE
 FIGURE 24 (E)].
 EXCEPTION: DOORS NOT REQUIRING FULL USER PASSAGE, SUCH
 AS SHALLOW CLOSETS, MAY HAVE THE CLEAR OPENING REDUCED
 TO 20"MINIMUM.
  
 8) SHEET ID-1A DOORS 023 AND 024 ARE BOTH CLOSET DOORS
 THAT OPEN TO A CLOSET DEEPER THAN 24" REQUIRING A CLEAR
 32" OPENING.
 SEE 11-4.13.5 CLEAR WIDTH.
  
 9) DOORS 16-19 ARE INDICATED AS 28" DOORS THAT LEAD TO
 THE INDIVIDUAL WATER CLOSET STALLS.PLEASE SEE 11-4.13.5
 AND 11-4.17.5
 DOORS. TOLIET STALL DOORS INCLUDING DOOR HARDWARE,
 SHALL COMPLY WITH SECTION 11-4.13.. DOORS SHALL BE SELF
 CLOSING.
 11-4.17.3 EXCEPTION: NEW CONSTRUCTION.
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR.
  
 10) IN BOTH THE WOMEN'S AND MEN'S RESTROOMS THERE ARE
 NO HANDICAPPED STALLS. 11-4.1.3(11)TOILET FACILITIES.
 IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH SECTION
 11-4.22 .
 EXCEPTION: NEW CONSTRUCTION.
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR.
  
 11) SHEET ID-14 DETAIL A1 BREAK ROOM# 112 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 12)SHEET ID-14 DETAIL A11 & A15 BOTH ARE OF RESTROOM
 VANITIES AND LAVATORIES.11-4.19.2 HEIGHT AND
 CLEARANCES.
 LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER
 SURFACE NO HIGHER THAN 34 INCHES (865 MM) ABOVE THE
 FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29 INCHES
 (735 MM) ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE
 APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE
 31 .
  
 11-4.19.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR
 OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM
 OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 32 ).
  
 11-4.19.4 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES UNDER LAVATORIES SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES
 UNDER LAVATORIES.
  
 13)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY.
  
 14) ON THE INTERIOR ELEVATION SHEETS QUITE A FEW WALLS
 INDICATE THE USE OF UPHOLSTERED PANELS, PLEASE PROVIDE
 ADDITIONAL INFORMATION 106.1.2.HOW WILL THE FABRIC BE
 MOUNTED? 803.6.1 TEXTILE WALL COVERINGS.
 TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME
 SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE
 PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE
 COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1
 OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE
 IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING
 SYSTEM, INCLUDING ADHESIVE.
  
 15) THE MILLWORK LEGEND INDICATES CATALOG NUMBERS FOR
 TRIM BUT DOESN'T IDENTIFY AS TO WHAT TYPE OF MATERIALS
 THE TRIM WILL BE MADE OF? 106.1.2* ADDITIONAL
 INFORMATION REQUIRED.805.5 TRIM .
 MATERIAL USED AS INTERIOR TRIM SHALL HAVE A MINIMUM
 CLASS C FLAME SPREAD INDEX AND SMOKE-DEVELOPED INDEX.
 COMBUSTIBLE TRIM , EXCLUDING HANDRAILS AND GUARDRAILS,
 SHALL NOT EXCEED 10 PERCENT OF THE AGGREGATE WALL OR
 CEILING AREA IN WHICH IT IS LOCATED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-09-10 Cont ID  
Sent By dpalmer Date 2008-09-10 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2008-09-10 Time 10:56 Sent To PC
Notes
2008-09-10 10:56:54REV FOR FINAL.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-08-28 Cont ID  
Sent By dpalmer Date 2008-08-28 Time 11:46 Rev Time 0.00
Received By dpalmer Date 2008-08-28 Time 11:46 Sent To PC
Notes
2008-08-28 11:46:27 
 ** DENIEDREVISION **
  
  
  
 1) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH
 PANEL SCHEDULES AND ALSO WITH THE LIGHTING CONTACTOR
 PANELS.
 THIS WAS THE SAME AS IN REVIEW NOTES DATED ON 7/15/08
 YET NO CHANGES HAVE BEEN MADE.
 FOR EXAMPLE:
 PLEASE SEE LIGHTING AND POWER PLANS WHICH BOTH INDICATE
 CIRCUITS? 10LA-13 AND 10LA-5 TO BE ON LIGHTING
 CONTACTORS YET NEITHER LIGHTING CONTACTOR ON SHEET E6.1
 CONTAINS THESE. THIS IS NOTING ONLY TWO, THERE ARE
 OTHERS.
 13-415.1.ABC.1.1, .1.2, .1.3.
 FBC 106.1.1
  
 2) NOTE: PLEASE SEE KEY NOTES ON SHEET E3.1 WHICH DOES
 NOT CONTAIN A KEYNOTE #6 AS NOTED ON PLANS. (MISPRINT)
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: PLEASE SEE SHEET E3.1 AS THIS INDICATES A
 *FPL* METER. IT HAS COME TO THIS REVIEWER?S ATTENTION
 THAT THERE IS NO FPL METER IN FACT IT IS NOT A TENANT
 CHECK METER EITHER. PLEASE VERIFY WHAT THIS DEVICE IS
 AND REVISE PLANS ACCORDINGLY.
 FBC 106.1.1, 106.3.5.1.2
 NEC
  
 4) NOTE: PLEASE REVISE ALL LIGHTING PERFORMANCE
 CALCULATIONS. THERE HAVE BEEN REVISIONS TO LIGHTS AND
 PLANS YET THE WATTAGE EVEN THOUGH LABELED AS REVISED
 DOES NOT COORDINATE.
 ONE EXAMPLE OF THIS IS THE STORAGE ROOM # 128 WHICH
 INDICATES A TOTAL OF 68WATTS YET THIS IS NOT POSSIBLE
 BASED ON THE WATTAGE OF EACH FIXTURE ON N
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-07-15 Cont ID  
Sent By dpalmer Date 2008-07-15 Time 08:29 Rev Time 0.00
Received By dpalmer Date 2008-07-15 Time 08:29 Sent To PC
Notes
2008-07-15 08:30:07** DENIEDREVISIONS **
  
  
 1) NOTE:THE SHEET E 6.1 SUBMITTED NOW DOES NOT
 COORDINATE WITH THE PREVIOUS SUBMITTED POWER PLANS AND
 LIGHTING PLANS FOR CIRCUITING. PLEASE SUBMIT REVISED
 LIGHTING AND POWER PLANS WITH REVISED CIRCUITING ETC.
 408.4, 310.16, 240.4, 220, ETC
 FBC 106.1.2, 106.1.1
  
 2) NOTE: THE LIGHTING POWER DENSITIES WERE REVISED
 HOWEVER NO REVISED LIGHTING PLANS WERE SUBMITTED.
 PLEASE SUBMIT. FBC 13-415.2, 13-415.2.ABC.1.1, .1.2
 FBC 106.5, 106.1.1
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-15 Cont ID  
Sent By dpalmer Date 2008-01-15 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2008-01-15 Time 12:59 Sent To  
Notes
2008-01-15 13:04:58FA AND FS SHEETS STILL NEED FIRE REVIEW STAMPS

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-22 Cont ID  
Sent By dpalmer Date 2007-12-22 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 12:44 Sent To  
Notes
2007-12-22 12:45:02** DENIED3RDREVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS TWO REVIEWS
 WITH RESPECT TO LIGHTING PERFORMANCE CALCULATIONS AND
 LIGHTING CONTROLS ARE STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS WHICH ARE BEING SUBMITTED FOR REVIEW ARE
 NOW COMPLETE HOWEVER COORDINATION OF PLANS, FIXTURES,
 AND CALCULATIONS ARE NEEDED. IN THE MEETING HELD ON
 DECEMBER 18TH, 2007 THE PREVIOUS COMMENT WAS GONE OVER
 TO MAKE SURE ALL LIGHTING WHICH IS SHOWN ON PLANS IS IN
 THE CALCULATIONS NOW SHOWN AND SUBMITTED ON E6.1. THERE
 WAS NO COMPLETE REVIEW OF CALCULATIONS THE COMMENT WAS
 MADE TO PLEASE BE SURE ALL COORDINATION WAS ADDRESSED.
 FIXTURE LEGEND DOES NOT COMPLETE INFORMATION FOR WALL
 SCONCES ONLY GIVES THE 40W DESIGNATION WHICH IS OK. ANY
 CHANGES OF MINIMUM FIXTURES MAY BE DONE BEFORE
 INSTALLATION.
 PLEASE SEE BELOW AS THERE ARE SOME EXAMPLES WHICH ARE
 BEING GIVEN WHICH NOTES SOME OF THE LOCATIONS ON PLANS
 WHICH ARE STILL IN QUESTION.
 THESE ARE FOR EXAMPLE:
  
 PLEASE SEE MISSING ROOM 133 FROM CALCULATIONS.
  
