Plan Review Details - Permit 07070312
Plan Review Stops For Permit 07070312
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-26 Cont ID  
Sent By mjacobs Date 2007-09-26 Time 12:53 Rev Time 0.00
Received By mjacobs Date 2007-09-26 Time 12:07 Sent To PC
Notes
2007-09-26 12:07:39PROCESS PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-21 Cont ID  
Sent By mjacobs Date 2007-09-21 Time 16:51 Rev Time 0.00
Received By mjacobs Date 2007-09-21 Time 05:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-06 Cont ID  
Sent By mjacobs Date 2007-09-06 Time 06:06 Rev Time 0.00
Received By mjacobs Date 2007-09-05 Time 17:46 Sent To  
Notes
2007-09-06 06:06:25BUILDING PLAN REVIEW
 PERMIT: 07070312
 ADD: 700 S.ROSEMARY AVE
 CONT: VENTURA ARCH.
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 ***NO RESPONSE***
  
 3)OK
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
 **A FAIR MARKET VALUE SHALL BE STATED OR WE WILL ADJUST
 THE VALUE PER MARSHALL-SWIFT.**
  
 5)OK
  
 6)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING
 A) OK
 B) OK
 C) OK
 D) OK
 E) OK
 F) OK
  
 7)SUBMIT THE LIFE SAFETY PLAN SHOWING THE MEANS OF
 EGRESS.
 **SHOW THE EXIT ACCESS TRAVEL PATH IN THE SERVICE
 CORRIDOR.**
  
 8) OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-25 Cont ID  
Sent By mjacobs Date 2007-07-25 Time 08:34 Rev Time 0.00
Received By mjacobs Date 2007-07-24 Time 09:36 Sent To  
Notes
2007-07-24 12:58:33BUILDING PLAN REVIEW
 PERMIT: 07070312
 ADD: 700 S.ROSEMARY AVE
 CONT: VENTURA ARCH.
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 5)715.3 FIRE DOOR AND SHUTTER ASSEMBLIES. APPROVED
 FIRE DOOR AND FIRE SHUTTER ASSEMBLIES SHALL BE
 CONSTRUCTED OF ANY MATERIAL OR ASSEMBLY OF COMPONENT
 MATERIALS THAT CONFORMS TO THE TEST REQUIREMENTS OF
 SECTION 715.3.1 , 715.3.2 OR 715.3.3 AND THE FIRE
 PROTECTION RATING INDICATED IN TABLE 715.3 . FIRE DOOR
 ASSEMBLIES AND SHUTTERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND NFPA
 80. STATE THE FIRE PROTECTION RATING OF THE DOORS IN
 NEW 2 HOUR FIRE PARTITION INCLUDING THOSE ENCLOSING THE
 EXISTING AV EQUIPMENT ROOM. SEE SHEET A-2 DOOR
 SCHEDULE.
  
 6)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 . -------------------------------------
 ) NUMBER OF FLOORS
  
 7)SUBMIT THE LIFE SAFETY PLAN SHOWING THE MEANS OF
 EGRESS.
  
 8)1005.2 DOOR ENCROACHMENT.
 DOORS OPENING INTO THE PATH OF EGRESS TRAVEL SHALL NOT
 REDUCE THE REQUIRED WIDTH TO LESS THAN ONE-HALF DURING
 THE COURSE OF THE SWING. WHEN FULLY OPEN, THE DOOR
 SHALL NOT PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH.SEE SHEET A-1 DOUBLE DOORS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-20 Cont ID  
Sent By dpalmer Date 2007-09-20 Time 10:46 Rev Time 0.00
Received By dpalmer Date 2007-09-20 Time 10:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 17:06 Sent To  
Notes
2007-09-04 17:07:07 
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #3 AS THE VALUE SHOWN
 IS TO BE BASED ON FAIR MARKET VALUE AND THE TABLES AS
 SET-FORTH IN THE FBC AND ADOPTED REFERENCES TO THE FBC.
 PLEASE ADJUST.
 PLEASE SEE THE APPLIED VALUE FOR THE SCOPE OF WORK
 BEING PERFORMED AND WHAT WILL BE REQUIRED BY THE FBC
 AND REVIEW COMMENTS WILL BE SUBSTANTIALLY HIGHER THAN
 THAT STATED ON PERMIT APPLICATION.
 PLEASE ADJUST THE VALUE FOR ALL OF THE PROPOSED WORK.
 PLEASE SEE FBC ADMIN SECTION 108.3
  
 2) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW.
 PLEASE SEE THE NEW CALCULATIONS ARE NOT SIGNED, DATED
 AND *SEALED* AS REQUIRED PER 13-103.1.1.1.
 PLEASE SEE THE LIGHTING INFORMATION ON THE INPUT DATA
 REPORT DOES NOT MATCH WITH PLANS.
 PLEASE SEE THE NUMBER OF FIXTURES IN THE IDR ONLY
 INDICATES ONE LIGHT FIXTURE. HOW IS THIS POSSIBLE WHEN
 THE PLANS INDICATE SEVERAL?
 PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE SHEET
 A-1 HOWEVER NO ELECTRICAL INFORMATION FOR COMMENT WAS
 ON THIS SHEET AS NOTED.
 PLEASE SEE THE PREVIOUS NOTE BELOW WHICH STILL STANDS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY DESIGNS FOR
 FBC CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THAT EVEN IF NOT CREATING ANY NEW A/C SPACE
 (WHICH IS BEING DONE) PERFORMANCE CALCULATIONS ARE
 STILL REQUIRED.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2 ETC FOR ENERGY
 CALCULATIONS/PERFORMANCE CALCULATIONS.
 PLEASE BE SURE THE FIXTURE LEGEND ON PLANS IS COMPLETE
 WITH ALL INFORMATION FOR FIXTURES/LUMINARIES. PLEASE BE
 SURE ALL THIS INFORMATION FOR FIXTURES ETC COORDINATES
 WITH THE PERFORMANCE CALCULATIONS.
 PLEASE SUBMIT THE TIMES ON DEVICES OR SYSTEM IF SYSTEM
 IS PROPOSED. PLEASE INDICATE MAXIMUM OVER RIDE TIMES.
 PLEASE SEE THAT LOCATIONS ARE REQUIRED TO MEET THE
 ABOVE SECTIONS.
 ** PLEASE SEE AS NO DESIGNS WERE SUBMITTED FOR FBC
 CHAPTER 13, A REVIEW OF THESE ITEMS CAN NOT BE DONE AT
 THIS TIME.
  
  
 3) NOTE: THIS IS THE SAME NOTE FROM PREVIOUS REVIEW.
 PLEASE SEE LOAD CALCULATIONS MUST MEET NEC 220.12,
 220.14, 220.42, 220.44, 220.87 ETC
 PLEASE SEE THAT LOADS MUST INCLUDE THE KNOWN LOADS AND
 NOT AN ESTIMATED AMOUNT BASED ON THE 3VA PER FT. PLEASE
 SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT 125%.
 THE LOAD CALCULATIONS SAYS *CONTINUOUS LOADS* HOWEVER
 THE FIGURES AS SHOWN ARE NOT FIGURED THAT WAY.215.3,
 230.42 ETC.
 FBC 106.3.5.1.2
  
  
 ** PLEASE BE SURE TO SEE POSSIBLE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL PLANS AND IN FACT
 ALL SHEETS IN SETS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By dpalmer Date 2007-07-17 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2007-07-17 Time 17:50 Sent To  
Notes
2007-07-17 18:51:27 
 ** UNSAT **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE REFERENCES ON PLANS WHICH CONTAIN NOTES
 WHICH REFLECT THE SOUTH FLORIDA BUILDING CODE? THIS
 CODE HAS NOT BEEN IN EFFECT SINCE THE ADOPTION OF THE
 2001 FBC.
  
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION IN
 TITLE BLOCKS FOR THE FIRM AS LISTED. PLEASE SEE THAT
 ANY CONSTRUCTION FIRM WHICH ALSO OFFERS ARCHITECTURAL
 SERVICES SHALL OBTAIN A CERTIFICATE OF AUTHORIZATION
 NUMBER FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION.
 PLEASE SEE FAC 61G1-16.004 AND FS 481.219
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE SCOPE OF
 WORK BEING PERFORMED AND WHAT WILL BE REQUIRED BY THE
 FBC AND REVIEW COMMENTS WILL BE SUBSTANTIALLY HIGHER
 THAN THAT STATED ON PERMIT APPLICATION.
 PLEASE ADJUST THE VALUE FOR ALL OF THE PROPOSED WORK.
 PLEASE SEE FBC ADMIN SECTION 108.3
  
 4) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY
 DESIGNS FOR FBC CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THAT EVEN IF NOT CREATING ANY NEW A/C SPACE
 (WHICH IS BEING DONE) PERFORMANCE CALCULATIONS ARE
 STILL REQUIRED.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2 ETC FOR ENERGY
 CALCULATIONS/PERFORMANCE CALCULATIONS.
 PLEASE BE SURE THE FIXTURE LEGEND ON PLANS IS COMPLETE
 WITH ALL INFORMATION FOR FIXTURES/LUMINARIES. PLEASE BE
 SURE ALL THIS INFORMATION FOR FIXTURES ETC COORDINATES
 WITH THE PERFORMANCE CALCULATIONS.
 PLEASE SUBMIT THE TIMES ON DEVICES OR SYSTEM IF SYSTEM
 IS PROPOSED. PLEASE INDICATE MAXIMUM OVER RIDE TIMES.
 PLEASE SEE THAT LOCATIONS ARE REQUIRED TO MEET THE
 ABOVE SECTIONS.
 ** PLEASE SEE AS NO DESIGNS WERE SUBMITTED FOR FBC
 CHAPTER 13, A REVIEW OF THESE ITEMS CAN NOT BE DONE AT
 THIS TIME.
  
