Plan Review Details - Permit 07070315
Plan Review Stops For Permit 07070315
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-08-14 Cont ID  
Sent By lursu Date 2007-08-14 Time 11:41 Rev Time 0.00
Received By lursu Date 2007-08-14 Time 11:41 Sent To  
Notes
2007-08-14 11:42:51SITE ADDRESS REMAINS AS 9055 IBIS BLVD FOR THE NEW
 BUILDING SINCE THE EXISTING STRUCTURE WILL BE
 DEMOLISHED.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-28 Cont ID  
Sent By shill Date 2007-11-28 Time 16:13 Rev Time 0.00
Received By shill Date 2007-11-27 Time 16:39 Sent To  
Notes
2007-11-28 16:18:04****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE.THE PLANS MUST BE STAMPED AND THE
 RECEIPT PROVIDED.PLEASE CALL 233-5025 FOR MORE
 INFORMATION.
  
 2.A7.0 SHOWS 42'7" TO TOP OF BEAM.HOW CAN THE MEAN
 ROOF HEIGHT BE 40'?PLEASE CLARIFY DESIGN CRITERIA.
  
 3.EXPOSURE B IS DECLARED.AERIALS SHOW OPEN AREA
 EXCEEDING 600FEET.PLEASE PROVIDE INFORMATION
 REGARDING EXPOSURE B CONDITION AS IT APPEARS TO BE
 EXPOSURE C.PLEASE NOTE THAT THE DEFINITION OF
 EXPOSURE C HAS CHANGED EFFECTIVE DECEMBER 8, 2006
 FBC1609.4, FBC R301.2.1.4 (AVAILABLE AT
 WWW.FLORIDABUILDING.ORG).NOTE THAT FOR COMPONENTS AND
 CLADDING, COEFFICIENT FOR 45 FEET, EXPOSURE C IS 1.53
 (FBC TABLE 1609.6.2.1(4).HOW DOES THIS AFFECT MWFRS?
  
  
 4.PLEASE NOTE THAT GOVERNING CODE INCLUDES 2007
 AMENDMENTS EFFECTIVE JULY 1, 2007.
  
 5.PROVIDE LOUVER PRODUCT APPROVALS.
  
 6.THE MECHANICAL ENGINEER HAS REVISED THE STRUCTURAL
 ENGINEER'S DESIGN ON SHEET M7.2.PLEASE INCORPORATE
 INTO STRUCTURAL SHEETS.ALSO PLEASE NOTE THAT THERE IS
 NO VERTICAL REINFORCEMENT AT BOTH SIDES; HAS THE
 STRUCTURAL ENGINEER DETERMINED THAT THIS IS NOT
 NECESSARY FOR THIS TWO STORY BUILDING?
  
 7.PLEASE SEE PREVIOUS COMMENT #20 REGARDING HEADROOM,
 FBC11-4.4.2.CLEARANCE AT LANDINGS IS CLEAR, BUT WHAT
 ABOUT THE STAIRS LEADING TO THIS LANDING?
  
 7.PLEASE NOTE THAT IF THIS PLAN PASSES OTHER REVIEWS,
 PROVISO ITEMS CAN BE CONSIDERED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By jjohnsto Date 2007-09-04 Time 10:43 Rev Time 11.00
Received By jjohnsto Date 2007-09-04 Time 08:00 Sent To  
Notes
2007-09-04 10:49:37CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON,CBO PERMIT NO. 07070315
 BUILDING PLAN EXAMINERII ADDRESS 9055 IBIS
 E-MAIL:JJOHNSTON @WPB.ORG PROJECT: KITSON
 CORPORATE OFFICE CONTRACTOR: SHAKMAN
 HOSPITALITY LLC
  DATE: AUGUST30,2007
  
 PLANREVIEW
  
  109.3.10.1HURRICANE PROTECTION
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAIL TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  SUBMITTING PLAN CORRECTIONS
 WHEN RE-SUBMITTING PLANS WITH CORRECTIONS PLEASE
 PROCEED AS FOLLOWS:
  A.INDICATE THE CORRECTED ITEMS BY CLOUDING ON THE
 NEW CORRECTED SHEET
  B.REMOVE THE OLD SHEET FROM THE PLAN AND INSERT THE
 NEWLY CORRECTED SHEET
  C.PUT OLD THE OLD SHEETS TOGETHER AS ONE SET AND
 SUBMIT TO THE BUILDING DEPT. ALONG
 WITH THE NEW CORRECTED PLANS. THIS IS NECESSARY
 FOR THE PLAN REVIEWER TO CRITIQUE
 THE CORRECTION REQUIRED FROM THE PREVIOUS PLAN
 REVIEW.
 D.SUBMIT A COVER LETTER IDENTIFYING THE CORRECTION
 MADE LISTING THE ITEM REFERENCED
 IN THE REVIEWER?S COMMENTS.
  
 61G1-16.004TITLE BLOCK
 LANDSCAPE ARCHITECT? URBAN DESIGN STUDIOS
 A TITLE BLOCK ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION INDICATION SHEETS. THE TITLE
 BLOCK MUST AT A MINIMUM CONTAIN THE FOLLOWING
 INFORMATION:
 FIRM NAME,ADDRESS,TELEPHONE NUMBER
 FIRM LICENSE NUMBER,CERTIFICATE OF AUTHORIZATION NAME
 OR IDENTIFICATION OF PROJECT
 DATE PREPARED
 A SPACE FOR THE SIGNATURE AND DATED SEAL
 A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT
  
  
  ICE ? INTERNATIONAL CONSULTING ENGINEERS, INC.
  UP-DATE YOUR ADDRESS. IT DOES NOT CONFORM TO THE DBPR
 RECORDS
  
 2. FBC506.2506.3AREA INCREASE
  NOTE ON PLAN ALLOWED PER CODE DEFINED
  
  WINDOWS / DOORS PRODUCT APPROVALS
  PRODUCT APPROVALS ARE REQUIRED FOR WINDOWS /
 DOORS/MULLIONS/ROOFING ASSEMBLIES
  WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72FLORIDA PRODUCT APPROVAL
 SUBMIT TWO COPIES OF EACH APPROVAL WITH
 FLORIDA PRODUCT APPROVAL COVER SHEET THE ARCHITECT?S /
 ENGINEER?S SIGNATURE AS APPLICABLE, STATING TO THE BEST
 OF THEIR KNOWLEDGE THE
 PRODUCT APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
  NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN
 PRESSURE BY LEGACYFPA
  
 SUBMIT PRODUCT APPROVALS WIDTH FLORIDA
 PRODUCT APPROVAL COVER
 PAGE FOR THE FOLLOWING
  FIXED GLASS
  MULLION TUBES
  STORE FRONT GLAZING SYSTEM
  ALUMINUM OUT SWING DOORS
 HOLLOW METAL DOORS
 TRUSS ANCHORS
  
  FBC13-100.2 ENERGY CALCULATIONS
  COVER SHEET ENERGY CALCULATIONS INFORMATION. THIS IS A
 2 STORY BUILDING
 COMPLETE OWNER AND ADDRESS INFORMATION
 FIRST FLOOR UN-FINISHED
 SECOND FLOOR FINISHED
 ENTER CORRECT SQUARE FOOTAGE FIRST AND
 SECOND FLOOR
  
 FBC-13-400. A METHOD A IS FOR A COMPLETED
 BUILDING AND STATES ( 2NDPARAGRAPH) EXCEPT
 DESIGNS WITH NO MECHANICAL SYSTEM.
 FBC-13-400.2.A.2 SHELL BUILDING ON THE FIRST FLOOR
 FBC-13-400.3.C METHOD CFOR THE 2ND FLOOR
 ZONE 1IS THE LOBBY NOT RECEPTIONIST AREA
 WINDOWTYPE A ON FIRST FLOOR(44) NOT 40
  COMPLETE ALL ITEMS WITH CORRECT INFORMATION
  
  FBCTABLE 1609.6.2 (14)MEAN ROOF HEIGHT
 USE 40 FEET. PROVIDE ON PLAN EXPOSURE B,
 ADJUSTMENT FACTOR 1.09
  FBCTABLE 1609.6.2 (12)NET DESIGN WIND PRESSURE
  
 PRODUCT APPROVALS
 ROOF TILEPRODUCT APPROVAL LEGACYREPORT
 PLAN STATES SPANISH SROOF TILE
 TABLE 3 PAGE 8 OF 12 EXPOSURE BWIND LOADS
 AT 140 MPH, MEAN ROOF HEIGHT 40,UPLIFT28
 BASED ON THIS INFORMATION, HIGHLIGHT
 FASTENERS TO BE USED ON USED ON TABLE 2 SCHEDULE
 TAMKO FLORIDA PRODUCT APPROVAL HAS EXPIRED
  
 CANOPIES
 STATE ON PLANS ?ALL CANOPIES UNDER SEPARATE
 PERMIT?
  
 1906.2.2.1SHORING & RESHORING
 SUBMIT PLAN FOR REMOVAL OF SHORES AND
 RE-SHORING
  
 SHEET S-4
 STRUCTURAL NOTES - INCLUDE THE STATEMENT 2004
 FBC WITH 2006 SUPPLEMENTS
  
 SHEETLS-1
 NOTE ON PLAN AREA INCREASE ALLOWEDFBC-506.2 &
 506.3
  
  FBC -3006.1 ELEVATOR MACHINE ROOM
  CAN?T HAVE A MACHINE ROOM LOCATED IN A TENANT SPACE
  
  ELEVATOR PITWATERPROOFINGFBC1802.2.3 FBC
 1807.2.2 FBC1807.3.3
  PROVIDE INFORMATION ON PLAN FOR SLAB ELEVATION AT BASE
 OF SHAFT AND WATERPROOFING OF WALLS AND SLAB
  
  
 3. FBC -3006.1 ELECTRICAL ROOM
  CAN?T HAVE AN ELECTRICAL ROOM LOCATED IN A TENANT
 SPACE
  
  11-4.6.4SINAGEHANDICAP SIGN
  PROVIDE THE DETAIL OF HANDICAP SIGN WITH HEIGHT,
 REQUIRED INFORMATION ON SIGN, SYMBOL
  
  DOOR SCHEDULE
  IDENTIFY THE DOORS ON THE FLOOR PLAN AS DESCRIBED ON
 DOOR SCHEDULE
  
  FBC-11-4.4.2 FIGURE8-C-1 HEADROOM
  A-7.2A-7.3VERIFY HEADROOM FIRST FLOOR TO LANDING
  
  FBC ? 11-7.2COUNTER ACCESSIBILITY
  (1)36?MAX HEIGHT COUNTER
  (2)FOLDING SHELF
  
  FBC-11-4.13.5ROOM 219
  CLEAR WIDTH ON LATCH SIDE OF DOOR IN OUT-SWING
 POSITION REQUIRES 18?
  
  FBC-11-4.1.3(11)ALL TOILET ROOMS SHALL BE
 ADAPTABLE
 THIS MEANS THE TOILET ROOMS SHALL REQUIRE THE CORRECT
 WIDTH AND REQUIRED BACKING FOR HANDICAP
 FIXTURES SHOULD THEY BE NEEDED IN THE FUTURE.
  
 FBC-1210.2RESTROOMS
 GYPSUM BOARD MUST BE NON-ABSORBENT, NOTE ON PLANS
  
 FBC-11-4.23, 11-4.24-7ACCESSIBILITY
 LUNCH ROOM SPACE 240NEEDS CLEAR FLOOR SPACE UNDER
 SINKS FOR FORWARD APPROACH
  
 FBC-1609 GENERATOR
 SUBMIT SPECIFICATIONS, FASTENING TO SLAB FOR MOMENT OF
 OVERTURNING
  
 FBC- 1406.2.2EIF?S
  ARCHITECTURAL TRIM OVER 40 FEET IN HEIGHT
  A-5.1 CANNOT BE COMBUSTIBLE
  
  STRUCTURAL SHEET1-5.2
  PROVIDE SECTION THROUGH GUARD RAIL (RAILING) DETAIL
 1-2-3
  
  STRUCTURAL SHEETWINDOW JAMBS
  IDENTIFY DOWELS IN MASONRY UNITS
  
 ARCHITECTURAL SHEETA-10.0BALCONY
  REQUIRES SECOND DRAIN
  
  TRUSSES-TRUSS REPORT
  LATERAL LOADS NOT IN COMPLIANCE,CHECK CHART WITH
 SIMPSON@ WWW.STRONGTIE.COM
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2007-10-12 Cont ID  
Sent By mawillia Date 2007-10-12 Time 07:41 Rev Time 0.00
Received By mawillia Date 2007-10-12 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-30 Cont ID  
Sent By dpalmer Date 2007-11-30 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2007-11-30 Time 13:02 Sent To  
Notes
2007-11-30 13:03:25 
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW COMMENTS BASED ON SOME INFORMATION
 ONLY NOW SUBMITTED FOR REVIEW.
  
  
 1) NOTE: PLEASE PROVIDE AND SUBMIT THE ORIGINAL PERMIT
 APPLICATION BACK WITH THE RESUBMITTED PLANS FOR THIS
 SCOPE OF WORK. PLEASE SEE THE PERMIT APPLICATION WHICH
 WAS SUBMITTED AND PLACED IN PACKAGE WAS FOR PERMIT
 #07070314 FOR SITE CLEARANCE AND DEMO/SITE WORK.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #5 REQUESTED
 THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 GENERATOR/FUEL TANK AND ATS TO BE SUBMITTED. THE SHEETS
 FOR THE GENERATOR WAS SUBMITTED HOWEVER NOT THE SHEETS
 FOR THE ATS.
 PLEASE ALSO SEE NO SPECS WERE SUBMITTED FOR FUEL TANK
 FOR REVIEW BY FIRE AND MECHANICAL.
 PLEASE KNOW THESE ARE REQUIRED AT THIS TIME. PLEASE SEE
 COMMENTS FROM OTHER TRADES SUCH AS MECHANICAL FOR
 POSSIBLE COMMENTS.
 PLEASE PROVIDE MINIMUM CLEARANCE INFORMATION FOR THE
 GENERATOR ON ALL SIDES OF UNIT. THE SIDE FACING THE
 CONDENSING UNITS SEEMS TO BE LESS THAN THE MINIMUMS
 WHICH THIS OFFICE HAS SEEN AS SET-FORTH FROM
 MANUFACTURE AND RECOMMENDED CLEARANCES. PLEASE KNOW ALL
 CLEARANCES PER NEC 110.26 SHALL ALSO BE REQUIRED.
 110.3, 90.7,
 FBC 106.1.2
  
 ** FN:BASED ON TANK PROVIDED AND SIZE OF GENERATOR
 WITH FUEL CONSUMPTION LISTED ON CUT SHEETS, THIS WILL
 NOT PROVIDE THE 72HRS AS STATED. AS THIS IS AN OPTIONAL
 STAND-BY SYSTEM, THE TIME IS NOT OF CONCERN HOWEVER
 RECORD PLANS SHOULD PROVIDE ALL INFORMATION.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #6. PLEASE SUBMIT
 COMPLETED ENERGY CALCULATIONS WHICH MEET THE FBC AND
 CORRELATE WITH ALL ELECTRICAL DESIGNS FOR LIGHTING
 FIXTURESETC ON PLANS.
 PLEASE BE SURE ALL FIXTURES ON PLANS COORDINATE WITH
 THE INPUT DATA REPORTS FOR ALL INTERIOR AND EXTERIOR
 LIGHTING.
 PLEASE SEE SOME OF THE FOLLOWING EXAMPLES WHERE THESE
 DO NOT CORRELATE.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE REST
 OF THIS COMMENT.
 FOR EXAMPLE: PLEASE SEE THE FIRST ITEM ON THE IDR WHICH
 IS THE LOBBY LIGHTING WHICH INDICATES A 260W FIXTURE
 WHEREAS NEITHER THE PLANS NOR THE FIXTURE LEGEND HAS
 ANY 260W FIXTURE.
 FOR EXAMPLE: PLEASE SEE THE FIXTURE WS4 WHICH IS ON
 PLANS AND FIXTURE LEGEND HOWEVER THE IDR DOES NOT ANY
 OF THESE 75W FIXTURES.
 FOR EXAMPLE: PLEASE SEE THE EXTERIOR LIGHTING FIXTURES
 WD26 WHICH DO APPEAR TO BE ON THE IDR AND/OR WATTAGE
 DOES NOT CORRELATE.
 FOR EXAMPLE: PLEASE SEE THE TOTAL NUMBER OF *EXTERIOR
 LIGHTING FIXTURES* DO NOT CORRELATE WITH THE IDR.THIS
 SHOULD INCLUDE ALL LIGHTING FIXTURES EVEN IF THEY ARE
 THE 2ND FLOOR EXTERIOR LIGHTS.
 FOR EXAMPLE: THE TOTAL SQ FT AND ASSUMPTIONS REQUIRED
 FOR SHELL SPACE HAVE NOT AND ARE NOT INCLUDED.
  
 THESE ARE A FEW EXAMPLES AND NOT ALL ITEMS. PLEASE
 CORRELATE ALL REQUIRED INFORMATION AND ALL INFORMATION
 ON PLANS WITH THAT OF THE IDR, SUMMARY AND TOTALS ON
 THE METHOD *B* AS SUBMITTED.
 PLEASE SEE 13-101.1.6, 13-415.2, 13-415.1.B AND ALL
 SECTIONS AS GIVEN IN FIRST REVIEW; 13-4, 13-101.1,
 13-414.2(2)(3)M 13-415.1.ABC.2, 13-415.1.ABC.1.4,
 13-415.2.ABC.1.3 ETC.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTE #9 WHICH REQUESTED TO
 SUBMIT COMPLETED PHOTO-METRICS FOR EGRESS PATHS
 INDICATING THE MINIMUM LIGHTING LEVELS FOR FLAT EGRESS
 SURFACES AS WELL AS BOTH STAIR AREAS. PLEASE SEE LS 101
 7.8.1.3, 7.9.2.2.
 PLEASE ALSO SEE THE FLORIDA ADMINISTRATIVE CODE
 61G15-33.004 AS THIS IS REQUIRED.
 THE RESPONSE ADDRESSED OTHER PARTS OF PREVIOUS NOTE
 HOWEVER THIS WAS NOT ADDRESSED AND NONE WERE SUBMITTED
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 ** PLEASE KNOW AS NO LIGHTING LEVELS WERE SUBMITTED
 NONE COULD BE REVIEWED AT THIS TIME.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #17 WHICH MENTIONED
 FOR ALL A/C CU DISCONNECTS TO MEET 110.26.
 THE RESPONSE MENTIONS THIS WILL BE FIELD VERIFIED. THIS
 IS CORRECT HOWEVER THE PLANS ARE STILL REQUIRED TO SHOW
 MINIMUM CODE COMPLIANCE.
 PLEASE SEE UNIT LAYOUT ON E4.2 AS DISCONNECTS ARE STILL
 BE SHOWNON TWO WALLS BEHIND UNITS.
 ** THIS IS AN ITEM WHICH WOULD NORMALLY BE REDLINED IF
 THIS WAS OF THE *MINOR* COMMENTS HOWEVER AS PLANS ARE
 COMING BACK FOR OTHER CORRECTIONS PLEASE SHOW *MINIMUM*
 CODE COMPLIANCE AT THIS TIME.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #20 FOR MEANS OF
 DISCONNECT FOR FEEDERS AT THE MAIN BUILDING FOR THE
 FEEDERS FROM THE OUTSIDE MAIN.
 THE RESPONSE GIVES A LONG EXPLANATION WHICH GOES INTO
 CODES IN CHAPTER 7 WHICH ARE KNOWN TO THIS OFFICE.
 PLEASE KNOW THIS PROJECT LOCATION AND BUILDING DOES NOT
 MEET THE EXCEPTION FOR UNDER SINGLE MANAGEMENT AND
 QUALIFIED PERSONNEL AND DOCUMENTED SAFE DISCONNECTING
 PRACTICES.
 PLEASE SEE AS STATED ON PREVIOUS COMMENTS; PLEASE
 PROVIDE DISCONNECTING MEANS FOR FEEDERS AS REQUIRED PER
 225.31-225.39.
 THE SECTIONS GIVEN IN THE RESPONSE LETTER FOR THE
 GENERATOR WHICH REFLECTS FEEDERS FROM *OUTDOOR
 GENERATOR* SETS FOR 700 AND 701 DO NOT APPLY AS THE
 SYSTEM AS SHOWN ON PLANS IS THAT OF 702. THE SECTION
 702.11 IN THE 2005 NEC WAS REVISED TO INCLUDE THE
 SECTION WHICH WAS PREVIOUSLY IN 700 AND 701 FOR OUTDOOR
 GENERATORS, HOWEVER WHEN SPEAKING OF 702.11 THIS
 SECTION REQUIRES THE DISCONNECTING MEANS TO BE *
 READILY ACCESSIBLE* AND *WITHIN SIGHT*. PLEASE SEE NEC
 100 FOR DEFINITIONS OF BOTH. THE GENERATOR IS WITHIN
 SIGHT(50FT) HOWEVER THE DISCONNECT MEANS DOES NOT
 MEET READILY ACCESSIBLE BASED ON PLANS AND INFORMATION
 SUBMITTED.
 IN EITHER CASE AS STATED ABOVE THE DISCONNECTING MEANS
 (W/OUT OCP) FOR THE FEEDERS IS STILL REQUIRED.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #21 FOR GROUNDING
 ELECTRODE SYSTEM. RESPONSE MENTIONS TO SEE DETAILS ON
 5.1 AND 7.1 HOWEVER EITHER SHEET DOES NOT PROVIDE THE
 INFORMATION NEEDED. WHERE IS THE GROUNDING ELECTRODE
 SYSTEM SHOWN FOR THE MAIN SERVICE LOCATION. RISER SHOWS
 THAT THERE WILL BE ONE, BUT GROUND RODS, HOW MANY,
 SIZE, WHAT TYPE ETC IS NOT SHOWN
 MAIN BUILDING DETAIL DOES SHOW TO CONCRETE ENCASED
 ELECTRODE BUT IT IS ONLY BEING ASSUMED THAT THIS IS THE
 FOOTER STEEL AS REQUIRED.
 (DETAIL ON E7.1 MENTIONS THERE WILL BE A GROUND LOOP)
 PLEASE PROVIDE MORE INFORMATION OR SHOW DETAIL FOR MAIN
 SERVICE GE-SYSTEM PER 250.50,-250.56
  
 8) NOTE: PLEASE SEE PREVIOUS NOTE #23 WHICH SPOKE OF
 THE REQUIRED DEDICATED CIRCUITS FOR ELEVATOR MACHINE
 ROOMS/PIT HOIST-WAY CIRCUITS.
 THE RESPONSE MENTIONS THAT CIRCUIT HP-16 WAS ALREADY
 PROVIDED. THIS IS TRUE, THIS CIRCUIT WAS PROVIDE
 HOWEVER AS STATED ON PREVIOUS COMMENT, THIS MAY NOT
 FEED ANY OTHER LOCATIONS EXCEPT THE AREA IN WHICH IS
 STATED IN THE CODE.
 PLEASE ALSO SEE THE RESPONSE MENTIONS THAT IT IS THE
 CONTRACTORS RESPONSIBILITY TO NOT CONNECT ON THE LOAD
 SIDE OF THE GFI. THE PREVIOUS REVIEW COMMENT DID NOT
 SAY ANYTHING ABOUT ANY CONNECTIONS TO THE LOAD SIDE OF
 THE GFI NOT DID THE COMMENT GIVE A SECTION IN THE CODE
 WHICH STATES THIS.
 PLEASE SEE THE PLANS. PLEASE SEE SPECIFICALLY SHEET
 E4.1, DETAIL #2 E4.1 WHICH SHOWS CIRCUIT HP1-16 FEEDING
 BOTH THE ELEVATOR ROOM GFI RECEPTACLES AND ALSO THE
 ELEVATOR PIT GFI RECEPTACLES. THESE ARE NOT PERMITTED
 AND PLEASE ADJUST CIRCUIT(S).
 PLEASE SEE SPECIFICALLY SHEET E4.1 WHICH SHOWS CIRCUIT
 HP1-13 FEEDING BOTH THE MAIN ELECTRICAL ROOM LIGHTING
 ON FIRST FLOOR AS WELL AS THE LIGHTING IN PIT.
 ONCE AGAIN THIS IS NOT PERMITTED AND REQUIRES DEDICATED
 CIRCUITS.
 PLEASE SEE 620.23 AND 620.24.
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE #26. PLEASE PROVIDE
 METER CAN SIZES ON BUILDING. PLEASE VERIFY THE 600AMP
 METER CAN AS SHOWN.
 PLEASE SEE NOTE #26 FROM PREVIOUS REVIEW IS COPIED FOR
 SAME CLARIFICATION.
 PLEASE PROVIDE NOTE FOR *FLOATING NEUTRAL KIT REQUIRED
 * AT THE METERS AT THE BUILDING. 250.6, 250.24
 ***************************
 26) NOTE: PLEASE INDICATE THE SIZE/AMERAGE OF THE METER
 CANS ON THE RISER. PLEASE SEE THE METER WHICH IS SHOWN
 ONE E-4.2 FOR MAIN IS NOT INCLUDED ON RISER DIAGRAM
 SHEET E-5.1.
 PLEASE COORDINATE AND ADJUST PLANS AND SHOW SIZES OF
 EQUIPMENT.
 FBC 106.1.2, 106.3.5.1.2
 ************************
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #27. PLEASE SHOW AND
 INDICATES FEEDERS FROM GUTTER TO METERS, METERS TO
 MAINS AT THE BUILDING.
 PLEASE INDICATE
 ** PREVIOUS REVIEW NOTE **
 27) NOTE: PLEASE INDICATE THE SIZE OF FEEDERS FROM
 WIRE-WAY TO METERS TO MAINS ON E5.1.
 310.16, 215.5, 240.4
 FBC 106.1.2, 106.3.5.1.2
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE #28.
 THE RESPONSE MENTIONS THIS BREAKER IS 1200AMPS JUST
 LIKE THE SERVICE. THIS IS OK, HOWEVER THE PLANS ARE
 STILL REQUIRED TO SHOW AND INDICATE THE SIZE OF THE OCP
 DEVICE AT UNIT.
 AS THE RESPONSE LETTER IS NOT PART OF THE RECORD SET
 OF PLANS AND IS NOT PART OF THE DESIGN PLANS THE PLANS
 ARE REQUIRED TO CHANGE.
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO INDICATE THE OVER CURRENT PROTECTION
 ON THE GENERATOR. PLEASE SEE E5.1 AS AT THIS TIME THE
 CONDUCTORS FROM THE GENERATOR CAN NOT BE VERIFIED PER
 445.13, 310.16 AND 240.4.
  
 12) NOTE: PLEASE SEE NOTICE TO FLORIDA STATUTES
 553.80(2)(B) HAS BEEN ATTACHED WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 THIS NOTICE STAND FOR ALL TRADES AND IS NOT ONLY FOR
 ELECTRICAL.
 PLEASE KNOW ONE SET OF ELECTRICAL AND MECHANICAL PLANS
 ARE BEING RETAINED BY THIS OFFICE ALONG WITH ONE SET OF
 ENERGY CALCULATIONS.
 ** THIS NOTICE TO FS 553.80 IS ONLY A NOTICE GIVEN AT
 THIS TIME.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-11-28 15:36:1911/27/07
  
 ELECTRICAL REVIEW TO COMMENCE ONCE ONE SET OF PLANS
 BECOME AVAILABLE FROM OTHER TRADES CURRENTLY REVIEWING
 PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By dpalmer Date 2007-08-08 Time 12:29 Rev Time 0.00
Received By dpalmer Date 2007-08-06 Time 16:53 Sent To  
Notes
2007-08-08 12:29:462007-08-07 12:29:46
  
  
 ** DENIED **
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES AT
 A MINIMUM ARE STATED ON PLANS FOR MINIMUM DESIGN. THIS
 IS REQUIRED ON ARCHITECTURAL TITLE/COVER SHEET AS WELL
 AS ELECTRICAL PLANS.
 PLEASE SEE NOTE ON ELECTRICAL PLANS WHICH MENTIONS
 LOCAL CODE PER PALM BEACH COUNTY JURISDICTION. PLEASE
 KNOW THIS JOB AS APPLIED IS LOCATION IN THE CITY OF
 WEST PALM BEACH.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC)
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 REQUIRE OTHER CODES.
  
 2) NOTE: PLEASE SEE THAT ONCE THE ADDRESS OF THE
 PROJECT IS CONFIRMED ALONG WITH TENANT SUITE/UNIT
 NUMBERS FROM THE ADDRESSING REVIEWER, PLEASE BE SURE TO
 COMPLETE TITLE BLOCK WITH ALL INFORMATION AS
 DETERMINED.
 FLORIDA ADMINISTRATIVE CODE61G1-16.004, 61G15-23.002
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE SEE THE PERMIT APPLICATION REQUESTS FOR
 THE PROJECT TO BE DESCRIBED IN DETAIL, HOWEVER THE
 APPLICATION ONLY STATES *NEW BUILD*? PLEASE SEE THE SQ
 FT ON PERMIT APPLICATION DOES NOT MATCH WITH THE ENERGY
 CALCULATIONS ETC.
 PLEASE COORDINATE AND SEE POSSIBLE COMMENTS FROM OTHER
 TRADES.
  
 4) NOTE: PLEASE SEE THAT THE LANDSCAPE LIGHTING PLANS
 ARE REQUIRED TO BE SIGNED, DATED AND SEALED BY THE
 DESIGNER OF RECORD. PLEASE SEE SHEET 1 OF 1. FLORIDA
 STATUTES 481.221
 PLEASE SEE OTHER LANDSCAPE PLANS WHICH WERE NOT DATED
 WHEN SIGNED AND SEALED AS REQUIRED PER ABOVE FLORIDA
 STATUTES.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 5) NOTE: PLEASE SEE PLANS INDICATE A NEW GENERATOR,
 FUEL TANK AND ATS. PLEASE SUBMIT MANUFACTURES SPECS/CUT
 SHEETS FOR THESE ITEMS. PLEASE KNOW AS THE PLANS SEEM
 TO INDICATE A BI-FUEL UNIT, PLEASE OBTAIN THE LISTING
 AND INFORMATION ON THIS UNIT. IT IS KNOWN TO THIS
 OFFICE THAT THE GAS COMBUSTION CHAMBER AND ACCESSORIES
 ARE ADDED TO EQUIPMENT AFTER EQUIPMENT. IT IS ALSO THE
 UNDERSTANDING OF THIS OFFICE THAT THE EPA CERTIFICATION
 IS LOST ALONG WITH LISTING FROM THE MANUFACTURE AS THE
 DIESEL UNITS ARE MADE TO A LISTED STANDARD. PLEASE KNOW
 IF THESE ITEMS ARE ADDED AS AN AFTER MARKET CONVERSION,
 THE UNIT WILL BE REQUIRED TO BE RE-LISTED, AND
 CERTIFICATION FROM EPA WILL BE REQUIRED.
 PLEASE SUPPLY MORE INFORMATION ON UNIT AND
 SPECIFICATIONS AS REQUESTED. PLEASE SEE POSSIBLE
 COMMENTS FROM OTHER TRADES.
 NEC 110.3, 90.7.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SUBMIT CORRECTED AND COMPLETE ENERGY
 CALCULATIONS WITH COORDINATION WITH THE ELECTRICAL
 PLANS SUBMITTED.
 PLEASE SEE THE INPUT DATA REPORT AS THIS DOES NOT
 CORRELATE WITH PLANS FOR LUMINARIES TYPE, LUMINARIES
 WATTAGE, THE NUMBER OF LUMINARIES, METHOD OF CONTROLS,
 AREAS ETC.
 PLEASE SEE PAGE #2 FOR EXAMPLE OF THE INPUT DATA REPORT
 WHICH ONLY INDICATES A TOTAL OF TWO LUMINARIES WHEN THE
 PLANS IN FACT INDICATE A FAR GREAT NUMBER.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE ANY
 LIGHTING ENTERED FOR EXTERIOR LIGHTING?? HOW IS THIS
 POSSIBLE WHEN THE PLANS INDICATE NUMEROUS FIXTURES FOR
 EXTERIOR LIGHTING?
 PLEASE SEE 13-4, 13-101.1, 13-414.2(2)(3)M
 13-415.1.ABC.2, 13-415.1.ABC.1.4, 13-415.2.ABC.1.3
 ETC.
 PLEASE COORDINATE ALL FIXTURES, CONTROLS, AREAS,
 WATTAGE AND INFORMATION ON PLANS WITH THE ENERGY
 CALCULATIONS.
 PLEASE BE SURE TO UPDATE THE PROJECT ADDRESS
 INFORMATION ON THE CALCULATIONS COVER SHEET. PLEASE
 KNOW THAT AT THIS TIME THERE SEVERAL AREAS WHICH NEED
 TO BE ADDRESSED AND CHANGED AND REVISED CALCULATIONS
 MAY VERY WELL CONTAIN NEW COMMENTS AS THERE ARE ITEMS
 NOT YET SUBMITTED FOR REVIEW.
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 SUCH AS MECHANICAL REVIEW WHICH MAY AFFECT ENERGY
 CALCULATIONS AND METHOD USED.
  
 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS FOR FBC
 CHAPTER 13 NEED SOME CLARIFICATION. PLEASE SEE THERE
 ARE AREAS ON PLANS WHICH DO NOT CONTAIN ANY OVER RIDE
 DEVICES ON PLANS. PLEASE SEE *COMMON AREAS* FOR EXAMPLE
 ON SHEET E1.2, WHICH ONLY CONTAIN STANDARD SWITCHES.
 PLEASE PROVIDE SCHEDULING FOR SYSTEM(S). A BASE TIME ON
 PLANS SHALL BE INDICATED.
 PLEASE PROVIDE MAXIMUM TIMES FOR ALL OVER RIDE DEVICES.
 THIS WOULD INCLUDE TIMERS, OCCUPANCY SENSOR DEVICES
 ETC.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 8) NOTE: PLEASE KNOW AS REQUIRED PER LIFE SAFETY CODE
 AND THE FIRE MARSHALS OFFICE, THE FIRST FLOOR TENANT
 SPACES WHICH ARE NOT GOING TO BE BUILT AT THIS TIME
 WILL STILL REQUIRE SOME TYPE OF NORMAL LIGHTING WITH
 AUTOMATIC SHUT OFF CONTROLS.
 THIS CAN BE A MINIMUM OF FIXTURES.
 PLEASE SEE LS 101 7.8 AND 7.9. BATTERY BACK UP FIXTURES
 ARE ALREADY SHOWN BUT MAY NOT MEET THE MINIMUM NEEDED
 FOR MINIMUM LIGHTING LEVELS.
  
 9) NOTE: PLEASE SEE THE PLANS ARE MISSING MINIMUM
 EGRESS LIGHTING IN MANY AREAS. PLEASE SEE FOR EXAMPLE
 THE FOYER AREA ON THE FIRST FLOOR WHERE NO BATTERY BACK
 UP LIGHTING FIXTURES COULD BE LOCATED TO THE PUBLIC
 RIGHT OF WAY. PLEASE ALSO SEE 2ND FLOOR COMMON ARE
 CORRIDORS FOR ANOTHER EXAMPLE.
 PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR EGRESS PATHS
 INDICATING THE MINIMUM LIGHTING LEVELS FOR FLAT EGRESS
 SURFACES AS WELL AS BOTH STAIR AREAS. PLEASE SEE LS 101
 7.8.1.3, 7.9.2.2.
 PLEASE ALSO SEE THE FLORIDA ADMINISTRATIVE CODE
 61G15-33.004 AS THIS IS REQUIRED.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 ** PLEASE KNOW AS NO LIGHTING LEVELS WERE SUBMITTED
 NONE COULD BE REVIEWED AT THIS TIME.
  
 10) NOTE: PLEASE SEE PLANS ARE MISSING THE MINIMUM
 LEVELS FOR ADA COMPLIANCE FOR HORNS, STROBES AND
 HORN/STROBES.
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM
 LEVELS TO BE PLACED ON PLANS FOR SYMBOL LEGEND FOR FIRE
 ALARM DEVICES AND OR FA PLANS.
 PLEASE KNOW THAT EVEN AS THE FIRE ALARM PLANS WILL BE
 UNDER SEPARATE PERMITS, THE BASE DESIGN ON BASE
 BUILDING PLANS ARE REQUIRED TO MEET THE MINIMUM DESIGN
 LEVELS PER THE FBC.
  
 11) NOTE: PLEASE BE SURE TO CORRELATE THE LANDSCAPE
 LIGHTING PLANS WITH THE ELECTRICAL PLANS FOR FIXTURES,
 LOADS AND CIRCUITING. LANDSCAPE PLANS DO SHOW LIGHTING
 AT THIS TIME AND THE INTENT OF INSTALLATION.
 PLANS ALONG WITH THE ENERGY CALCULATIONS WILL BE
 REQUIRED TO BE UPDATED.
 310.16, 240.4, 408.4 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION
 REQUIRED ON PLANS.
  
 12) NOTE: PLEASE KNOW THE WIND LOAD ENGINEERING FOR
 SITE LIGHTING POLES WILL BE NEED FOR REVIEW FROM THIS
 STRUCTURAL REVIEWER. THIS IS BEING NOTED FOR
 INFORMATION AT THIS TIME.
  
 13) NOTE: PLEASE SEE THE SITE LIGHTING PLANS INDICATE A
 TITLE AND A BLOCK FOR *CITY OF WEST PALM BEACH LIGHTING
 REQUIRED*. PLEASE CLARIFY WHERE THIS INFORMATION IS
 FOUND AS THIS OFFICE CONTAINS NO SUCH REQUIREMENTS.
 THERE IS MAXIMUM ALLOWED WATTAGE AND ENERGY USE AS
 STATED IN THE FLORIDA BUILDING CODE AND CHAPTER 13 BUT
 WE DO NOT REQUIRE SPECIFICS AS STATED ABOVE. PLEASE
 CLARIFY.
 FBC 106.1.2
  
 14) NOTE: PLEASE GIVE CONSIDERATION FOR THE TYPE OF
 DEVICES BEING CHOSEN FOR NOT ONLY THE ELECTRICAL ROOM
 BUT FOR BOTH ELECTRICAL ROOMS AND ELEVATOR MACHINE ROOM
 LIGHTS.
 PLEASE SEE 110.26E FOR THE TYPE OF DEVICE.
  
 15) NOTE: PLEASE SEE THE LIGHTING PLANS FOR SECOND AND
 FIRST FLOORS CONTAINS A *KEYED NOTE* #2 WHICH MENTIONS
 THE CONNECTION OF LIGHTING AHEAD OF SWITCHES AND
 OCCUPANCY TYPE DEVICES.
 PLEASE SEE FBC 1006.1.2 AND LS 101 7.8.1.2.2 AUTOMATIC,
 MOTION SENSOR?TYPE LIGHTING SWITCHES SHALL BE PERMITTED
 WITHIN THE MEANS OF EGRESS, PROVIDED THAT THE SWITCH
 CONTROLLERS ARE EQUIPPED FOR FAIL-SAFE OPERATION, THE
 ILLUMINATION TIMERS ARE SET FOR A MINIMUM 15-MINUTE
 DURATION, AND THE MOTION SENSOR IS ACTIVATED BY ANY
 OCCUPANT MOVEMENT IN THE AREA SERVED BY THE LIGHTING
 UNITS.
 PLEASE SEE 7.8 AND 7.9 AS THE FAILURE OF A SINGLE
 CONTROL DEVICE SHALL NOT LEAVE ANY ONE AREA IN TOTAL
 DARKNESS.
  
 16) NOTE: PLEASE KNOW AS INFORMATION, THE LOW VOLTAGE
 AS SHOWN ON PLANS WILL BE REQUIRED TO BE UNDER A
 SEPARATE PERMIT. THESE PLANS MAY BE REFERENCED FOR THE
 WORK AS APPLIED AND SHOWN.
 ** INFORMATION ONLY AT THIS TIME AND NO CHANGES ARE
 NEEDED TO PLANS.
  
 17) NOTE: PLEASE SEE 110.26 OF THE NEC AS THE MINIMUM
 WIDTHS FOR DISCONNECTS AT THE CONDENSING UNITS IS NOT
 MET BY THE PLANS AND THE SCALE AS NOTED AND SHOWN.
 PLEASE SEE E4.2 FOR NORTH AND SOUTH YARDS.
  
 18) NOTE: PLEASE BE SURE PANEL SCHEDULES ARE SPECIFIC
 TO ALL ROOMS AND AREAS IN WHICH THEY FEED. PLEASE SEE
 THE USE OF *GENERAL RECEPTACLES AND GENERAL LIGHTS*
 NEEDS TO BE SPECIFIC. PLEASE SEE THIS COMMENT IS FOR
 ALL PANEL SCHEDULE WITH GENERAL DESIGNATIONS. PLEASE
 KNOW THE DESIGNATION MAY BE THE NUMERICAL DESIGNATION
 AS NOTED ON PLANS.
 PLEASE SEE 408.4 AND COMMENTARY AS EXTRACTED FROM THE
 NEC BELOW.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 19) NOTE: PLEASE CORRELATE RISER DIAGRAM WITH THE PANEL
 SCHEDULES FOR EQUIPMENT AS SUBMITTED.
 PLEASE SEE RISER SHEET E5.1 FOR EXAMPLE AS SHEET
 INDICATES A MAIN CIRCUIT BREAKER PANEL AND RISER DOES
 NOT.
 FBC 106.1.2
  
 20) NOTE: PLEASE SEE MISSING MEANS OF DISCONNECTS AT
 THE MAIN BUILDING AS THIS IS CONSIDERED A DETACHED
 STRUCTURE AND WOULD NEED TO COMPLY WITH 225.31-225.39.
 PLEASE LABEL ALL EQUIPMENT FOR MAINS AT THIS BUILDING.
 THE SERVICE MAIN OUTSIDE CAN NOT BE CONSIDERED THIS
 MAIN AS IT IS NOT PART OF THE BUILDING.
 PLEASE ADJUST AND PLACE NOTES ON PLANS FOR SIGNS OF THE
 BUILDING MAINS AND LOCATION FOR SERVICE MAIN.
  
 21) NOTE: PLEASE CLARIFY THE LOCATION OF THE GROUNDING
 ELECTRODE SYSTEM AS SHOWN. PLEASE SEE THE SYSTEM AS
 SHOWN APPEARS TO BE AT THE MAIN BUILDING WHICH IS
 REQUIRED AS IT IS A DETACHED STRUCTURE PER 250.32,
 HOWEVER PLEASE CLARIFY SYSTEM AT THE SERVICE MAIN
 LOCATION PER 250.50.
  
  
 22) NOTE: PLEASE CLARIFY FIRE SPRINKLER BOND PER
 250.104. THE DETAIL ON 7.1 INDICATES WATER PIPE,
 HOWEVER NOT CLEAR AS THIS APPEARS TO BE THE ONE FOR THE
 BUILDING.
  
 23) NOTE: PLEASE SEE 620.24C,AS THE ELEVATOR ROOM
 AND PIT LIGHTS/RECEPTACLES ARE REQUIRED TO BE ON A
 DEDICATED BRANCH CIRCUITS. PLEASE SEE SHEET FOR
 LIGHTING AND ELEVATOR ROOMS ON E4.1 AS SOME OF THESE
 CIRCUITS AS SHOWN ACTUALLY FEED OTHER AREAS. (EXAMPLE
 ELECTRICAL ROOM).
  
 24) NOTE: PLEASE PROVIDE INFORMATION ON PLANS FOR OVER
 CURRENT PROTECTION FOR ELEVATOR CAB LIGHTS. PLEASE SEE
 THE DETAIL ON E4.1 SHOWS THE DISCONNECT AS REQUIRED
 HOWEVER DOES NOT INDICATE THE OVER CURRENT PROTECTION
 WHICH IS REQUIRED TO BE THE SAME ROOM PER 620.22A.
  
 25) NOTE: PLEASE CLARIFY THE *TELCO* ROOM THAT THIS IS
 OR IS NOT AN IT ROOM BY DEFINITIONS.
 IF THIS IS GOING TO BE AN IT ROOM OR IF ANY OTHER
 LOCATION IS GOING TO BE USED FOR THIS SAME REASON,
 PLEASE SEE NEC 645.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 26) NOTE: PLEASE INDICATE THE SIZE/AMERAGE OF THE METER
 CANS ON THE RISER. PLEASE SEE THE METER WHICH IS SHOWN
 ONE E-4.2 FOR MAIN IS NOT INCLUDED ON RISER DIAGRAM
 SHEET E-5.1.
 PLEASE COORDINATE AND ADJUST PLANS AND SHOW SIZES OF
 EQUIPMENT.
 FBC 106.1.2, 106.3.5.1.2
  
 27) NOTE: PLEASE INDICATE THE SIZE OF FEEDERS FROM
 WIRE-WAY TO METERS TO MAINS ON E5.1.
 310.16, 215.5, 240.4
 FBC 106.1.2, 106.3.5.1.2
  
 28) NOTE: PLEASE BE SURE TO INDICATE THE OVER CURRENT
 PROTECTION ON THE GENERATOR. PLEASE SEE E5.1 AS AT THIS
 TIME THE CONDUCTORS FROM THE GENERATOR CAN NOT BE
 VERIFIED PER 445.13, 310.16 AND 240.4.
  
 29) NOTE: PLEASE CLARIFY THE DIMENSIONS ON THE WIRE-WAY
 AS THIS IS CURRENTLY SHOWN AS 8X8. PLEASE PROVIDE
 CALCULATIONS BASED ON THE CONDUCTORS AND RADIUS/BENDING
 SPACE ETC.
 PLEASE SEE 376.22
  
 30) NOTE: PLEASE SEE RISER SHEET E5.1 STATES THE
 AVAILABLE FAULT CURRENT HAS BEEN ASSUMED AND ALSO
 CONTAINS AN ADDITIONAL NOTE ON RISER WHICH MENTIONS TO
 BE VERIFIED BY CONTRACTOR.
 CONTACT SHOULD BE MADE TO THE FPL SERVICE PLANNER AT
 THIS TIME FOR THE CORRECT AVAILABLE FAULT CURRENT AND
 PLACE THE MINIMUM RATINGS ON THE PLANS AT THIS TIME.
 PLEASE SEE 110.9, 110.10
 PLEASE KNOW THIS IS REQUIRED ON THE DESIGN
 PROFESSIONALS PLANS AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-07 21:28:152007-08-07 21:28:15
  
 REVIEW COMPLETED. REVIEW NOTES TO FOLLOW ON 8/8/07
2007-08-07 07:12:432007-08-07 07:12:43
  
 1-SET IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-11-21 Cont ID  
Sent By rchokshi Date 2007-11-21 Time 14:33 Rev Time 0.00
Received By rchokshi Date 2007-11-21 Time 14:11 Sent To  
Notes
2007-11-21 14:32:57***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 COUND NOT FIND IN YOUR PACKAGE. PLEASE MAKE A SEPARATE
 PACKAGE FOR ENGINEERING REVIEW, SO, I GET IT WITHOUT
 LOST.
  
 2. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS
 THAT HOW DID YOU DETERMINE THE FIRST FLOOR ELEVATION?
 FIRST FLOOR ELEVATION MUST BE HIGHER THAN MAXIMUM CROWN
 OF THE ROAD BY ATLEAST 1 FOOT.
 3. PLEASE SHOW DETAIL OF THE CONTROL STRUCTURESWITH
 ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON
 DRAWINGS,PLEASE PROVIDE CALCULATION FOR EXFILTRATION
 TRENCHES IN WATER QUALITY CALS.PLEASE SHOW DRY
 DETENTION/WET DETENTION AREAS IN STORM WATER CALS.
 AFTER CONTROL STRUCTURE WHERE DOES STORM WATER GOES??
 4. PLEASE RESUBMIT A COPY OF SFWMD PERMIT,, & PROVIDE
 STORM WATER QUALITY CALCULATIONS. PLEASE RESUBMIT
 GEO-TECH REPORT WITH STORM WATER CALS. ALSOSTORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES.
 5. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By rchokshi Date 2007-09-11 Time 10:25 Rev Time 0.00
Received By rchokshi Date 2007-09-11 Time 10:14 Sent To  
Notes
2007-09-11 10:24:56***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON CIVIL DRAWING THE SITE PLAN SHOWING
 STREETS/ROADS AROUND THE SITE WITH NORTH ARROW.
 3.PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS
 THAT HOW DID YOU DETERMINE THE FIRST FLOOR
 ELEVATION??.
 6. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 7. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE
 SHOW DETAIL OF THE CONTROL STRUCTURESWITH
 ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON
 DRAWINGS,PLEASE SHOW CALCULATION FOR EXFILTRATION
 TRENCHES IN WATER QUALITY CALS.PLEASE SHOW DRY
 DETENTION/WET DETENTION AREAS IN STORM WATER CALS.
 AFTER CONTROL STRUCTURE WHERE DOES STORM WATER GOES??
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. PLEASE RESUBMIT GEO-TECH
 REPORT WITH STORM WATER CALS.STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 10. POLLUTION PREVENTION:HEIGHT OF THE SILTFENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 11. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-19 Cont ID  
Sent By mawillia Date 2007-12-19 Time 10:45 Rev Time 0.00
Received By mawillia Date 2007-12-19 Time 09:14 Sent To  
Notes
2007-12-19 10:10:13*****PROVISO****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS SP-2, LS-1, LS-2, A-2.4,
 A-5.1, FA1.1, FA1.2, FP0.1, FP1.1, FP1.2, AND FP7.1
 WERE STAMPED, INITIALED, AND DATED.HOWEVER, PLAN
 SHEETS E1.1 & E1.2 STILL NEED TO BE FIRE-STAMPED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By mawillia Date 2007-10-12 Time 21:51 Rev Time 0.00
Received By mawillia Date 2007-10-12 Time 07:41 Sent To  
Notes
2007-10-15 11:15:06*****DENIED*****
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 03.THE RELOCATED FIRE HYDRANTS SHALL BE INSTALLED,
 COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK,
  
 04.LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS
 TO FIRE PROTECTION EQUIPMENT AND DEVICES.
  
 05.NFPA 101, LIFE SAFETY CODE, 2003 EDITION AND THE
 FLORIDA FIRE PREVENTION CODE 2004 SHALL BE REFERENCED.
 THESE REFERENCES ARE INCORRECTLY SHOWN AS ONE LISTED ON
 THE LIFE SAFETY SHEETS.
  
 06.ON THE LIFE SAFETY SHEETS (LS-1 & LS-2), CLASS "D"
 FINISHES FOR ROOMS AND ENCLOSED SPACES IS LISTED.AS
 PER 38.3.3.2.2 , CLASS A, B, OR C SHALL BE LISTED IN
 THESE OTHER AREAS.
  
 07.ON SHEET LS-2, REFERENCE IS INCORRECTLY MADE TO
 1ST FLOOR - LIFE SAFETY.
  
 08.ON SHEET LS-2, PLEASE EXPLAIN RATIONALE FOR ONLY
 SHOWING TRAVEL DISTANCE TO ONLY 1 OF THE 2 STAIRWELLS.
  
 09.SPECIFY THE INTERIOR FLOOR FINISH FOR THE EXIT
 ENCLOSURES IN TERMS OF CLASS I OR CLASS II.
  
 10.PLEASE PROVIDE FLAME SPREAD DETAILS ON THE FABRIC
 OF THE PARKING CANOPY.
  
 11.HOW WILL THE INSTALLATION OF THE CARD ACCESS
 SYSTEM (CARD READERS) IMPACT ANY EXITING FROM THE EXIT
 STAIRWAYS?PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR CARD ACCESS SYSTEM.
  
 12.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING TO BE VISIBLE FROM
 IBIS BOULEVARD.AS PER WEST PALM BEACH CODE, THE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.
  
 13.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE
 LOCATION OF THE KNOX BOX.FOR APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 14.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR
 HANDRAILS/GUARD RAILS.
  
 15.SHOW/VERIFY THAT THE HEADROOM ON STAIRS SHALL NOT
 BE LESS THAN 80" AND SHALL BE MEASURED VERTICALLY ABOVE
 A PLANE PARELLEL TO AND TANGENT WITH THE MOST FORWARD
 PROJECTION OF THE STAIR DETAIL.
  
 16.NO TAMPER SWITCH (TS) AND FLOW SWITCH (FS) SHOWN
 ON THE FA1.1 SHEET.
  
 17.FIRE DEPARTMENT CONNECTION (FDC) SHALL BE EQUIPPED
 WITH KNOX LOCKING CAPS.FOR APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 18.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE
 REQUIRED ON THE FIRE LINE BACKFLOW DEVICE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 08:36 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 08:35 Sent To  
Notes
2007-11-15 14:51:37TO "COMM" BD#38
2007-11-05 08:36:15WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-12 Cont ID  
Sent By mawillia Date 2007-10-12 Time 21:52 Rev Time 0.00
Received By mawillia Date 2007-07-13 Time 08:59 Sent To  
Notes
2007-08-07 18:34:17MOVED TO COMM BOARD #36
2007-07-24 11:11:14TO "COMM" BD#37
2007-07-13 08:59:21WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-28 Cont ID  
Sent By rregueir Date 2007-11-28 Time 16:33 Rev Time 0.00
Received By rregueir Date 2007-11-26 Time 17:55 Sent To  
Notes
2007-11-28 16:34:45REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE REVISED NOTE #13 INDICATES AN AUDIBLE AND
 VISIBLE SIGNAL WILL BE LOCATED AT THE RESPECTIVE
 THERMOSTATS. IS THIS IN ADDITION TO THE GENERAL ALARM
 SIGNAL AS INDICATED BY NOTE 9(D) ON PG E5.2? ALSO,
 PLEASE COORDINATE THIS NOTE WITH NOTE #17 ON PG FA 1.2,
 WHICHINDICATES A VISIBLE AND AUDIBLE ALARM WILL BE
 SENT TO THE FACP. THIS IS LOCATED AT THE 1ST FLOOR
 LOBBY AND DOES NOT APPEAR TO BE A CONSTANTLY ATTENDED
 LOCATION.
  
 2. OK
  
 3. M1.1: THERE IS STILL ONE 12X8 EXHAUST DUCT
 PENETRATION (ASSOCIATED WITH KEY NOTE #2, AS STATED IN
 PREVIOUS REVIEW) WHICH IS NOT SHOWN AS BEING PROTECTED
 BY A FIRE DAMPER. SHOW COMPLIANCE WITH FBC,M 607.6 AND
 607.8.
  
 4. OK
  
 5. THE DESIGN INTENT IS STILL UNCLEAR. ON M7.2, DETAIL
 9 SHOWS THE PIPES ENTERING A FIRE RATED CHASE. ON M7.1,
 DETAIL 9 SHOWS A THROUGH-PENETRATION FIRESTOP SYSTEM
 FOR CONCRETE, INDICATING THIS IS A FLOOR/CEILING
 PENETRATION. A FLOOR/CEILING THROUGH-PENETRATION SYSTEM
 IS NOT NEEDED IF THE PIPE IS IN A FIRE RATED CHASE.
 ALSO, THE SYSTEM SPECIFIED IN THE DETAIL IS NOT
 APPLICABLE TO THIS LOCATION FOR THE FOLLOWING REASONS:
 A) IT ONLY ALLOWS FOR ONE PIPE PER HOLE.
 B) IT IS ONLY LISTED FOR STEEL PIPE. COPPER IS NOT PART
 OF ITS LISTING.
 C) IF THIS IS NOT FOR THE FLOOR/CEILING, BUT FOR WHERE
 THE PIPES LEAVE THE FIRE RATED CHASE, IT WILL NOT WORK
 BECAUSE IT IS ONLY LISTED FOR USE IN CONCRETE, NOT A
 FRAMED WALL OR SHAFT ASSEMBLY.
 ALSO, THERE IS NO FIRE RATED CHASE SHOWN ON
 ARCHITECTURAL FLOOR PLANS AT THESE LOCATIONS, ONLY
 PARTITIONS TO GO 6 INCHES ABOVE THE CEILING ACCORDING
 TO THE WALL LEGEND ON THE A PAGES. THERE IS NO LISTED
 ASSEMBLY FOR A FIRE RATED CHASE IN THE ARCHITECTURAL
 DETAILS. PLEASE CLARIFY THE INTENT AND DEMONSTRATE
 COMPLIANCE WITH FBC 712.4.
  
 6. OK
  
 7. OK
  
 8. THE ?ASSEMBLY AND DIMENSIONAL INFORMATION? PACKAGE
 SUBMITTED FOR FIRE DAMPERS DOES NOT INCLUDE THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. DETAIL 7 ON
 M7.1 DOES NOT CORRESPOND WITH RUSKIN INSTALLATION
 INSTRUCTIONS. OPTIONS:
 A) REMOVE THE CURRENT DETAIL FROM THE PLANS. PROVIDE A
 NOTE ON PLANS DEFERRING TO MANUFACTURER?S INSTALLATION
 INSTRUCTIONS. PROVIDE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS IN THE SUBMITTAL PACKAGE.
 B) INCLUDE THE MANUFACTURER?S INSTALLATION INSTRUCTION
 ON PLANS (IF ALLOWED BY MANUFACTURER, THIS IS NOT A
 RECOMMENDATION TO VIOLATE ANY COPYRIGHT.).
 SHOW COMPLIANCE WITH FBC, M 607.2.
  
 9. THE PRESCRIPTIVE FASTENING METHOD LISTED IN FBC, M
 301.13.1 IS ONLY APPLICABLE FOR GROUP R-3 OCCUPANCIES.
 IT IS NOT APPLICABLE TO THIS PROJECT. IN ANY OTHER
 OCCUPANCY, ENGINEERING IS REQUIRED BASED ON THE WIND
 SPEED AND WIND LOAD CALCULATIONS IN ACCORDANCE WITH FBC
 CH.16. OPTIONS:
 A) PROVIDE WIND LOAD CALCULATIONS FOR OUTDOOR EQUIPMENT
 WITH FASTENER DETAILS FOR BUILDING PLAN REVIEW. NOTE:
 DETAIL 3 ON M7.2 SHOWS INBED OR EXPANSION ANCHOR BOLTS
 TO BE USED ON CONDENSERS BUT KEY NOTES CALL FOR STRAPS
 AND TAPCONS.
 B) CHECK WITH EQUIPMENT MANUFACTURER. MANY
 MANUFACTURERS HAVE THEIR INSTALLATION INSTRUCTIONS
 TESTED AND CERTIFIED TO MEET WIND LOADS ALREADY. IF
 THIS IS THE CASE, MANUFACTURER?S INSTRUCTIONS MAY BE
 USED. A DETAIL MAY BE PROVIDED WHICH CORRESPONDS WITH
 THOSE INSTRUCTIONS AND A NOTE WHICH DEFERS TO
 INSTRUCTIONS MAY BE USED. IF THIS METHOD IS USED,
 PROVIDE DOCUMENTATION WHICH VERIFIES THAT THE
 MANUFACTURER?S INSTRUCTIONS HAVE BEEN TESTED AND MEET
 WIND LOADS FOR THIS AREA.
  
 10. OK
  
 11. ENERGY CALCULATIONS: METHOD B HAS BEEN SUBMITTED.
 HOWEVER, IT APPEARS THAT ONLY THE SPACES BEING
 BUILT-OUT ARE INCLUDED IN THE CALCULATIONS. AS STATED
 IN FBC 13-101.1.6, ?ALL ASSUMPTIONS MADE ABOUT FEATURES
 NOT INSTALLED UNTIL LATER THAT ARE NOT ON THE BUILDING
 PLANS SHALL BE LISTED AND APPENDED TO THE COMPLIANCE
 FORM SUBMITTED TO THE BUILDING DEPARTMENT.? NO
 ASSUMPTIONS ABOUT FEATURES TO BE INSTALLED IN THE
 UNFINISHED AREA COULD BE FOUND APPENDED TO THE
 CALCULATIONS. ALSO, THE PROJECT SUMMARY PAGE INDICATES
 THAT ONLY THE FINISHED AREAS WERE COUNTED IN THE
 CALCULATIONS. COOLING LOAD CALCULATIONS, A/C EQUIPMENT
 AND LIGHTING ASSUMPTIONS SHALL BE PROVIDED WITH THE
 COMPLIANCE FORM FOR ALL UNFINISHED AREAS OF THE
 BUILDING AND BE INCLUDED IN THE CALCULATIONS IN
 ACCORDANCE WITH THIS SECTION. ENERGY CALCULATIONS CAN
 NOT BE REVIEWED AT THIS TIME.
  
 12. OK
  
 13. OK
  
 14. RESPONSE INDICATES THAT THE GENERATOR IS NOT
 RELATED TO THE MECHANICAL DISCIPLINE. PLEASE SEE FBC, M
 915.1, WHICH STATES ?THE INSTALLATION OF LIQUID-FUELED
 STATIONARY INTERNAL COMBUSTION ENGINES AND GAS
 TURBINES, INCLUDING FUEL STORAGE AND PIPING, SHALL MEET
 THE REQUIREMENTS OF NFPA 37.? THIS CLEARLY MAKES DIESEL
 POWERED GENERATORS AND THEIR FUEL STORAGE SYSTEMS
 SUBJECT TO THE MECHANICAL CODE. THE MECHANICAL CODE
 REFERENCES NFPA 37, WHICH IS THE STANDARD BY WHICH THE
 GENERATOR INSTALLATION AND ITS FUEL STORAGE SYSTEM WILL
 BE REVIEWED BY THE MECHANICAL REVIEWER. NO INFORMATION
 HAS BEEN PROVIDED REGARDING DIESEL FUEL STORAGE FOR
 THIS GENERATOR. ALSO, IF THE DIESEL TANK EXCEEDS 550
 GALLONS; THE TANK, ITS INSTALLATION METHOD AND LOCATION
 MUST BE FIRST APPROVED BY PALM BEACH COUNTY DERM BEFORE
 SUBMITTAL TO THIS AHJ FOR PERMIT. CONTACT INFORMATION
 FOR PBC DERM WAS PROVIDED TO THE DESIGN TEAM DURING OUR
 MEETING IN THIS OFFICE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By rregueir Date 2007-08-08 Time 18:20 Rev Time 0.00
Received By rregueir Date 2007-08-07 Time 16:26 Sent To  
Notes
2007-08-08 18:20:10REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M0.2 MECHANICAL EQUIPMENT NOTE #13: DUCT SMOKE
 DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM
 PER FBC,M 606.4.1. EITHER A SUPERVISORY SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION OR ACTIVATION OF THE
 BUILDING'S ALARM NOTIFICATION DEVICES IS ACCEPTABBLE
 UNDER THIS CODE. HOWEVER, THE DESIGNER SHOULD CHECK
 WITH THE WEST PALM BEACH FIRE PREVENTION BUREAU (FIRE
 MARSHAL'S OFFICE) TO DETERMINE THEIR REQUIREMENTS FOR
 NOTIFICATION UPON ACTIVATION OF THE DETECTORS.
  
 2. M0.3: PROVIDE INFORMATION FROM EQUIPMENT
 MANUFACTURER SHOWING REQUIRED CLEARANCES OF OUTDOOR
 EQUIPMENT FOR SERVICE, MAINTENANCE AND REQUIRED AIRFLOW
 FOR EFFICIENT OPERATION. FBC 106.1.2
  
 3. M1.1: KEYED NOTES 2 AND 4, ONLY TWO OF THE FIVE 2ND
 FLOOR DUCT PENETRATIONS SHOW FIRE DAMPERS. FIRE DAMPERS
 ARE REQUIRED AT ALL DUCT PENETRATIONS OF 2ND FLOOR SLAB
 PER FBC,M 607.6. THE SPECIFIC LOCATION OF EACH FIRE
 DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED ON PLANS
 BY THE DESIGNER. FBC,M 607.8
  
 4. M1.1: REFRIGERANT LINES THROUGH 1ST FLOOR SLAB
 APPEAR TO PASS THROUGH STRUCTURAL FOOTERS IN TWO
 LOCATIONS. PROVIDE DETAIL SHOWING SIZE AND NUMBER OF
 SLEEVES GOING THROUGH THE FOOTERS FOR STRUCTURAL
 REVIEW. FBC 106.1.2
  
 5. M1.2: REFRIGERANT LINES FROM 1ST FLOOR ARE SHOWN IN
 2 REFIRGERANT CHASES. THE CHASES ARE NOT SHOWN AS FIRE
 RATED ON ARCHITECTURAL PLANS. THESE PENETRATIONS SHALL
 BE PROTECTED IN A FIRE RESISTANCE RATED ASSEMBLY PER
 FBC 712.4.1.1 OR PROTECTED BY AN APPROVED THROUGH
 PENETRATION FIRESTOP SYSTEM PER FBC 712.4.1.2. PROVIDE
 DETAIL AND TYPE OF ASSEMBLY TO BE USED.
  
 6.PROVIDE SUBMITTALS/INSTRUCTIONS FOR TITUS BYPASS
 TERMINALS.
  
 7. M1.2: KEY NOTE #9, THE 12X12 DUCT FROM 1ST FLOOR TO
 ROOF NEAR 2AHU-10 APPEARS TO PASS THROUGH THE 18X12
 RETURN DUCT. THESE DUCTS DO NOT LOOK LIKE THEY ARE
 INTENDED TO BE CONNECTED, BUT THAT'S HOW THEY APPEAR ON
 FLOOR PLAN. PLEASE CLARIFY.
  
 8. M7.1 DETAIL 7: FIRE DAMPERS LOCATED WITHIN AIR
 DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE REQUIREMENTS OF THIS SECTION, AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING
 PER FBC,M 607.2. IF THIS DETAIL IS NOT FROM THE
 MANUFACTURER, IT IS NOT ACCEPTABLE AND THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS MUST BE
 PROVIDED.
  