 PLEASE SEE MISSING ROOM 128 FROM CALCULATIONS.
  
 PLEASE SEE ROOM 108 AS 6-32W FIXTURES AND 1-J-FIXTURE
 WHICH IS 200W IS SHOWN ON PLANS. THIS TOTALS 392W
 HOWEVER THE CALCULATION SHOWS DESIGN AS 328W.
  
 PLEASE SEE ROOM 105 AS PLANS SHOWS 5-32W FIXTURES WHICH
 TOTALS 160W YET CALCULATIONS SHOWS DESIGN AS128W.
  
 PLEASE SEE ROOM 101 (LOBBY) WHICH INDICATES 7-32W, 2-35
 AND 2-40W (WALL SCONCES) WHICH IS 374W YET CALCULATIONS
 SHOWS DESIGN AS 310W.
  
 PLEASE SEE ROOM 112 AS PLANS SHOW 5-32W, 3-32W (UC LTS)
 WHICH IS A TOTAL OF 256W, YET THE CALCULATIONS SHOWS
 DESIGN AS 192W.
  
 PLEASE SEE THE CORRIDORS AS THE TOTAL NUMBER OF GENERAL
 LIGHTING AND DECORATIVE LIGHTING FIXTURES COMES TO A
 TOTAL OF 1462W, YET BASED ON THE TOTAL OF CORRIDOR
 DESIGN WATTAGE SHOWN ON TABLE, THE TOTAL IS 1145W.
  
 ** PLEASE SEE SOME OTHER ROOMS SUCH AS 107 SHOWS 397W
 BASED ON PLANS AND FIXTURES SHOWN AND TABLE DESIGN IS
 497W?
  
 THE ABOVE IS SOME EXAMPLES; PLEASE MAKE SURE ALL
 LIGHTING ON PLANS CORRELATES WITH THE LIGHTING
 CALCULATIONS.
 13-415.2, 13-415.2.B.1, TABLE 13-415.2.B
  
 2) NOTE: PLEASE SEE AS PREVIOUSLY MENTIONED ON BOTH
 PREVIOUS REVIEWS, PLEASE COMPLETE AND COORDINATE ALL
 LIGHTING CIRCUITS FOR LIGHTING CONTACTORS AND CONTROLS
 PER FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE PREVIOUS NOTES GAVE A COUPLE OF EXAMPLES AND
 SPECIFICALLY STATED THESE WERE NOT ALL. IN MEETING HELD
 DECEMBER 18TH, 2007 A COMMENT WAS MADE TO PLEASE BE
 SURE ALL CIRCUITING FOR LIGHTING ETC WAS COORDINATED ON
 PLANS, PANELS, CONTROLS ETC.
 PLEASE SEE BELOW FOR EXAMPLES:
  
 ROOM 120, 130 AS BOTH OF THESE ROOMS CONTAINS A
 CIRCULAR NOTE #1 WHICH STATES TO CONNECT TO THE
 LIGHTING CLOCK OUTLETS TO THE SAME WALL SCONCE LIGHTING
 CIRCUIT IN THAT SPECIFIC ROOM. PLEASE SEE THESE ARE
 NOTED AS CIRCUIT 10LA-13 ON POWER PLANS YET THE
 LIGHTING PLANS WHICH SHOWS THE LIGHTING CIRCUIT
 INDICATES 10LA-15.
  
 ROOM/LOBBY 101 WHICH INDICATES LIGHTING OUTLETS FOR
 CIRCUIT 10LB-16, YET THIS CIRCUIT IS NOT ON EITHER
 LIGHTING CONTACTOR LCA OR LCB. PLEASE SEE THE SWITCH IS
 STILL ALSO SHOWN AS A STANDARD SINGLE POLE SWITCH FOR
 THESE LIGHTING OUTLETS.
 PLEASE SEE PANEL SCHEDULE AS CIRCUIT IS NOTED FOR
 GENERAL PURPOSE RECEPTACLES
  
 ROOM 109 AND 111 WHICH CONTAIN CIRCUITS FOR ACCENT
 LIGHTING TIED TOGETHER. PLEASE SEE THE ACCENT LIGHTING
 OUTLETS ON POWER PLANS FOR THESE ROOMS ARE SHOWN AS
 CIRCUIT 10LA7, HOWEVER LIGHTING PLANS SHOW 10LA- AND
 10LA- 11 TIED TOGETHER.
 PLEASE ALSO SEE EVEN AS THE PLANS CONTAINS NOTES WHICH
 MENTIONS ALL ACCENT LIGHTING TO CONTACTORS, NEITHER
 CONTACTOR SCHEDULE LCA OR LCB CONTAIN EITHER10LA-7 OR
 10LA-11?
 PLEASE SEE EVEN AS THESE SWITCHED LIGHTING OUTLETS
 CONTAIN A NOTE #1 ON ROOM 117 WHICH STATES TO CONNECT
 TO WALL SCONCE CIRCUIT IN SAME ROOM, THE WALL SCONCES
 IN THIS SAME ROOM 117 DOES NOT CONTAIN ANY CIRCUIT(S).
  
 ROOM/CORRIDOR 123 CONTAINS A SWITCH WITH A NOTE WHICH
 STATES TO HALLWAY WALL SCONCES, YET THE PLANS DOE NOT
 SHOW ANY HALLWAY WALL SCONCES?
  
 *** AS MENTIONED ON PREVIOUS REVIEWS AND MEETING PLEASE
 BE SURE ALL ITEMS ON PLANS CORRELATE WITH ALL LIGHTING
 CONTROLS REQUIRED IN SECTIONS NOTED ABOVE. SOME OF THE
 EXAMPLES AS NOTED ABOVE MAY NOT BE ALL AND ONLY SOME
 EXAMPLES WERE GIVEN.
  
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 MINIMUM CODE COMPLIANCE.
 PLEASE SEE THAT A FEE OF $7500.00 HAS BEEN ASSESSED AS
 REQUIRED BY THE FLORIDA STATUTES. PLEASE ALSO SEE AS
 REQUIRED UNDER THE FLORIDA STATUTES FEE MUST BE PAID
 BEFORE NEXT RE-SUBMISSION OF PLANS.
 THIS IS NOT THE RESPONSIBILITY OF THE CONTRACTOR OR
 OWNER.
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED BY THIS OFFICE.
  
 *** AS STATED ON PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS, COMMENTS OR IF ANY PARTS OF THE NOTES WHICH
 ARE TYPED ARE NOT CLEAR IN ANY WAY, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE FOR CLARIFICATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-28 Cont ID  
Sent By dpalmer Date 2007-11-28 Time 11:33 Rev Time 0.00
Received By dpalmer Date 2007-11-28 Time 09:31 Sent To  
Notes
2007-11-28 11:33:41** DENIED2ND REVIEW **
  
 ** PLEASE KNOW THERE ARE STILL SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG
 WITH NEW COMMENTS DUE TO ITEMS NOW REVISED ON PLANS
 WHICH WERE NOT ON ORIGINAL PLANS.
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION PACKAGE WAS
 SUBMITTED BACK WITH RESPONSES FROM THE INTERIOR DESIGN
 TEAM WHICH MENTIONS TO SEE RESPONSES TO THE MEP NOTES
 FROM OTHER DESIGN PROFESSIONALS; HOWEVER NO RESPONSE
 LETTERS FROM ANY OTHER TRADE DESIGNERS WERE LOCATED
 WITH PACKAGE BROUGHT BACK.
 (PACKAGE CONTAINED:
 1) LETTER/RESPONSE FROM STH FOR BASE BUILDING REVIEW.
  
 2) 3-BOOKETS FOR RESPONSES FROM LISA ERDMANN AND
 ASSOCIATES.
  
 3) ORIGINAL PERMIT APPLICATION WITH NOTES FROM TRADES.
  
 ** PLEASE KNOW RESPONSES FROM MEP DESIGNERS ARE NOT
 REQUIRED HOWEVER DO HELP TO EXPEDITE THE REVIEW PROCESS
 ON HOW COMMENTS WERE ADDRESSED OR RESPONSE ON
 COMMENTS.
  
  
 2) NOTE: PLEASE SEE THAT THE FOLLOWING CODES SHALL BE
 STATED ON PLANS. PLEASE SEE THIS COMMENT IS FOR THE ID
 COVER SHEETS AS IT REFLECTS A 2003 NFPA-70.
 PLEASE KNOW THIS SHOULD BE 2005.
 IF THIS SHEET DOES NOT NEED TO BE REVISED FOR OTHER
 TRADES OR FOR OTHER COMMENTS, THERE WILL BE NO NEED TO
 RE-PRINT SHEET ONLY FOR THIS. IT COULD BE REDLINED.
  
 2) NOTE: PLEASE SEE ELECTRICAL PLANS INDICATES THE
 TRANSFORMER AS CEILING MOUNTED HOWEVER THE ID PLANS
 SPECIFICALLY CALL FOR A 1HR RATED CEILING TO BE
 INSTALLED IN THIS SAME ROOM.
 THIS WAS GONE OVER IN THE MEETING PREVIOUSLY HELD
 BEFORE PLANS WERE RESUBMITTED THAT THE CODE
 SPECIFICALLY 450.13 A AND B DOES NOT PERMIT THIS SIZE
 OF TRANSFORMER ABOVE CEILING. THE COMMENT IN THE
 MEETING WAS THAT THERE WOULD BE NO CEILING INSTALLED IN
 THE ELECTRICAL ROOM 127 AND THE 1HR RATED WALLS WERE
 GOING TO GO UP TO THE DECK.
 PLEASE ADJUST.
  
 3) NOTE: PLEASE SEE POSSIBLE COMMENTS FROM MECHANICAL
 REVIEW FOR RATED CEILING IN SERVER ROOM 104. ** THIS IS
 ONLY NOTED FOR INFORMATIONAL PURPOSE.
  
 4) NOTE: PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO
 COMPLETED SYSTEM FOR LIGHTING CONTROLS PER FBC CHAPTER
 13, 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THERE ARE CIRCUITS ON PLANS WHICH ARE NOTED
 TO LIGHTING CONTACTOR EITHER LCA OR LCB, HOWEVER
 NEITHER LIGHTING CONTACTOR CONTAINS THESE CIRCUITS.
 PLEASE SEE FOR EXAMPLE ONE FROM EACH: 10LA-27 AND
 10HA-1
 PLEASE ALSO SEE 13-415.1.ABC.1.3 FOR ACCENT/TASK
 LIGHTING.
 PLEASE COORDINATE AND ADJUST.
  
 5) NOTE: PLEASE COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS WHICH CONFORM TO THE FBC. PLEASE SEE THE
 LIGHTING POWER DENSITIES SUBMITTED ON E6.1REFLECT
 13-415.2.B.1 WHICH IS FOR SPACE BY SPACE HOWEVER NO
 SPACE BY SPACE CALCULATIONS WERE SUBMITTED. THE FIGURE
 SUBMITTED SHOWS ALL AS *OFFICE* ONLY AT 1.1 SQ FT.
 PLEASE KNOW THE LIGHTING ON PLANS AND FIXTURES SHOWN ON
 FIXTURE LEGEND ON E0.1 ARE NOT COMPLETE AT THIS TIME.
 PLEASE IDENTIFY ALL FIXTURES ON FIXTURE LEGEND. FOR
 EXAMPLE: FIXTURE *J* ON PLANS, NOT ON FIXTURE LEGEND.
 FOR EXAMPLE: PLEASE SEE THE FIXTURE COUNT SHALL INCLUDE
 ALL FIXTURES, WATTAGES FOR THE MAXIMUM LPD AS ALLOWED.
 PLEASE KNOW AS THE FIXTURE LEGEND WILL NEED TO BE
 ADJUSTED AND SPACE BY SPACE WAS NOT SUBMITTED, A
 COMPLETE REVIEW OF ALL FIXTURES COULD NOT BE DONE AT
 THIS TIME.
 PLEASE BE SURE TO COORDINATE ALL.
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT CODE COMPLIANT COMMENTS. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
 PLEASE KNOW ONE COPY OF EACH ELECTRICAL HAS BEEN
 RETAINED BY THIS OFFICE.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By dpalmer Date 2007-08-06 Time 12:45 Rev Time 0.00
Received By dpalmer Date 2007-08-06 Time 09:45 Sent To  
Notes
2007-08-06 12:45:17 
  
 ** UNSAT **
  
  
 1) NOTE:PLEASE SEE ONCE THE ADDRESSING REVIEWER HAS
 ASSIGNED A SUITE/UNIT NUMBER, PLEASE BE SURE TO PLACE
 DESIGNATION ON TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE THE ID PLANS ARE REQUIRED TO BE
 DATED WHEN SIGNING AND SEALING DOCUMENTS.
 PLEASE SEE FS 481.221.
  
 3) NOTE: PLEASE KNOW THAT ALL PLANS SHALL BE SIGNED,
 WITH SIGNATURES AS ON FILE AND RECORD WITH THE CITY OF
 WEST PALM BEACH AND THIS JURISDICTION.
 FS 481.221/471.025
  
 4) NOTE: PLEASE SEE COMMENTS WHICH WERE MADE BY THE
 MECHANICAL REVIEWER ALSO WITH RESPECT TO THE BASE
 BUILDING DESIGN TEAM BEING REQUIRED TO REVIEW THE PLANS
 AS THIS BUILDING DOES NOT CONTAIN A CO AND ALL WORK
 BEING DONE ON A BUILDING WHICH IS UNDER THE
 RESPONSIBILITY OF ANOTHER DESIGN TEAM MUST BE
 REVIEWED.
 FBC 106.1.2
  
 5) NOTE: PLEASE BE SURE TO STAMP AS REVIEWED. PLEASE BE
 KNOW ANY ASSUMPTIONS MADE TO THE BASE BUILDING FOR LOAD
 CALCULATIONS AND ENERGY CALCULATIONS WILL BE REQUIRED
 TO BE REVISED ON BASE BUILDING AND INFORMATION SHOULD
 BE MAD AVAILABLE TO THE BASE BUILDING DESIGN TEAM.
 FBC 106.1.2, 106.3.5.1.2
 NEC 220/408/215 ETC
 FBC CHAPTER 13 AS NOTED ON MECHANICAL REVIEW.
  
 6) NOTE: PLEASE VERIFY THE CORRIDOR BEING UNDER THE
 SCOPE OF WORK FOR THIS PERMIT OR NOT. PLEASE ALSO
 VERIFY WITH THE BASE BUILDING DESIGN TEAM AND OWNER FOR
 POSSIBLE OWNER REQUIRED ELECTRICAL ROOM/AREA. PLEASE
 SEE THAT THE TENANT/OCCUPANT DOES NOT CONTAIN ACCESS TO
 OVER CURRENT PROTECTION DEVICES AS REQUIRED. PLEASE SEE
 THIS WOULD AFFECT THE LOCATIONS AS THE BASE BUILDING
 HAD CONDITIONS DUE TO CONSTRUCTION BOARD OF APPEALS
 APPLICATION AND ITEMS GRANTED.
 PLEASE CORRELATE.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
 240.24D.
  
 7) NOTE: PLEASE BE SURE TO CORRELATE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE SEE DESIGNATIONS AS
 PROVIDED ON THE ID PLANS ARE NOT THE SAME ON MEP.
 PLEASE SEE THE ELECTRICAL PLANS CONTAIN THE SAME
 NUMERICAL DESIGNATION USED IN MORE THAN ONE LOCATION.
 PLEASE SEE FOR EXAMPLE: ROOM/AREA 103.
 PLEASE ALSO SEE THE STORAGE ROOM WHICH IS BEING NOTED
 ON ALL PLANS WHEN IN FACTTHIS IS A SERVER. AND
 POSSIBLE IT ROOM.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE THE ROOM NOTED AS STORAGE IS SHOWN
 WITH MULTIPLE CIRCUITS FOR WHAT APPEARS WILL BE AN IT
 ROOM.
 PLEASE PROVIDE MORE INFORMATION ON THIS ROOM AND ALL
 EQUIPMENT INTENDED TO BE INSTALLED.
 THIS ROOM IS BEING FED WITH A SEPARATE AC SYSTEM.
 PLEASE SEE 645.10,645.4, 645.5 ETC.
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13 FOR ENERGY CODE
 COMPLIANCE NEEDS TO BE MET.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE MISSING CONTROLS FOR SEPARATE SPACES IN MANY
 ROOMS.
 PLEASE SEE THAT NO ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS WERE SUBMITTED FOR REVIEW. 13-415.1.A,
 13-415.B, 13-415.1.C, 13-415.2.
 PLEASE CORRELATE FIXTURE LEGEND FOR ALL FIXTURES ON
 PLANS WITH CALCULATIONS FOR TYPES, WATTAGE, METHOD OF
 CONTROL ETC.
 PLEASE PROVIDE SCHEDULING FOR PROPOSED SYSTEM. PLEASE
 KNOW A BASE TIME SHOULD BE SHOWN.
 PLEASE INDICATE LOCATIONS AS REQUIRED FOR ALL OVER RIDE
 DEVICES SO THE OCCUPANT CAN VISUALLY SEE THE LIGHTING
 WHICH IS BEING OVER RIDDEN.
 PLEASE PROVIDE ALL MAXIMUM TIMES ON OVER RIDES AND OVER
 RIDE DEVICES.
 PLEASE SUBMIT THE MANUFACTURES/SPEC CUT SHEETS ON THE
 PROPOSED SYSTEM. PLEASE BE SURE ALL DEVICES/SYSTEM
 CONTAINS A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY. (NRTL)
 110.3, 90.7.
 PLEASE BE SURE ALL DOCUMENTS ARE SIGNED, DATED AND
 SEALED AS REQUIRED PER 13-103.1.1.1 AND OWNER/AGENT IS
 SIGNED.
  
 10) NOTE: PLEASE SEE THE FIXTURE LEGEND AS PROVIDED ON
 THE ID PLANS NEEDS COORDINATION WITH THE LEGEND ON THE
 ELECTRICAL PLANS.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE THE PANEL 10HA SHOWS ON THE RISER
 AS CONTAINING SOME SORT OF FEED COMING FROM THIS PANEL
 TO PANEL 10LA, YET THIS DESIGNATION DOES NOT CORRELATE
 WITH EITHER PANEL OR OTHER INFORMATION.
 PLEASE SEE THE RISER WHICH SHOWS 10TA-1L?
 FBC 106.1.2 FOR COORDINATION.
  
  
 12) NOTE: PLEASE SEE THE TRANSFORMER SCHEDULE INDICATE
 THE FEEDERS ON THE SECONDARY SIDE OF THE TRANSFORMER AS
 4/0 WHICH ARE NOT SUFFICIENT. PLEASE SEE 310.16, 240.4,
 240.21 AS THE TAPPED CONDUCTORS ARE REQUIRED TO
 TERMINATE IN OVER CURRENT PROTECTION WHICH LIMITS THE
 LOAD ON THE TAPPED CONDUCTOR.
  
 13) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE
 PANEL 10LA IS SHOWN AS 250AMPS WHICH IS TOO LARGE FOR
 THE CONDUCTORS AS NOTED ABOVE IN NOTE #13, HOWEVER THE
 PANEL MENTIONS THIS CONTAINS FEED-THRU LUGS TO FEED
 PANEL 10LB, YET PANEL 10LB IS A 225AMP RATED PANEL.
 THIS DOES NOT MEET THE NEC AS THE RATING OF THE PANEL
 MUST MEET THE MINIMUM RATING FOR THE OCP WHICH IS
 250AMPS AS SHOWN ON PANEL 10LA MAIN.
 240.4, 310.16, 408.36, 240.30, 240.20 ETC.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-02-04 Cont ID  
Sent By mawillia Date 2008-02-04 Time 16:52 Rev Time 0.00
Received By mawillia Date 2008-02-04 Time 16:22 Sent To  
Notes
2008-02-04 16:37:13*****APPROVED*****
  
  
 PLAN SHEETS 1D-3B, ID-6, ID-6B, E2.1, FA0.1, FA2.1,
 FS0.1, AND FS2.1 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By mawillia Date 2007-12-03 Time 13:19 Rev Time 0.00
Received By mawillia Date 2007-12-03 Time 12:40 Sent To  
Notes
2007-12-03 13:17:15*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED, HOWEVER, THE APPROPIATE PLAN SHEETS ARE
 TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By mawillia Date 2007-09-14 Time 13:12 Rev Time 0.00
Received By mawillia Date 2007-09-14 Time 10:19 Sent To  
Notes
2007-09-14 11:11:44*****DENIED*****
  
 (UNLESS OTHERWISE NOTED, THIS TENANT SPACE IMPROVEMENT
 SHALL BE CLASSIFIED AS A NEW BUSINESS OCCUPANCY)
  
  
 01.THE NUMERICAL ADDRESS OF THE PROJECT SITE
 (INCLUDING THE SUITE NUMBER) SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.PROJECT SITE
 LOCATION NEEDED ON COVER PAGE OF HYDRAULIC CALCULATION
 SHEETS ALSO.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR
 HINDER ACCESS TO OR EGRESS FROM THE TENANT SPACE, OTHER
 TENANT SPACES ON THE TENTH FLOOR, OR THE BUILDING.
  
 06.PROVIDE OCCUPANT LOAD AS IN NUMBER OF PERSONS FOR
 WHOM MEANS OF EGRESS ARE REQUIRED BASED UPON THE
 CHARACTERISTIC OF THE USE OF THE TENANT SPACE.
  
 07.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THE EXITS, AISLE CORRIDORS, AND ALL OTHER SPACES IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 08.DOORS THAT LEAD INTO THE EXIT CORRIDOR SHALL BE
 SELF CLOSING OR AUTOMATIC CLOSING.ALL FIRE RATED
 DOORS TO COMPLY WITH NFPA 80.
  
 09.PROVIDE A LIFE SAFETY PLAN SHEET WHICH ILLUSTATES
 TRAVEL DISTANCE TO THE EXITS.EXIT LIGHTS, EMERGENCY
 LIGHTS, AND LOCATION OF FIRE EXTINGUISHER MAY ALSO BE
 INCLUDED ON THIS PLAN SHEET.
  
 10.ON SHEET E2.1, EXPLAIN RATIONALE FOR EXIT LIGHTS
 DIRECTING PATRONS IN CORRIDOR 123 AND 125.
  
 11. SHOW THE LOCATION OF THE 2A:10BC FIRE
 EXINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
 12.NO EXIT LIGHTS OR EMERGENCY LIGHTING SHOWN ON SHEET
 ID-6. CORRELATE WITH SHEET E3.1.
  
 13. THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED.
 (SEE NOTE #2 AND #12 ON SHEET FA0.1.
  
 14.AMEND NOTE #17 ON SHEET FA0.1 TO REFLECT LOCAL
 REQUIREMENT:DELETE "SUPERVISORY SIGNAL ONLY"INSERT
 "GENERAL FIRE ALARM".
  
 15.EXPLAIN THE DIFFERENCE/RATIONALE IN FIRE ALARM
 DEVICES LOCATED IN THE TWO CONFERENCE ROOMS (108 AND
 117) ONE BEING COMBINATION AUDIBLE/VISUAL AND THE OTHER
 ONLY VISUAL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDIACTING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 12:38 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 12:38 Sent To P
Notes
2008-09-03 12:39:03TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 10:27 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 10:27 Sent To E
Notes
2008-09-03 10:27:45TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 13:57 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 13:57 Sent To P
Notes
2008-08-28 13:58:12TO "PLUMB"KEN S.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-08-18 Cont ID  
Sent By adarroug Date 2008-08-18 Time 08:40 Rev Time 0.00
Received By adarroug Date 2008-08-18 Time 08:40 Sent To E
Notes
2008-08-18 08:41:05TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-07-02 Cont ID  
Sent By adarroug Date 2008-07-02 Time 10:38 Rev Time 0.00
Received By adarroug Date 2008-07-02 Time 10:38 Sent To B
Notes
2008-07-02 10:38:35TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:38 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:38 Sent To E
Notes
2008-06-17 16:39:05TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-23 Cont ID  
Sent By adarroug Date 2008-05-23 Time 11:32 Rev Time 0.00
Received By adarroug Date 2008-05-23 Time 11:32 Sent To E
Notes
2008-06-04 15:44:596/3/08--ELECT. SHEETS PULLED FROM REVISION PER
 CONTRACTOR, AND LUIS MARTINEZ.PLANS ROUTED TO RON
 REGUEIRO'S DESK.
2008-05-23 11:33:25TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 14:07 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 14:07 Sent To M
Notes
2008-05-21 14:08:06TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 10:40 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 10:40 Sent To M
Notes
2008-05-05 10:41:06TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-20 Cont ID  
Sent By adarroug Date 2008-03-20 Time 15:52 Rev Time 0.00
Received By adarroug Date 2008-03-20 Time 15:52 Sent To B
Notes
2008-03-20 15:52:53TO "JWITME" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 14:39 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 14:39 Sent To P
Notes
2008-03-13 14:39:58TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 19:17 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 19:17 Sent To  
Notes
2008-01-10 19:18:08SENT TO COMMERICAL BOARD # 43 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 11:41 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 11:41 Sent To  
Notes
2007-11-27 14:43:51TO "COMM" BD#59
2007-11-15 11:42:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-14 Cont ID  
Sent By mawillia Date 2007-09-14 Time 10:43 Rev Time 0.00
Received By mawillia Date 2007-07-27 Time 11:47 Sent To  
Notes
2007-07-27 11:47:15TO "COMM" BD#15

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-06-06 Cont ID  
Sent By rregueir Date 2008-06-06 Time 16:03 Rev Time 0.00
Received By rregueir Date 2008-06-06 Time 15:47 Sent To PC
Notes
2008-06-06 16:02:59ENGINEER LETTER FOR DUCT SIZE CHANGE DATED 5/20/08

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-06-06 Cont ID  
Sent By rregueir Date 2008-06-06 Time 15:57 Rev Time 0.00
Received By rregueir Date 2008-06-06 Time 15:47 Sent To PC
Notes
2008-06-06 15:56:56PAGE M2.1 REVISION #12

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-05-21 Cont ID  
Sent By rregueir Date 2008-05-21 Time 15:34 Rev Time 0.00
Received By rregueir Date 2008-05-21 Time 15:11 Sent To PC
Notes
2008-05-21 15:34:35PG M2.1 REVISION 10 CONTAINS THE SEAL OF MIRCEA PELLA
 BUT APPEARS TO HAVE BEEN SIGNED BY SOMEONE OTHER THAN
 MR PELLA OR SIGNED BY MR. PELLA IN A MANNER OTHER THAN
 HIS LEGAL SIGNATURE WHICH IS ON FILE WITH THIS OFFICE.
 PLEASE PROVIDE PLANS PROPERLY SIGNED AND SEALED BY THE
 DESIGNER OF RECORD IN ACCORDANCE WITH FS 471.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-02-04 Cont ID  
Sent By rregueir Date 2008-02-04 Time 15:12 Rev Time 0.00
Received By rregueir Date 2008-02-04 Time 14:26 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-01-04 Cont ID  
Sent By rregueir Date 2008-01-04 Time 14:34 Rev Time 0.00
Received By rregueir Date 2008-01-03 Time 16:56 Sent To PC
Notes
2008-01-04 14:34:18REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 COMMENT #3 IS THE ONLY OUTSTANDING COMMENT FROM
 PREVIOUS REVIEWS.
 PG M0.1, REFERENCE TO ASHRAE 62.1-2004 HAS BEEN REMOVED
 FROM PLANS. CALCULATIONS ARE DECLARED TO BE BASED ON
 FBC, M TABLE 403.3. HOWEVER, NOTE #2 IN THE
 CALCULATIONSINDICATES THAT CALCULATIONS ARE BASED ON
 VARIABLE OR INTERMITTENT OCCUPANCY. THERE IS NO
 PROVISION FOR SUCH CALCULATIONS RELATED TO TABLE 403.3.
 THE FULL OUTSIDE AIR RATES ARE TO BE PROVIDED WHENEVER
 HE SPACES ARE OCCUPIED. ALSO, THE CONFERENCE AND LOBBY
 AREAS HAVE DIFFERENT OCCUPANT LOADS BASED ON TABLE
 403.3 AND THE OUTSIDE AIR REQUIREMENTS FOR THESE AREAS
 SHALL BE CALCULATED SEPARATELY AND IN ADDITION TO THE
 OFFICE AREAS. IF TABLE 403.3 IS TO BE USED, PLEASE BASE
 THE DESIGN ON THE REQUIREMENTS OF THIS SECTION. DO NOT
 MIX THE REQUIREMENTS OF 403.3 WITH ASHRA 62.1. PLEASE
 CORRECT AND RESUBMIT.
 NOTE: IF THIS WERE THE FINAL ISSUE REQUIRED TO BE
 RESOLVED FOR PERMIT, IT MAY HAVE BEEN COVERED WITH A
 PROVISO. HOWEVER, A PASSED ELECTRICAL REVIEW IS ALSO
 PENDING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-30 Cont ID  
Sent By rregueir Date 2007-11-30 Time 11:45 Rev Time 0.00
Received By rregueir Date 2007-11-29 Time 15:31 Sent To  
Notes
2007-11-30 11:45:02REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
  
  
 NOTE: THE WRITTEN RESPONSE FROM ERDMANN & ASSOCIATES
 INDICATES THAT RESPONSES TO SEVERAL COMMENTS WERE TO BE
 PROVIDED BY OTHER PROFESSIONALS. NO SUCH RESPONSES WERE
 FOUND IN THE RESUBMITTAL PACKAGE. WRITTEN RESPONSES TO
 REVIEW COMMENTS ARE NOT A REQUIREMENT. HOWEVER, THEY DO
 SERVE TO EXPEDITE THE PROCESS AND CLARIFY DESIGN
 INTENT.
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. THIS COMMENT WAS NOT ADDRESSED. SEE OUTSIDE AIR
 CALCULATIONS ON PG M0.1.
  
 4. OK
  
 5. OK
  
 6 AND 7: A) ID-1A INDICATES THAT RATED WALLS AT THESE
 LOCATIONS ARE EXISTING AND PART OF BASE BUILDING PLANS.
 NO SUCH WALLS ARE SHOWN ON BASE BUILDING PLANS.
 B) M2.1 SHOWS LAY-IN GRILLS IN CEILINGS FOR ROOMS 104
 AND 127, BUT ID-1A CALLS FOR RATED CEILINGS. THERE IS
 NO INDICATION OF OPENING PROTECTIVES AT THESE CEILING
 PENETRATIONS.
 C) M2.1 ROOM 127 SHOWS TWO FIRE DAMPERS INSTALLED AT
 THE NORTH WALL. ACCORDING TO WALL DETAILS ON ID-1A THIS
 WALL DOES NOT GO TO DECK, RATHER IT TERMINATES 6 INCHES
 ABOVE THE CEILING. HOW ARE FIRE DAMPERS TO BE INSTALLED
 IN THIS WALL? ARE THEY TO BE BELOW THE CEILING? FIRE
 DAMPERS SHALL BE INSTALLED AS PART OF A RATED ASSEMBLY
 IN ACCORDANCE WITH FBC, M 607.2.
 D) HP-1 IS SHOWN PROVIDING SUPPLY AIR TO ROOMS 104 AND
 127. RETURN FOR HP-1 AND BASE BUILDING AC SYSTEM ARE
 SHARING A COMMON RETURN PLENUM AS AIR FROM ROOM 127 IS
 SHOWN RETURNING TO THE ABOVE CEILING PLENUM. FAN
 SHUT-DOWN BY SMOKE DETECTOR FOR HP-1 SHALL BE REQUIRED
 IN ACCORDANCE WITH FBC, M 606.2.2. SMOKE DETECTOR SHALL
 BE TIED INTO THE BUILDING FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC, M 606.4.
 E) ACCORDING TO PG ID-1A, HP-1 WILL BE LOCATED ABOVE A
 FIRE RATED CEILING. SHOW THIS EQUIPMENT TO BE SERVICE
 ACCESSIBLE IN ACCORDANCE WITH FBC, M 306.1.
  
 8. OK
  
 9. THIS COMMENT HAS BEEN ADEQUATELY ADDRESSED. THERE IS
 NO CODE DEFICIENCY RELATED TO THIS COMMENT.
 FOR INFORMATION PURPOSES ONLY: BASED ON A CONFERENCE
 WITH DAVID ALLEN AND TOM JOYNER (AHA ENGINEERING),
 FIRE/SMOKE DAMPERS ARE NOT REQUIRED IN TENANT
 SEPARATION WALLS FOR THE FUNCTION OF THE SMOKE CONTROL
 SYSTEM. THIS CHANGE MAY BE INCORPORATED INTO AN UPDATED
 TENANT DESIGN MANUAL. CONSULT WITH BUILDING MANAGEMENT
 REGARDING THIS CHANGE AS CHANGING THIS DESIGN PRIOR TO
 RESUBMITTAL COULD ELIMINATE THE NEED FOR REVISIONS
 RELATED TO THESE AREAS AFTER PERMIT ISSUANCE.
  
 10. OK
  
 11. COMPLIANCE WITH FBC 13-411.1.ABC.1.4 FOR WATER FLOW
 CONTROLS HAS NOT BEEN SHOWN.
  
 12. OK
  
 13. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-05 Cont ID  
Sent By rregueir Date 2007-08-05 Time 15:33 Rev Time 0.00
Received By rregueir Date 2007-08-05 Time 12:40 Sent To  
Notes
2007-08-05 15:33:36---------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. BASED ON THE DETERMINATION OF THE BUILDING OFFICIAL,
 APPLICATIONS FOR TENANT IMPROVEMENT PERMITS PRIOR TO
 C.O. OF THE BASE BUILDING REQUIRE SHOP DRAWING REVIEW
 BY THE BASE BUILDING DESIGNER(S) OF RECORD. HAVE
 DESIGNER(S) OF RECORD REVIEW CONSTRUCTION DOCUMENTS
 PRIOR TO RESUBMITTAL AND, IF FOUND SUFFICIENT, AFFIX
 THEIR SHOP DRAWING REVIEW STAMP AND SIGNATURE ON SAID
 DOCUMENTATION.
  
 2. AT THIS TIME THE BUILDING IS NOT EXISTING AS A C.O
 HAS NOT BEEN ISSUED. ADDITIONALLY, THE ENERGY
 CALCULATIONS FOR THE BASE BUILDING ARE BASED ON
 ASSUMPTIONS FOR A SHELL BUILDING UNDER FBC 13-101.1.6.
 UNLESS THE BUILDING IS COMPLETED AS PER ALL ASSUMPTIONS
 MADE IN THE ORIGINAL CODE COMPLIANCE SUBMITTAL, A
 REVISED CODE SUBMITTAL(S) USING METHODS A, B OR C SHALL
 BE SUBMITTED WHEN COMPLETION OF THE BUILDING (OR PART
 OF THE BUILDING) IS PERMITTED.
  
 3. M0.1: IN SEVERAL LOCATIONS, SCHEDULES REFERENCE
 ASHRAE 62-01. NOTE THAT PER FBC 2004 W/ 2006 UPDATES,
 THE CORRECT REFERENCE STANDARD IS ASHRAE 62.1-2004.
 ALSO, THE CODE ALLOWS FOR COMPLIANCE WITH ETHER FBC,M
 TABLE 403.3 OR ASHRAE 62.1-2004. RATHER THAN CITING
 BOTH STANDARDS AT ONCE, ONE METHOD OF COMPLIANCE OR THE
 OTHER SHOULD BE DECLARED ON PLANS. FBC 106.1.1
  
 4. M0.1 FAN SCHEDULE: CONTROL FOR EXHAUST FANS IS
 STATED AS "LIGHT INTERLOCK." EXHAUST FANS IN TOILET
 ROOMS SHALL RUN CONTINUOUS OR WHENEVER AIR IS BEING
 SUPPLIED TO THE SPACE AS ALL AIR SUPPLIED TO SPACES
 REQUIRED TO HAVE MECHANICAL EXHAUST SHALL BE EXHAUSTED
 PER FBC,M 403.2.1.
 NOTE: PROVISIONS SHALL ALSO BE MADE TO ASSURE
 VENTILATION IS PROVIDED WHENEVERA ROOM OR SPACE IS
 OCCUPIED PER FBC,M 401.3.
  
 5. M2.1: EF-1 AND EF-2 DUCTS ARE UNDER POSITIVE
 PRESSURE AND THEREFORE SHALL NOT BE LOCATED IN OR PASS
 THROUGH A PLENUM PER FBC,M 601.3.
  
 6. M2.1 NOTE #8: THIS NOTE INDICATES WALLS ARE ONLY TO
 EXTEND TO CEILING HEIGHT. HOWEVER, FLOOR PLAN AND WALL
 DETAIL ON PG ID-1A SHOW THE WALL BETWEEN ROOMS 103 AND
 104 AS TYPE "B" WHICH IS CONTINUOUS FROM FLOOR TO DECK.
 THIS WILL NOT ALLOW FOR RETURN OF AIR IN PLENUM SPACE
 TO THE AIR HANDLING EQUIPMENT. COORDINATE PLANS AND
 SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN
 ACCORDANCE WITH FBC,M 601.4.
  
 7. M2.1 GENERAL NOTES: NOTE CALLS FOR NO CEILING IN
 ROOM 104. HOWEVER, FLOOR PLAN SHOWS 24X24 LAY-IN TYPE
 DIFFUSERS AND GRILLS. PLAN ALSO SHOWS HP-1 ABOVE A
 CEILING WITH AN ACCESS PANEL. PLEASE CLARIFY. ALSO, IF
 THERE IS NO CEILING IN ROOM 104, IT MAY BE CONSIDERED
 PART OF THE PLENUM SPACE AND WILL BE SUBJECT TO THE
 RESTRICTIONS OF FBC,M 602.2.1 AND NFPA 90A-02 SEC
 4.3.10.
  
 8. M2.1: SIZES OF LARGE RECTANGLE DUCTS FROM MECH ROOM
 ARE NOT SHOWN ON PLANS. PLEASE CLARIFY AND RESUBMIT.
  
 9. INSTALLATION OF FIRE DAMPERS IN TRANSFER OPENINGS IN
 THE NEW TENANT SEPARATION WALLS MAY INTERFERE WITH THE
 PERFORMANCE OF THE BASE BUILDING SMOKE CONTROL SYSTEM
 AND AS SUCH IS PROHIBITED PER FBC,M 607.2.1. PLEASE
 SHOW MEANS OF APPROVED ALTERMANTIVE PROTECTION FOR
 THESE OPENINGS.
  
 10. M2.1: SOME GRILL AND CFM DESIGNATIONS ARE MISSING
 FROM PLAN IN ROOM 102. PLEASE CORRECT AND RESUBMIT.
  
 11. M2.1: HP-1, PLEASE SHOW SOURCE AND ROUTING OF
 CONDENSER WATER PIPING FOR THE HEAT PUMP. ALSO SHOW THE
 MEANS AND LOCATION OF CONDENSATE DISPOSAL TO BE IN
 COMPLIANCE WITH FBC,M SEC 307.2. NOTE: ALSO SHOW
 COMPLIANCE WITH FBC 13-411.1.ABC.1.4 FOR WATER FLOW
 CONTROLS.
  
 12. M5.1 SOUND BOOT DETAIL: PLEASE REFERENCE THE
 CORRECT CODE UNDER WHICH THIS PROJECT IS DESIGNED (FBC
 2004).
  
 13. ENGINEER HAS NOT USED FULL SIGNATURE TO SIGN/SEAL
 MECHANICAL PLANS AS REQUIRED BY F.S. 471. IT APPEARS
 THAT THE ENGINEER HAS USED INITIALS WHEN COMPARED TO
 THE FULL SIGNATURE WHICH WAS USED TO SIGN/SEAL THE
 PLUMBING PLANS IN THIS SAME SET OF DRAWINGS. PLEASE
 CORRECT AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-09-09 Cont ID  
Sent By kstevens Date 2008-09-09 Time 12:13 Rev Time 0.00
Received By kstevens Date 2008-09-09 Time 12:13 Sent To  
Notes
2008-09-09 12:15:51SUBMITTAL OK -- ROHL A3606LM FAUCET -- NSF-61 COMPLIANT
 UNDER ASME A112.18.1-2005/CSA125.1-05 TESTING (SEE
 STANDARDS)

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-09-05 Cont ID  
Sent By kstevens Date 2008-09-05 Time 10:30 Rev Time 0.00
Received By kstevens Date 2008-09-05 Time 10:30 Sent To  
Notes
2008-09-05 10:36:28SUBMITTAL DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SUBMITTAL SUBMITTED SHOWS COMPLIANCE WITH THE
 REQUIREMENTS OF ASME & CSA STANDARDS, BUT NOT FOR THE
 NSF-61 REQUIREMENT INDICATED IN SECTION 424.1. PLEASE
 SUBMIT NSF-61 LISTING FOR THE FAUCET OR HAVE THE FAUCET
 TESTED BY AN APPROVED TESTING AGENCY INDICATING THAT
 THE FAUCET CONFORMS TO THE NSF-61 REQUIREMENT ALONG
 WITH THE SUBMITTAL FROM IAPMO SUBMITTED FOR APPROVAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-09-03 Cont ID  
Sent By kstevens Date 2008-09-03 Time 07:40 Rev Time 0.00
Received By kstevens Date 2008-09-03 Time 07:40 Sent To  
Notes
2008-09-03 07:41:57REVISION OK -- SHT P0.1

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-03-29 Cont ID  
Sent By kstevens Date 2008-03-29 Time 16:04 Rev Time 0.00
Received By kstevens Date 2008-03-29 Time 16:04 Sent To  
Notes
2008-03-29 16:09:03REVISIONS APPROVED.--SHT PO.1 SEE PROVISO FROM
 PREVIOUS REVIEW, AND PROVISO WHA REQD ON D.W SUPPLY
 LINE. 604.9.--SHT P2.1.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-27 Cont ID  
Sent By kstevens Date 2007-12-27 Time 16:20 Rev Time 0.00
Received By kstevens Date 2007-12-27 Time 16:20 Sent To  
Notes
2007-12-27 16:24:02 
  
  
  
 PASSED/PROVISO:
 BREAK ROOM SINK NOT APPROVED. MANUF. SPECIFICATION
 SHEETS DO NOT SHOW THE FAUCET MEETING THE STANDARDS
 REQUIRED IN SECTION 424.1. MANUF. SPECIFICATIONS SHALL
 MEET THE REQUIREMENTS OF ASME A112.18.1 OR SCA B125 AS
 WELL AS NSF-61 SECTION 9. THIS INFORMATION IS REQUIRED
 AT THE TIME OF PLUMBING FINAL.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By kstevens Date 2007-12-03 Time 16:31 Rev Time 0.00
Received By kstevens Date 2007-12-03 Time 16:31 Sent To  
Notes
2007-12-03 16:46:11DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. THE BASE BUILDING HAS NOT RECIEVED A CERTIFICATE OF
 OCCUPANCY AT THIS TIME. THE BUILDING OFFICIAL HAS
 DETERMINED THAT ALL PLANS SHALL BE REVIEWED BY THE
 DESIGNERS OF THE BASE BUILDING FOR ALL TENANT
 BUILDOUTS. PLANS SHALL BE STAMPED AS REVIEWED BY BASE
 BUILDING DESIGN TEAM PRIOR TO RESUBMITTING FOR REVIEW
 AT THE CITY WPB. (SEE COMMENTS BY MECHANICAL REVIEW,
 (1), ELECTRICAL REVIEW, (4), AND BUILDING (2)).--
 SINCE THE BUILD-OUT G.C. IS A DIFFERENT COMPANY FROM
 THE BASE BUILDING G.C., A LETTER IS REQUIRED FROM THE
 DEVELOPER, SIGNED BY THE BASE BUILD G.C. AND THE SHELL
 G.C., STATING THAT ALL PARTIES UNDERSTAND THAT NO
 DISPUTE OVER WORK SCOPE OR RESPONSIBILITY CAN COME
 BEFORE THE REQUIREMENT FOR COMPLIANCE WITH FLORIDA
 BUILDING CODE.
 ****RESPONSE NOTED, BUT THE LETTER REQUESTED FROM THE
 DEVELOPER, SIGNED BY THE GENERAL CONTRACTORS HAS NOT
 BEEN SUBMITTED.
  
 5. SHTS ID-1 THRU ID-15 SHALL HAVE THE SIGNATURE AND
 DATE THE SEAL AND SIGNATURE WERE AFFIXED TO PLANS. IT
 APPEARS THAT INITIALS HAVE BEEN USED IN PLACE OF
 SIGNATURE WHEN SEALING THE PLANS. IF THIS INDEED THE
 LEGAL SIGNATURE OF THE INTERIOR DESIGNER, THEN A
 SIGNED, SEALED, NOTORIZED LETTER INDICATING THE
 INTERIOR DESIGNER'S LEGAL SIGNATURE SHALL BE SUBMITTED
 FOR OUR FILES. FAC 61G1-16.003,61G1-16.004(5) &
 481.2055.
 ****RESPONSE NOTED, BUT THE DATE THAT THE SIGNATURE AND
 SEAL WERE AFFIXED ON THE PLANS HAS NOT BEEN INDICATED
 AS REQUIRED.
  
 6. OK
 7. OK
 8. OK
 9. OK
  
 10. SUBMIT A DETAIL FOR THE TOILET ROOM FIXTURES
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS. SHOW THE CLEAR
 FLOOR SPACE FOR ALL ACCESSIBLE FIXTURES ON THE FLOOR
 PLAN AS WELL AS THE TURNING AREA IN BOTH TOILET ROOMS.
 SUBMIT ELEVATIONS TO SHOW COMPLIANCE FOR ALL OTHER
 REQUIREMENTS.
 ****RESPONSE NOTED, BUT COMPLIANCE FOR THE FOLLOWING IS
 NOT SHOWN:
 ___FOR THE W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS (42" REQD ON SIDE)
 THE LAV FAUCET SHOWN ON THE PLAN IS A KOHLER MODEL
 PK272, BUT THE ATTACHED SPECIFICATION BOOK INDICATES
 THE FAUCET AS A KOHLER MODEL K-394, (APPROVED), PLEASE
 CLARIFY AND CORRELATE.
  
 11. OK
  
 12. THE SINK IN THE BREAKROOM, (ROOM #112), SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. ELEVATION
 A1/ID-14 INDICATES CABINET DOORS. THE DOORS ARE NOT
 APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE DELETED
 FROM DETAIL. FORWARD APPROACH IS REQUIRED. SHOW CLEAR
 FLOOR SPACE ON THE FLOOR PLAN AND OTHER REQUIREMENTS ON
 THE ELEVATION. (NOTE: THE GARBAGE DISPOSAL SHALL BE ADA
 APPROVED. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 SHOWING APPROVAL).
 ****RESPONSE NOTED, BUT COMPLIANCE NOT SHOWN FOR
 SECTION 11-4.24.7 FAUCET, AND THE GARBAGE DISPOSAL
 SEPCIFICATION SHEETS HAS NOT BEEN SUBMITTED.
  
 13. OK
  
 14. DELETED - OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-01 Cont ID  
Sent By kstevens Date 2007-09-01 Time 13:09 Rev Time 0.00
Received By kstevens Date 2007-09-01 Time 13:09 Sent To  
Notes
2007-09-01 14:02:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INTERIOR DESIGN DOCUMENTS PREPARED BY A REGISTERED
 INTERIOR DESIGNER SHALL CONTAIN A STATEMENT THAT THE
 DOCUMENT IS NOT AN ARCHITECTURAL OR ENGINEERING STUDY,
 DRAWING, SPECIFICATION OR DESIGN AND IS NOT TO BE USED
 FOR CONSTRUCTION OF ANY LOAD BEARING COLUMNS,
 LOAD-BEARING FRAMING OR WALLS OF STRUCTIURES, OR
 ISSUANCE OF ANY BUILDING PERMIT, EXCEPT AS OTHERWISE
 PROVIDED BY LAW.FS 481.2131. PLEASE SHOW COMPLIANCE.
  
 2. INDICATE WHICH CODES PLANS WERE DESIGNED TO AND
 OCCUPANCY CLASSIFICATION ON THE PLANS. SECTIONS 106.1.1
 & 106.3.5.1.1(2)(7).
  
 3. ALL SHEETS REQUIRE THE ADDRESS AND TENANT SPACE IN
 THE TITLE BLOCK PER SECTION 106.1.1. FLORIDA
 ADMINISTRATIVE CODE. AFTER SUITE NUMBER IS ASSIGNED
 PLEASE INDICATE ADDRESS & SUITE NUMBER IN TITLE BLOCK.
  
 4. THE BASE BUILDING HAS NOT RECIEVED A CERTIFICATE OF
 OCCUPANCY AT THIS TIME. THE BUILDING OFFICIAL HAS
 DETERMINED THAT ALL PLANS SHALL BE REVIEWED BY THE
 DESIGNERS OF THE BASE BUILDING FOR ALL TENANT
 BUILDOUTS. PLANS SHALL BE STAMPED AS REVIEWED BY BASE
 BUILDING DESIGN TEAM PRIOR TO RESUBMITTING FOR REVIEW
 AT THE CITY WPB. (SEE COMMENTS BY MECHANICAL REVIEW,
 (1), ELECTRICAL REVIEW, (4), AND BUILDING (2)).--
 SINCE THE BUILD-OUT G.C. IS A DIFFERENT COMPANY FROM
 THE BASE BUILDING G.C., A LETTER IS REQUIRED FROM THE
 DEVELOPER, SIGNED BY THE BASE BUILD G.C. AND THE SHELL
 G.C., STATING THAT ALL PARTIES UNDERSTAND THAT NO
 DISPUTE OVER WORK SCOPE OR RESPONSIBILITY CAN COME
 BEFORE THE REQUIREMENT FOR COMPLIANCE WITH FLORIDA
 BUILDING CODE.
  
 5. SHTS ID-1 THRU ID-15 SHALL HAVE THE SIGNATURE AND
 DATE THE SEAL AND SIGNATURE WERE AFFIXED TO PLANS. IT
 APPEARS THAT INITIALS HAVE BEEN USED IN PLACE OF
 SIGNATURE WHEN SEALING THE PLANS. IF THIS INDEED THE
 LEGAL SIGNATURE OF THE INTERIOR DESIGNER, THEN A
 SIGNED, SEALED, NOTORIZED LETTER INDICATING THE
 INTERIOR DESIGNER'S LEGAL SIGNATURE SHALL BE SUBMITTED
 FOR OUR FILES. FAC 61G1-16.003,61G1-16.004(5) &
 481.2055.
  
 6. SHT ID-1A IF TOILET STALLS ARE PROVIDED, THAN AT
 LEAST ONE SHALL BE A STANDARD TOILET STALL COMPLYING
 WITH SECTION 11-4.17 EXCEPTION: NEW CONSTRUCTION(1) AND
 SHALL CONTAIN AN ACCESSIBLE LAVATORY WITH IT. (SEE FIG.
 11-30(E).
  
 7. SHT ID-2 WHITE OUT OR HAND WRITTEN CHANGES ARE NOT
 APPROVED ON SIGNED, SEALED PLANS. SECTION 106.1.3.
  
 8. SHT ID-3 FLOOR FINISH SCHEDULE. MORE INFORMATION
 REQUIRED. PER SECTION 1210.1 THE FLOOR SHALL HAVE A
 "SMOOTH, HARD, NONABSORBENT" SURFACE. PLEASE SUBMIT THE
 MANUF. SPECIFICATION FOR THE MEDIUM SATURNIA INDICATED
 ON THE SCHEDULE TO VERIFY COMPLIANCE. SECTION 106.1.2.
  
 9. SHT ID-3B WALLS WITHIN 2FT OF THE WATER CLOSETS
 SHALL HAVE A "SMOOTH, HARD, NONABSORBENT" SURFACE UP TO
 4FT ABOVE THE FLOOR. PLEASE INDICATE COMPLIANCE WITH
 SECTION 1210.2.
  
 10. SUBMIT A DETAIL FOR THE TOILET ROOM FIXTURES
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS. SHOW THE CLEAR
 FLOOR SPACE FOR ALL ACCESSIBLE FIXTURES ON THE FLOOR
 PLAN AS WELL AS THE TURNING AREA IN BOTH TOILET ROOMS.
 SUBMIT ELEVATIONS TO SHOW COMPLIANCE FOR ALL OTHER
 REQUIREMENTS.
  
 11. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE SHOW THE LOCATION AND SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-5.15 AND ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 12. THE SINK IN THE BREAKROOM, (ROOM #112), SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. ELEVATION
 A1/ID-14 INDICATES CABINET DOORS. THE DOORS ARE NOT
 APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE DELETED
 FROM DETAIL. FORWARD APPROACH IS REQUIRED. SHOW CLEAR
 FLOOR SPACE ON THE FLOOR PLAN AND OTHER REQUIREMENTS ON
 THE ELEVATION. (NOTE: THE GARBAGE DISPOSAL SHALL BE ADA
 APPROVED. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 SHOWING APPROVAL).
  
 13. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 SUBMIT ONE COPY OF SHEETS REMOVED FOR COMPARISON. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 14. SHT P31 SHOWS NO PLUMBING INFORMATION. PLEASE
 CLARIFY. THERE SEEMS TO BE ELECTRIC OR MECHANICAL
 INFORMATION THAT SHOULD BE TRANSFERED TO THE RESPECTIVE
 ELECTRIC OR MECHANICAL SHEETS. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]