Plan Review Details - Permit 07070249
Plan Review Stops For Permit 07070249
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-19 Cont ID  
Sent By mawillia Date 2007-12-19 Time 12:06 Rev Time 0.00
Received By mawillia Date 2007-12-19 Time 11:49 Sent To  
Notes
2007-12-19 12:04:03*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET FP-2.0 STAMPED, INITIALED AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-21 Cont ID  
Sent By mwennerg Date 2007-09-21 Time 13:45 Rev Time 0.00
Received By mwennerg Date 2007-09-21 Time 13:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-25 Cont ID  
Sent By mwennerg Date 2007-07-25 Time 13:13 Rev Time 0.00
Received By mwennerg Date 2007-07-25 Time 13:13 Sent To  
Notes
2007-07-25 13:21:20***DENIED***
  
 1) THE MINIMUM SAFETY MARGIN SHALL BE NOT LESS THAN 5.0
 PSI IN ACCORDANCE WITH LOCAL REQUIREMENTS. PLEASE
 PROVIDE THIS INFORMATION WITH THE HYDRAULIC ANALYSIS.
  
 2) A DOUBLE DETECTOR CHECK ASSEMBLY WAS NOT SHOWN ON
 PLANS. PLEASE PROVIDE A DETAIL SHOWING ASSEMBLY OR
 ILLUSTRATE HOW BACKFLOW REQUIREMENTS WILL BE MET.
  
 3) CENTRAL STATION MONITORING IS REQUIRED. NEW SYSTEMS
 SUPERVISING AUTOMATIC SPRINKLER PROTECTION TO BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 14:06 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 14:06 Sent To FIRE
Notes
2007-08-24 14:06:43TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-25 Cont ID  
Sent By mwennerg Date 2007-07-25 Time 13:21 Rev Time 0.00
Received By mwennerg Date 2007-07-12 Time 09:41 Sent To  
Notes
2007-07-12 09:41:59TO "F" BOX