| 2007-08-16 21:50:30 | BUILDING PLAN REVIEW |
| | PERMIT: 07070268 |
| | ADD: 5800 CORPORATE WAY |
| | CONT: LTL BUILDERS, INC. |
| | TEL: (561)628-9753 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) THE PLANS SUBMITTED FROM THE PALM BEACH COUNTY |
| | SCHOOL BOARD FOR A PORTABLE DO NOT APPEAR TO HAVE |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS APPROVAL SINCE |
| | THERE IS NO DCA APPROVAL NUMBERS PRESENT. A LETTER FROM |
| | THOMAS HOGARTH P.E. ALSO ADDS DOUBT THAT THIS UNIT WAS |
| | DESIGNED UNDER THE DCA'S MANUFACTURED BUILDING ACT. IF |
| | SO PLEASE SEE PAGES PULLED OFF THE DCA WEBSITE WITH |
| | INFORMATION AS HOW TO GO ABOUT RETRIEVING OLD PLANS |
| | THAT HAD BEEN DESIGNED UNDER THE STANDARD BUILDING |
| | CODE. NOTE QUESTION# 4 AS HOW DO I KNOW IF A |
| | MANUFACTURED (MODULAR) BUILDING IS DCA APPROVED. |
| | |
| | 4) SEE QUESTION # 6 HOW DOES A SCHOOL OBTAIN A DCA |
| | INSIGNIA FOR AN EXISTING PORTABLE CLASSROOM. THIS IS |
| | COMMENTS THAT DEALS WITH PORTABLES STILL OWNED BY THE |
| | SCHOOL BOARD. |
| | |
| | 5) THE ISSUES ARE THIS BUILDING WILL NOW BE A PERMANENT |
| | BUILDING AND WOULD NOT BE CLASSIFIED AS A TEMPORARY |
| | STRUCTURE TO BE USED LESS THAN 180 DAYS. THIS WOULD |
| | MEAN A PERMANENT FOUNDATION MEETING THE REQUIREMENTS OF |
| | THE BOTTOM OF THE FOUNDATION TO BE 12" BELOW GRADE. |
| | 1805.2 DEPTH OF FOOTINGS. THE MINIMUM DEPTH OF FOOTINGS |
| | BELOW THE UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES |
| | (305 MM). WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL |
| | ALSO CONFORM TO SECTIONS 1805.2.1 THROUGH 1805.2.3 . |
| | EXISTING BUILDING CODE 1102.2 THE FOUNDATION SYSTEM OF |
| | RELOCATED BUILDINGS SHALL COMPLY WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 6) IF THE BUILDING WAS NOT MANUFACTURED UNDER THE STATE |
| | DCA PROGRAM THEN THE BUILDING BEING MOVED WILL NEED TO |
| | MEET THE REQUIREMENTS OFTHE 2004 EXISTING BUILDING |
| | CODE CHAPTER 11. |
| | |
| | 6A) EXISTING BUILDING CODE 1102.1 LOCATION ON THE LOT. |
| | THE BUILDING SHALL BE LOCATED ON THE LOT IN ACCORDANCE |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | BUILDING. PLEASE PROVIDE A SITE PLAN WITH THE LOCATION |
| | OF THIS NEW BUILDING ANDTHE EXISTING BUILDING BEING |
| | USED FOR A SCHOOL. PLEASE PROVIDE THE DISTANCE BETWEEN |
| | BUILDINGS. |
| | |
| | 6B)PLEASE LOOK AT MULTIPLE BUILDINGS ON SAME LOT. |
| | 503.1.3 BUILDINGS ON SAME LOT. |
| | TWO OR MORE BUILDINGS ON THE SAME LOT SHALL BE |
| | REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED |
| | AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF EACH |
| | BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE WITHIN |
| | THE LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS |
| | 504 AND 506 . THE PROVISIONS OF THIS CODE APPLICABLE TO |
| | THE AGGREGATE BUILDING SHALL BE APPLICABLE TO EACH |
| | BUILDING. |
| | PLEASE INDICATE IF THE TWO BUILDINGS ON THE SAME LOT |
| | WILL BE CLASSIFIED AS ONE LARGER BUILDING WITH NO FIRE |
| | SEPARATION BETWEEN THEM OR TWO |
| | SEPARATE BUILDINGS WITH FIRE SEPARATION BETWEEN THE 2 |
| | BUILDINGS. |
| | |
| | 6C)) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FORRECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | 6C)(A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT |
| | IS DESIGNED. |
| | 6C)(B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | 6C)(C) THE TYPE OF CONSTRUCTION AS DEFINED IN |
| | CHAPTER 6, TABLE 601. |
| | 6C)(D) THE OCCUPANT LOAD, SEE 1004. |
| | 6C)(E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED |
| | 6C)(F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. 6C)(G) |
| | ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT |
| | 6C)(.H) SQ. FT. FOOTPRINT |
| | 6C)(I) FLOOD ZONE DESIGNATIONA-8 MINIMUM ELEVATION |
| | FINISH FLOOR AND A/C EQUIPMENT 14'-6". 2004 FL. BLD |
| | CODE 1603.1.4 THE |
| | 6C)(J) THE FOLLOWING INFORMATION RELATED TO WIND SHALL |
| | BE SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN WIND |
| | PRESSURES IN TERMS OF PSF. |
| | 6C)(K) OPENING PROTECTIVE'S:1609.1.4 PROTECTION |
| | OF OPENINGS. IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE |
| | BALANCE OF GLAZED OPENINGS IN THE REST OF |
| | THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS |
| | SUCH GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT |
| | RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS OF |
| | SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE TAS |
| | 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE |
| | MISSILE TEST. 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | 6D)ON THE SITE PLAN PLEASE INDICATE THE ACCESSIBLE |
| | ROUTE:11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS. THIS |
| | EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS, |
| | STRUCTURES OR FACILITIES WHICH WERE IN EXISTENCE ON |
| | OCTOBER 1,1997, UNLESS: |
| | (I) THE BUILDING, STRUCTURE OR FACILITY IS BEING |
| | CONVERTED FROM RESIDENTIAL TO NONRESIDENTIAL OR MIXED |
| | USE, AS DEFINED BY LOCAL LAW. |
| | (II) THE PROPOSED ALTERATION OR RENOVATION OF THE |
| | BUILDING, STRUCTURE OR FACILITY WILL AFFECT USABILITY |
| | OR ACCESSIBILITY TO A DEGREE WHICH INVOKES THE |
| | REQUIREMENTS OF SECTION 303(A) OF THE ADA OF 1990, OR |
| | (III) THE ORIGINAL CONSTRUCTION OR ANY FORMER |
| | ALTERATION OR RENOVATION OF THE BUILDING, STRUCTURE OR |
| | FACILITY WAS CARRIED OUT IN VIOLATION OF APPLICABLE |
| | PERMITTING LAW: |
| | (1) GENERAL. ALTERATIONS TO EXISTING BUILDINGS AND |
| | FACILITIES SHALL COMPLY WITH THE FOLLOWING: |
| | (A)NO ALTERATION SHALL BE UNDERTAKEN WHICH |
| | DECREASES OR HAS THE EFFECT OF DECREASING ACCESSIBILITY |
| | OR USABILITY OF A BUILDING OR FACILITY BELOW THE |
| | REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF |
| | ALTERATION. |
| | (B)IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS |
| | ARE ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE, |
| | FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE |
| | PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3 , |
| | MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE |
| | APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT |
| | AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE |
| | ROUTE , THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS |
| | NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS |
| | PROVIDED IN SECTION 11-4.1.6 (2), ALTERATIONS TO AN |
| | AREA CONTAINING A PRIMARY FUNCTION |
| | |
| | 7) PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW |
| | CONSTRUCTION WITH BASE FLOOD ELEVATION, CITY CODE |
| | REQUIRES |
| | AN ADDITIONAL 6". OR 14'-6". |
| | |
| | 8) 1102.2 THE CONNECTION OF THE RELOCATED BUILDING TO |
| | THE FOUNDATION SHALL COMPLY WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 9) 1102.3 WIND LOADS, BUILDINGS SHALL COMPLY WITH THE |
| | FLORIDA BUILDING CODE, BUILDING |
| | EXCEPTIONS; |
| | 1) STRUCTURAL ELEMENTS WHOSE STRESS IS NOT INCREASED BY |
| | MORE THAN 5 PER CENT. |
| | 2) MANUFACTURED BUILDINGS AS APPROVED BY THE |
| | MANUFACTURED BUILDING PROGRAM, FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS. |
| | |
| | 10)PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 11)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |