Plan Review Details - Permit 07070279
Plan Review Stops For Permit 07070279
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-30 Cont ID  
Sent By rmcdouga Date 2007-10-30 Time 07:37 Rev Time 0.00
Received By rmcdouga Date 2007-10-30 Time 07:12 Sent To  
Notes
2007-10-30 07:36:56BUILDING PROVISO
  
 THE GARAGE DOOR LOCATED WITHIN 10 FEET OF THE GENERATOR
 IS REQUIRED TO BE ENCLOSED WITH GLASS BLOCK PER PERMIT
 # 07100033.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-30 Cont ID  
Sent By rmcdouga Date 2007-08-30 Time 18:53 Rev Time 0.00
Received By rmcdouga Date 2007-08-30 Time 18:53 Sent To  
Notes
2007-08-30 19:09:022004 FBC
 INSTALL RESIDENTIAL GENERATOR
 2ND REVIEW
  
 DENIED BY BUILDING
  
  
  
 1)GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BE USED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 PLANS MUST SHOW THAT THE GENERATOR IS ADEQUATELY
 ANCHORED TO RESIST OVERTURNING, UPLIFT AND SLIDING AS
 REQUIRED BY FBC 1609.1.3.
  
  
 2) A SEPARATE PERMIT IS REQURED TO INSTALL THE GLASS
 BLOCK AND THE WORK WILL HAVE TO BE COMPLETED AND
 APPROVED BY THE CITY BUILDING DEPARTMENT BEFORE THE
 GENERATOR PERMIT CAN BE ISSUED.
  
 3) ADDRESS REVIEW COMMENTS OF OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-01 Cont ID  
Sent By rmcdouga Date 2007-08-01 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2007-08-01 Time 07:43 Sent To M
Notes
2007-08-01 08:53:59DENIED BY BUILDING
  
 1)GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) PROVIDE PLANS ENOUGH TO VERIFY LOCATION
 OF GENERATOR VERSES BUILDING OPENINGS
 WINDOWS, DOORS OR SOFFIT TYPE VENTS,
 ETC.
 - PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-29 Cont ID  
Sent By btrobaug Date 2007-10-26 Time 07:15 Rev Time 0.00
Received By btrobaug Date 2007-10-26 Time 06:49 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By btrobaug Date 2007-08-29 Time 10:01 Rev Time 0.00
Received By btrobaug Date 2007-08-29 Time 09:42 Sent To M
Notes
2007-08-29 10:01:53 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 SAME COMMENT AS PREVIOUS REVIEW, RESPOND IN WRITING AS
 I CANNOT FIND THE REQUIRED INFORMATION IN THE PACKAGE.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS FOR THE GENERATOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By btrobaug Date 2007-07-16 Time 09:20 Rev Time 0.00
Received By btrobaug Date 2007-07-16 Time 08:30 Sent To M
Notes
2007-07-16 09:20:52 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 NOTE: ALL PERMIT APPLICATIONS MUST BE SUBMITTED
 TOGETHER TO EXPEDITE THE REVIEW PROCESS.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS FOR THE GENERATOR.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2007-10-30 Cont ID  
Sent By tgordon Date 2007-10-30 Time 07:57 Rev Time 0.15
Received By tgordon Date 2007-10-30 Time 07:57 Sent To B
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2007-08-01 Cont ID  
Sent By tgordon Date 2007-08-01 Time 09:18 Rev Time 0.20
Received By tgordon Date 2007-08-01 Time 09:18 Sent To  
Notes
2007-08-01 09:18:56SEE MECHANICAL REVIEW.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-07-30 Cont ID  
Sent By mperson Date 2007-07-30 Time 14:35 Rev Time 0.00
Received By mperson Date 2007-07-30 Time 14:35 Sent To B
Notes
2007-07-30 14:37:36NOTE: GENERATOR IS DIESEL FUEL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-22 Cont ID  
Sent By adarroug Date 2007-10-22 Time 13:19 Rev Time 0.00
Received By adarroug Date 2007-10-22 Time 13:19 Sent To Z
Notes
2007-10-22 13:19:17TO "Z" BOX/RESUB--NEW SHEETS FOR "Z"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 16:56 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 16:56 Sent To E
Notes
2007-08-23 16:56:50TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-01 Cont ID  
Sent By rmcdouga Date 2007-08-01 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2007-07-11 Time 14:08 Sent To  
Notes
2007-07-11 14:08:50TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-29 Cont ID  
Sent By btrobaug Date 2007-10-29 Time 16:24 Rev Time 0.25
Received By tgordon Date 2007-10-29 Time 12:04 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-30 Cont ID  
Sent By tgordon Date 2007-08-30 Time 09:02 Rev Time 0.35
Received By tgordon Date 2007-08-30 Time 09:02 Sent To B
Notes
2007-08-30 09:53:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 7-20-07. PLEASE SUBMIT
 COMPLETE DETAILED MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND SPECIFICATIONS FOR DIESEL GENERATOR
 AND FUEL TANK (MUST SHOW FUEL TANK CAPACITY).
  
 2) PLAN SHOWS THE GENERATOR NEXT TO A DOOR, SEE NFPA
 37. A PERMIT WILL BE REQUIRED AND THE DOOR WILL NEED TO
 BE CLOSED OFF BEFORE THE GENERATOR PERMIT CAN BE
 ISSUED.
  
 3)INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 (PRINTED NAME OF PERSON SEALING PLANS) SEE FAC
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4) THE WORKERS COMP. EXEMPT CARD SUBMITTED FOR KARL
 SCHIBINGER, EXEMPTION IS FOR SALES ONLY THE PERMIT
 APPLICATION IS FOR THE INSTALLATION OF A GENERATOR,
 PLEASE CORRECT.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By tgordon Date 2007-07-17 Time 09:46 Rev Time 0.20
Received By tgordon Date 2007-07-17 Time 09:46 Sent To P
Notes
2007-07-17 09:50:29*** DENIED ***
 1) PLEASE SUBMIT COMPLETE DETAILED MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AND SPECIFICATIONS FOR DIESEL
 GENERATOR AND FUEL TANK.
  
 2) PLAN SHOWS THE GENERATOR NEXT TO A GARAGE DOOR, SEE
 NFPA 37, PLEASE CORRECT.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-07-30 Cont ID  
Sent By mperson Date 2007-07-30 Time 14:40 Rev Time 0.00
Received By mperson Date 2007-07-30 Time 14:40 Sent To G
Notes
2007-07-30 14:41:34NOTE: GENERATOR IS DIESEL FUEL.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-25 Cont ID  
Sent By choops Date 2007-10-25 Time 11:02 Rev Time 0.00
Received By choops Date 2007-10-25 Time 11:02 Sent To E
Notes
2007-10-25 11:02:59***APPROVED - RESUB #2***
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status P Date 2007-07-12 Cont ID  
Sent By choops Date 2007-07-12 Time 13:16 Rev Time 0.00
Received By choops Date 2007-07-12 Time 13:16 Sent To E
Notes
***NONE***