 9. M7.2 DETAIL 3: SHOW CONDENSING UNIT ATTACHMENT TO BE
 DESIGNED FOR THE 140 MPH WIND ZONE PER FBC,M 301.13 AND
 FBC CH.16
  
 10. ENERGY CALCULATIONS: PROJECT SUMMARY INDICATES MAX
 TONNAGE AT 3.4. THE LARGEST SYSTEM SHOWN ON PLANS IS 5
 TONS. ALSO, THE OWNER'S NAME AND THE ADDRESS OF THE
 PROJECT ARE MISSING. PLEASE CORRECT.
  
 11. ENERGY CALCULATIONS: FORM 400A HAS BEEN USED FOR
 THIS BUILDING. HOWEVER, EITHER METHOD B OR C SHALL BE
 USED. PLEASE SEE THE FOLLOWING REQUIREMENTS FOR ENERGY
 CALCULATIONS FOR SHELL BUILDINGS:
 "NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED." FBC 13-101.1.6
  
 12. PROVIDE AN AIR BALANCE SCHEDULE FOR THE SPACES
 BEING CONDITIONED TO ASSURE THAT THE BUILDING IS
 PRESSURIZED WITH RESPECT TO THE OUTDOORS. FBC
 13-409.1.ABC.2
  
 13. PROVIDE SHUTOFF DAMPER CONTROLS THAT WILL
 AUTOMATICALLY SHUT WHEN SYSTEMS OR SPACES SERVED ARE
 NOT IN USE. FBC 13-409.1.ABC.3.3
  
 14. PROVIDE ALL RELEVANT SUBMITTAL DATA FOR THE
 PROPOSED GENERATOR, INCLUDING INFORMATION ON FUEL
 STORAGE TANK TO BE USED.
 NOTE: GENERATORS ARE TO BE INSTALLED IN CONPLIANCE WITH
 NFPA 37-02. FUEL GAS PERMIT AND PBC DERM APPROVAL MAY
 BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-10 Cont ID  
Sent By kstevens Date 2007-12-10 Time 16:38 Rev Time 0.00
Received By kstevens Date 2007-12-10 Time 16:38 Sent To  
Notes
2007-12-10 17:01:56DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW: THE COMMENT NUMBER SHALL
 REMAIN THE SAME TO AVOID CONFUSION.
  
 1.OK
  
 2. SHTS 1 THRU 3 OF 3 & 1 THRU 7 OF 7. THE CERTIFICATE
 OF AUTHORIZATION NUMBER, (FIRM LICENSE NUMBER),IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET AS WELL AS
 THE DATED SEAL, SIGNATURE, AND PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT. FAC 61G1-16.003,
 61G1-16.004(2)(6) AND FS 481.219, 481.2055.--IT
 APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH A
 INITIALS, NOT A SIGNATURE. IF INDEED THIS IS THE LEGAL
 SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED,
 LEGALLY NOTORIZED LETTER INDICATING THE LEGAL ADDRESS
 OF THE LANDSCAPE ARCHITECT SHALL BE SUBMITTED FOR OUR
 FILES.
 ****RESPONSE NOTED, BUT SHT 7 OF 7 STILL SHOWS
 INITIALS, AND NO LETTER HAS BEEN SUBMITTED. --THE
 LICENSE FOR THE DESIGN PROFESSIONAL IS SHOWN IN
 DELINQUENT STATUS ON THE FLORIDA STATE DBPR WEBSITE.
 (SEE ATTACHED SHEET). PLEASE HAVE THE STATUS UPDATED
 PRIOR TO RESUBMITTING.
  
 3. SHT 1 0F 1. THE CERTIFICATE OF AUTHORIZATION NUMBER,
 (FIRM LICENSE NUMBER),IS REQUIRED IN THE TITLE BLOCK
 OF EACH SHEET AS WELL AS THE DATED SEAL, SIGNATURE, AND
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.003, 61G1-16.004(2)(6) AND FS 481.219,
 481.2055.--THE SHEET HAS NOT BEEN SIGNED, SEALED &
 DATED ALSO. SECTION 106.1.
 ****RESPONSE NOTED, AND COMMENT IS OK,BUT THE LICENSE
 FOR THE DESIGN PROFESSIONAL IS SHOWN IN DELINQUENT
 STATUS ON THE FLORIDA STATE DBPR WEBSITE. (SEE ATTACHED
 SHEET). PLEASE HAVE THE STATUS UPDATED PRIOR TO
 RESUBMITTING.
  
 4. SHT A-1.0 PER TABLE 403.1, MINIMUM FIXTURE
 REQUIREMENTS FOR THE FIRST FLOOR INCLUDE 4 W/C'S, 3
 LAVS & 2 DRINKING FOUNTAINS. PLEASE INDICATE MINIMUM
 FACILITIES.
 ****RESPONSE NOTED, BUT ONLY 3 W/C'S ARE SHOWN. 4 W/C'S
 REQUIRED.
  
 5. OK
 6. OK
 7. OK
  
 8. SHT A-3.0 DETAIL #3 TOI.ET ROOMS SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT NOT ADDRESSED. NO GRAB BARS
 SHOWN, NO CLEAR FLOOR SPACE SHOWN, STILL INDICATESAS
 ADAPTABLE. PLEASE SHOW THE TOILET ROOMS AS ACCESSIBLE.
 SECTION 11-4.1.3(11).
  
 9. SHT A-3.0 DETAILS #5 & #6 SINKS SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.--THE GARBAGE DISPOSALS SHALL BE ADA
 COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 WITH INSTALLATION INSTRUCTIONS. SECTION 106.1.2 MORE
 INFORMATION REQD.
 ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. NO
 CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN, DIMENSIONS
 AT TOE KICK NOT APPROVED. MAX 6" FROM WALL REQUIRED,
 ONE DETAIL SHOWS 1'1" AND THE OTHER INDICATES 8-1/4".
 PLEASE SHOW COMPLIANCE WITH FIG. 11-31.--ONLY ONE
 COPY OF THE GARBAGE DISPOSAL FOUND, AND IT IS NOT
 APPROVED. NO ADA APPROVAL IS SHOWN ON THE MANUF.
 SPECIFICATION SHEET.
  
 10. OK
  
 11. SHT A-9.0 DETAIL #6 SINK SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****RESPONSE NOTED, BUT COMPLIANCE SHALL BE SHOWN FOR
 THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.7 FAUCETS
  
 12. OK
 13. OK
  
 14. SHT A-9.1 DETAIL #3 SINK SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.7 FAUCETS
  
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P5.1 DOMESTIC WATER RISER DIAGRAM FOR RRW &
 RRWR DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE
 RISER AND FLOOR PLAN. SECTION 106.1.1. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED COMPLETLY. RISER STILL
 DOES NOT REFLECT THE FLOOR PLAN IN SOME AREAS.
  
 23. OK
 24. OK (INDICATED AS A BALLCOCK STYLE FLOAT VALVE. IF
 THERE IS AN AIR GAP, NO BACKFLOW IS REQUIRED).
  
 25. SHT P5.1 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. FUTURE 4" LINE FOR TENANT 2 IS
 SHOWN ON THE 2ND FLOOR OF THE THE RISER DIAGRAM.--
 THE FLOOR DRAIN SHOWN ON THE FLOOR PLAN NEAR ROOM 105
 IS NOT SHOWN ON THE SANT. RISER DIAGRAM.--THE
 CLEANOUT SHOWN ON THE FLOOR PLAN DOWNSTREAM OF THE LAV
 IN THE WOMENS TOILET ROOM 2ND FLOOR IS NOT SHOWN ON THE
 RISER DIAGRAM.--ONLY ONE EWC IS INDICATED. THE EWC
 BY THE RECEPTION AREA IS NOT SHOWN ON THE RISER
 DIAGRAM.--RISER SHOWS AN EXTRA FLOOR DRAIN AND VENT
 UPSTREAM OF THE ONE SHOWN IN THE ELEVATOR MACHINE ROOM,
 (TO BE DELETED PER SECTION 301.6).--NOTE #3 AT THE
 TWO WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER DOES NOT REFLECT KEY NOTE
 #3. PLEASE CHECK THAT THE RISER DIAGRAM. CORRELATES
 WITH THE FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE VENT FOR THE FLOOR DRAIN BY
 THE ELECTRICAL ROOM APPEARS TO OFFSET BELOW THE SLAB.
 PER SECTION 905.4 THE VENT SHALL RISE VERTICALLY A
 MINIMUM 6" ABOVE THE FLOOD RIM LEVEL PRIOR TO
 OFFSETTING HORIZONTALLY.--THE 4" BRANCH LINE FOR
 THE FUTURE TENANT IS SHOWN DOWNSTREAM OF THE SECOND
 FLOOR RISER ON THE FLOOR PLAN, BUT UPSTREAM OF THE
 RISER ON THE ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE.
  
  
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
  
 33. THE APPLICATION STATES "DESCRIBE PROJECT IN DETAIL"
 (FAILURE TO DO SO MAY RESULT IN DELAYS). IT APPEARS
 THAT THE SECOND FLOOR WILL BE BUILT OUT,BUT THE FIRST
 FLOOR WILL BE SHELL ONLY WITH THIS PERMIT. THIS IS NOT
 INDICATED ON THE PERMIT APPLICATION, (NEW BUILD).
 PLEASE INDICATE THE SCOPE OF WORK FOR THIS PERMIT AS
 REQUIRED ON THE APPLICATION.
 ****RESPONSE NOTED, WILL CHECK WHEN THE APPLICATION IS
 RETURNED.
  
 **********NEW COMMENT**********
  
 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL & FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****RESPONSE NOTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By kstevens Date 2007-09-06 Time 16:13 Rev Time 0.00
Received By kstevens Date 2007-09-05 Time 18:59 Sent To  
Notes
2007-09-06 18:10:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1.ALL SHEETS. THE ADDRESS OF THE PROJECT SHALL BE
 INDICATED IN THE TITLE BLOCK OF EACH SHEET. SECTION
 106.1.1.
  
 2. SHTS 1 THRU 3 OF 3 & 1 THRU 7 OF 7. THE CERTIFICATE
 OF AUTHORIZATION NUMBER, (FIRM LICENSE NUMBER),IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET AS WELL AS
 THE DATED SEAL, SIGNATURE, AND PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT. FAC 61G1-16.003,
 61G1-16.004(2)(6) AND FS 481.219, 481.2055.--IT
 APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH A
 INITIALS, NOT A SIGNATURE. IF INDEED THIS IS THE LEGAL
 SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED,
 LEGALLY NOTORIZED LETTER INDICATING THE LEGAL ADDRESS
 OF THE LANDSCAPE ARCHITECT SHALL BE SUBMITTED FOR OUR
 FILES.
  
 3. SHT 1 0F 1. THE CERTIFICATE OF AUTHORIZATION NUMBER,
 (FIRM LICENSE NUMBER),IS REQUIRED IN THE TITLE BLOCK
 OF EACH SHEET AS WELL AS THE DATED SEAL, SIGNATURE, AND
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.003, 61G1-16.004(2)(6) AND FS 481.219,
 481.2055.--THE SHEET HAS NOT BEEN SIGNED, SEALED &
 DATED ALSO. SECTION 106.1.
  
 4. SHT A-1.0 PER TABLE 403.1, MINIMUM FIXTURE
 REQUIREMENTS FOR THE FIRST FLOOR INCLUDE 4 W/C'S, 3
 LAVS & 2 DRINKING FOUNTAINS. PLEASE INDICATE MINIMUM
 FACILITIES.
  
 5. SHT A-2.0 PER TABLE 403.1, TWO DRINKING FOUNTAINS
 ARE REQUIRED. ONLY ONE IS SHOWN ON THE FLOOR PLAN.
 PLEASE INDICATE THE LOCATION OF TWO DRINKING FOUNTAINS
 ON THE FLOOR PLAN.
  
 6. SHT A-2.0 KEY NOTE #11 NOT FOUND. PLEASE INDICATE
 THE ROOM NUMBER KEY NOT CAN BE LOCATED. SECTION
 106.1.1.
  
 7. SHTS A-2.0, A-2.1, A-2.4, A-3.0 (DETAIL #2)AND SHT
 P1.2. PER SECTION 11-4.17.3 EXCEPTION NEW CONSTRUCTION
 (2), THE ACCESSIBLE W/C SHALL BE LOCATED IN THE CORNER
 DIAGONAL TO THE DOOR. THE W/C IN THE ACCESSIBLE STALL
 IN THE WOMENS TOILET ROOM (225) DOES NOT MEET THIS
 REQUIREMENT. PLEASE MOVE DOOR OR W/C TO COMPLY.
  
 8. SHT A-3.0 DETAIL #3 TOI.ET ROOMS SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.22 AND
 ALL SUBSECTIONS.
  
 9. SHT A-3.0 DETAILS #5 & #6 SINKS SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.--THE GARBAGE DISPOSALS SHALL BE ADA
 COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 WITH INSTALLATION INSTRUCTIONS. SECTION 106.1.2 MORE
 INFORMATION REQD.
  
 10. SHT A-9.0 DETAILS #2 & #5 THE FLUSH CONTROL FOR THE
 W/C SHALL BE TO THE WIDE SIDE OF THE W/C PER SECTION
 11-4.16.5. PLEASE SHOW ON DETAILS.
  
 11. SHT A-9.0 DETAIL #6 SINK SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 12. SHT A-9.0 DETAIL #12 THE URINAL SHALL BE
 ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTION
 11-4.18.4, MAX HEIGHT FOR FLUSH CONTROLS. (44").
  
 13. SHT A-9.0 DETAIL #12 THE LAVS SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTIONS 11-4.19.4 EXPOSED
 PIPES & SURFACES, AND 11-4.19.5 FAUCETS.
  
 14. SHT A-9.1 DETAIL #3 SINK SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 15. SHTS S-1 THRU S-6 THE ENGINEER SHALL LEGIBLY
 INDICATE THEIR ADDRESS IN THE TITLE BLOCK. FAC
 61G15-23.002(2) & FS 471.025.
  
 16. ALL M, E, P & FP SHEETS. THE ENGINEER SHALL LEGIBLY
 INDICATE THEIR ADDRESS AND IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, THE ADDRESS OF THE
 ENGINEERING BUSINESS IS REQUIRED AS WELL. FAC
 61G15-23.002(2) & FS 471.025. AS SHOWN, THE ADDRESS OF
 THE ENGINEER IS SHOWN, BUT THE ADDRESS OF THE
 ENGINEERING BUSINESS, (INDICATED AS 797 ANDREWS AVE.,
 DELRAY BEACH ON THE FLORIDA STATE DBPR WEBSITE), IS NOT
 SHOWN IN THE TITLE BLOCKS. (SEE ATTACHED SHEET). PLEASE
 INCLUDE THE BUSINESS ADDRESS IN THE TITLE BLOCKS. IF
 THE ADDRESS IS DIFFERENT FROM THE DBPR WEBSITE, PLEASE
 UPDATE THE DBPR WEBSITE PRIOR TO RESUBMITTING FOR
 REVIEW AT THE CITY WPB.
  
 17. SHT P0.3 ABBREIVIATIONS RRW & RRWR ARE NOT
 INDICATED IN THE LIST OF ABBREIVIATIONS ON SHT P0.1.
 PLEASE CLARIFY WHAT THE ABBREIVIATIONS STAND FOR.
 SECTION 106.1.2.
  
 18. SHT P1.1 NOTE: 3" FROM RAIN WATER PIPING. REFER
 ARCHITECTURAL FOR CONT. & DETAILS. PLEASE INDICATE
 WHERE ON THE ARCHITECTURAL SHEETS THIS CAN BE FOUND.
 SECTION 106.1.2.
  
 19. SHT P1.1 KEYED NOTES #12 IS NOT INDICATED ON THE
 FLOOR PLAN. PLEASE INDICATE WHERE #12 CAN BE FOUND.--
 THE SANITARY RISER NEXT TO STAIR #2 IS NOT IDENTIFIED.
 PLEASE IDENTIFY THIS RISER. SECTION 106.1.1.
  
 20. SHT P1.1 FLOOR DRAIN IN THE ELEVATOR MACHINE ROOM.
 SECTION 301.6. PLEASE DELETE FROM FLOOR PLAN & SANITARY
 RISER DIAGRAM.
  
 21. SHT P1.2 VENT FROM EWC BY THE WATER HEATER DOES NOT
 CONNECT TO OR SHOW VTR. PLEASE CLARIFY. SECTIONS
 106.1.1 AND 901.2.1.
  
 22. SHT P5.1 DOMESTIC WATER RISER DIAGRAM FOR RRW &
 RRWR DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE
 RISER AND FLOOR PLAN. SECTION 106.1.1.
  
 23. SHT P5.1 DOMESTIC WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PIPING AT THE BAR SINK, THE
 JANITOR SINK. THE LINE TO THE HOSE BIBB THAT ALSO
 INDICATES A LINE THAT CONNECTS TO THE RRW LINE IS NOT
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 24. SHT P5.1 THE CHECK VALVE SHOWN BETWEEN THE DCW AND
 THE RRW IS NOT APPROVED. AN RPZV BACKFLOW IS REQUIRED
 FOR PROTECTION OF THE POTABLE WATER FROM A POSSIBLE
 CROSS CONNECTION. SECTION 608.13.2.
  
 25. SHT P5.1 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. FUTURE 4" LINE FOR TENANT 2 IS
 SHOWN ON THE 2ND FLOOR OF THE THE RISER DIAGRAM.--
 THE FLOOR DRAIN SHOWN ON THE FLOOR PLAN NEAR ROOM 105
 IS NOT SHOWN ON THE SANT. RISER DIAGRAM.--THE
 CLEANOUT SHOWN ON THE FLOOR PLAN DOWNSTREAM OF THE LAV
 IN THE WOMENS TOILET ROOM 2ND FLOOR IS NOT SHOWN ON THE
 RISER DIAGRAM.--ONLY ONE EWC IS INDICATED. THE EWC
 BY THE RECEPTION AREA IS NOT SHOWN ON THE RISER
 DIAGRAM.--RISER SHOWS AN EXTRA FLOOR DRAIN AND VENT
 UPSTREAM OF THE ONE SHOWN IN THE ELEVATOR MACHINE ROOM,
 (TO BE DELETED PER SECTION 301.6).--NOTE #3 AT THE
 TWO WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER DOES NOT REFLECT KEY NOTE
 #3. PLEASE CHECK THAT THE RISER DIAGRAM. CORRELATES
 WITH THE FLOOR PLAN. SECTION 106.1.1.
  
 26. SHT P5.1 KEY NOTE 11 PAN DRAIN NOT SHOWN. CORRELATE
 NOTE AND RISER DIAGRAM. SECTION 106.1.1.
  
 27. SHT P5.1 KEY NOTE 16. TWO PUMPS ARE SHOWN. PLEASE
 CLARIFY. SUBMIT A DETAIL FOR THE PIPING TO THE PUMPS AT
 THE CISTERN. SECTION 106.1.2.
  
 28. SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL PUMPS.
 SHEETS SHALL SHOW A LISTING AND MANUF. INSTALLATION
 INSTRUCTIONS. SECTION 303.4.
  
 29. DURING A CONVERSATION WITH THE ELECTRICAL PLAN
 REVIEWER, IT WAS BROUGHT TO MY ATTENTION THAT THE HOUSE
 PANEL ON SHT E8.1 ONLY SHOWS ONE BOOSTER PUMP AND ONE
 RECIRCULATION PUMP. TWO OF EACH PUMP ARE SHOWN ON THE
 PLUMBING SHEET P5.1. PLEASE CLARIFY. SECTION 106.1.1.
  
 30. SHT P5.1 KEY NOTES 14 INDICATES A WATER FILTER.
 PLEASE EXPLAIN THE 2 VFD'S TO THE LEFT OF THE FILTER.
 SECTION 106.1.2 MORE INFORMATION REQUIRED.
  
 31. SHT P5.1 KEY NOTE 2 INDICATES A CLEANOUT 36" BELOW
 THE FINISH FLOOR. SECTION 708.4 REQUIRES THAT CLEANOUTS
 SHALL BE EXTENDED THROUGH AND SHALL TERMINATE FLUSH
 WITH THE FINISHED FLOOR. PLEASE CORRECT KEY NOTE.
  
 32. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM. SHOW
 ALL PIPE SIZES AND INDICATE VENTS. SECTION
 106.3.5.1.3(13).
  
 33. THE APPLICATION STATES "DESCRIBE PROJECT IN DETAIL"
 (FAILURE TO DO SO MAY RESULT IN DELAYS). IT APPEARS
 THAT THE SECOND FLOOR WILL BE BUILT OUT,BUT THE FIRST
 FLOOR WILL BE SHELL ONLY WITH THIS PERMIT. THIS IS NOT
 INDICATED ON THE PERMIT APPLICATION, (NEW BUILD).
 PLEASE INDICATE THE SCOPE OF WORK FOR THIS PERMIT AS
 REQUIRED ON THE APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-19 Cont ID  
Sent By lfranco Date 2007-11-19 Time 16:13 Rev Time 0.00
Received By lfranco Date 2007-11-19 Time 16:13 Sent To  
Notes
2007-11-19 16:23:20PLANNING AND ZONING: ****FAILED *****
  
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.THE APPLICATION FOR A FORMAL SITE PLAN REVIEW IN
 THE PLANNING AND ZONING DEPARTMENT WAS DENIED ON
 NOVEMBER 5, 2007 (SEE ATTACHED DENIAL LETTER).
 PURSUANT TO SECTION 94-36(E)(2), WHEN AN APPLICATION IS
 DENIED, ZONING CLEARANCE OR CERTIFICATE OF OCCUPANCY
 SHALL NOT BE ISSUED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By lfranco Date 2007-08-09 Time 17:49 Rev Time 0.00
Received By lfranco Date 2007-08-06 Time 17:17 Sent To  
Notes
2007-08-06 11:03:57PLANNING AND ZONING: ****FAILED *****
  
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.THE PROJECT IS CURRENTLY UNDER A FORMAL SITE PLAN
 REVIEW IN THE PLANNING AND ZONING DEPARTMENT.FINAL
 APPROVAL OF THE PLANS HAS NOT BEEN GIVEN, THEREFORE,
 BUILDING PERMIT CAN NOT BE APPROVED AT THIS TIME.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]