 5) NOTE: PLEASE SEE THE SPACES WHICH CONTAIN AV
 EQUIPMENT ARE NOT LOCATED IN A RATED CORRIDOR WITH OUT
 ANY INFORMATION FOR SEPARATION. PLEASE SEE LOCATIONS OF
 ELECTRICAL EQUIPMENT AS SHOWN IS NOT PERMITTED IN RATED
 EGRESS AREAS. PLEASE SEE BUILDING REVIEW COMMENTS FOR
 THIS. PLEASE SEE CHAPTER 10 OF THE FBC.
 PLEASE SEE PLANS WERE REDLINED UNDER 06080951 OF
 EQUIPMENT WHICH IS NOT PERMITTED IN RATED STAIRS OR
 HALLS.
  
 6) NOTE: PLEASE PROVIDE INFORMATION FOR ELECTRICAL WORK
 AND AREAS FOR THE AV PANEL AND EQUIPMENT WHICH IS BEING
 SHOWN ON PLANS AS EXISTING. THE PLANS DATED BACK FOR
 SECURITY WORK WHICH WAS PERMIT #06080951 DID NOT
 INCLUDE THE ELECTRICAL PANEL AND OTHER EQUIPMENT AS
 SHOWN ON THESE PLANS.
 PLEASE PROVIDE DOCUMENTATION FOR THIS WORK AS NOT
 RECORD COULD BE LOCATED FOR THIS FOR SUITE #200 BASED
 ON THIS ADDRESS OF 700 S. ROSEMARY.
 PLEASE SUBMIT INFORMATION FOR THIS *EXISTING* AV
 PANEL.
  
 7) NOTE: PLEASESEE LOAD CALCULATIONS MUST MEET NEC
 220.12, 220.14, 220.42, 220.44,220.87 ETC
 PLEASE SEE THAT LOADS MUST INCLUDE THE KNOWN LOADS AND
 NOT AN ESTIMATED AMOUNT BASED ON THE 3VA PER FT. PLEASE
 SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT 125%.
 THE LOAD CALCULATIONS SAYS *CONTINUOUS LOADS* HOWEVER
 THE FIGURES AS SHOWN ARE NOT FIGURED THAT WAY.215.3,
 230.42 ETC.
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE 408.4 AS THE ROOMS AND AREAS ON
 PLANS SHALL CONTAIN DESIGNATIONS AND THESE DESIGNATIONS
 NEED TO CORRELATE WITH THE PANEL SCHEDULE. THE USE OF
 *LIGHTING* OR *RECEPTACLES* IS NOT ACCEPTABLE. PLEASE
 KNOW NUMERICAL DESIGNATIONS ARE PERMITTED. PLEASE SEE
 THE FOLLOWING TEXT WHICH IS TAKEN FROM THE 2005 NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS.PLEASE SHOW LOCATIONS AS REQUIRED
 AND LEVELS AS REQUIRED. THIS BUILDING DOES CONTAIN A FA
 SYSTEM.
 ** PLEASE KNOW THAT EVEN THOUGH THE FIRE ALARM WILL BE
 UNDER A SEPARATE PERMIT THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS TO COMPLY WITH THE FBC AND FS
 633.
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** PLEASE BE SURE TO SEE POSSIBLE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL PLANS AND IN FACT
 ALL SHEETS IN SETS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 12:09 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 11:58 Sent To B1
Notes
2007-09-25 12:09:36*****APPROVED*****
  
  
 THE COMMENT FROM THE PREVIOUS PLAN REVIEW HAS BEEN
 ADDRESSED;PLAN SHEETS A-5 AND E-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-06 Cont ID  
Sent By mawillia Date 2007-09-06 Time 14:19 Rev Time 0.00
Received By mawillia Date 2007-09-06 Time 13:38 Sent To  
Notes
2007-09-06 14:19:43*****UNSAT*****
  
  
 6.PLEASE SPECIFY THE NEW WALL AND CEILING FINISH
 MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND
 OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C.
 SHEET A-2 REMARKS DOOR RATING 90 MIN. CLASS "C" , WHAT
 ABOUT THE OTHER AREAS STATED IN THE COMMENT?
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-25 Cont ID  
Sent By mawillia Date 2007-07-25 Time 17:44 Rev Time 0.00
Received By mawillia Date 2007-07-25 Time 17:01 Sent To  
Notes
2007-07-25 17:17:30*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, TO
 BE REFERENCED.
  
 2.LIST THE OCCUPANCY TYPE AND OCCUPANT LOAD FOR THIS
 SPACE.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.THE SCOPE OF WORK IN NO WAY SHALL BLOCK, INTERFERE
 OR HINDER ACCESS TO OR EGRESS FROM THE SAID BUILDING
 FLOOR/SUITE OR OTHER FLOORS/SUITES IN THE BUILDING
 (INCLUDING EXITS, EXIT AISLE CORRIDORS).
  
 6.PLEASE SPECIFY THE NEW WALL AND CEILING FINISH
 MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND
 OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7.ON SHEET E-2, THERE IS AN EXIT LIGHT (OF WHICH I'VE
 CIRCLED IN RED) NOTED.WHERE DOES THIS EXIT LEAD
 PERSON(S) ?
  
 8.WILL THE SCOPE OF WORK IMPACT THE FIRE SPRINKLERS?
 IF SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR
 THE SPRINKLER REMODEL.
  
 9.WILL THE SCOPE OF WORK IMPACT THE FIRE ALARM
 DEVICES?IF SO, SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FOR THE FIRE ALARM REMODEL.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 15:49 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 15:49 Sent To  
Notes
2007-09-19 17:06:13TO "BOB"#4--EXPEDITED--
2007-09-18 15:50:08WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 14:30 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 14:30 Sent To  
Notes
2007-09-04 14:33:47TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-25 Cont ID  
Sent By mawillia Date 2007-07-25 Time 17:01 Rev Time 0.00
Received By mawillia Date 2007-07-13 Time 14:39 Sent To  
Notes
2007-07-17 14:28:13TO "BOB"#10
2007-07-13 14:39:46WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-24 Cont ID  
Sent By tgordon Date 2007-09-24 Time 13:58 Rev Time 0.25
Received By tgordon Date 2007-09-24 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-06 Cont ID  
Sent By tgordon Date 2007-09-06 Time 12:03 Rev Time 0.30
Received By tgordon Date 2007-09-06 Time 12:03 Sent To  
Notes
2007-09-06 12:22:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) PLANS PAGE M-1 IS TO DIFFICULT TO READ AS IT HAS THE
 FLOOR PLAN WITH FURNITURE LAY-OUT, OVER CEILING PLAN,
 OVER DUCT LAY-OUT. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1.
  
 2) PAGE M-1 ROOM 215-C SHOWS SOMETHING ABOUT EF-13 (ON
 ROOF), BUT UNABLE TO DO A CORRECT REVIEW AT THIS TIME.
 PLEASE CLEAN UP MECHANICAL PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
 .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By tgordon Date 2007-07-19 Time 11:46 Rev Time 0.30
Received By tgordon Date 2007-07-19 Time 11:46 Sent To  
Notes
2007-07-19 13:54:58*** DENIED ***
 1) AS ROOM SIZES HAVE CHANGED THE REQUIRED CFM'S OF
 SUPPLY AIR MAY HAVE CHANGED, PLEASE SHOW THE CFM'S AT
 ALL SUPPLY AIR GRILLS TO ROOMS THAT HAVE BEEN ALTERED.
  
 2) NOTE #1 ON MECHANICAL PLAN STATES RELOCATE
 DIFFUSERS, WERE PLAN SHOWS #1 AS RELOCATED GRILL. AND
 NOTE #4 STATES EXTEND FLEX, WERE PLAN SHOWS NEW FLEX.
 PLEASE CORRECT MECHANICAL PLAN SO EXACT WORK TO BE DONE
 IS CLEAR.
  
 3) MECHANICAL PLAN SHOWS AN EXISTING RETURN DUCT NEXT
 TO IT IS A RELOCATED FIRE DAMPER. IS THE RETURN DUCT TO
 BE RELOCATED TO THE FIRE DAMPER OR IS THE FIRE DAMPER
 FOR SOMETHING ELSE. PLEASE CLARIFY.
  
 4) PLEASE ADD TO MECHANICAL PLAN A DETAIL SHOWING THE
 INSTALLATION OF THE FIRE DAMPER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-25 Cont ID  
Sent By choops Date 2007-07-25 Time 09:26 Rev Time 0.00
Received By choops Date 2007-07-25 Time 09:26 Sent To  
Notes
2007-07-25 09:26:37CITY PLACE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved