Plan Review Details - Permit 07070240
Plan Review Stops For Permit 07070240
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-08-22 Cont ID  
Sent By shill Date 2007-08-22 Time 07:57 Rev Time 0.00
Received By shill Date 2007-08-22 Time 07:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-05 Cont ID  
Sent By btrobaug Date 2007-09-05 Time 17:41 Rev Time 0.00
Received By btrobaug Date 2007-09-05 Time 17:11 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By btrobaug Date 2007-07-16 Time 10:50 Rev Time 0.00
Received By btrobaug Date 2007-07-16 Time 10:28 Sent To M
Notes
2007-07-16 10:50:18 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR
 INDICATING RECOMMENDED SETBACKS FROM STRUCTURES.
  
 2} } PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-10-01 Cont ID  
Sent By mperson Date 2007-10-01 Time 11:22 Rev Time 0.00
Received By mperson Date 2007-10-01 Time 11:22 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-09-11 Cont ID  
Sent By mperson Date 2007-09-11 Time 14:05 Rev Time 0.00
Received By mperson Date 2007-09-11 Time 14:05 Sent To M
Notes
2007-09-11 14:14:05DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS WITH 2006 REVISIONS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO**PLEASE SUBMIT (TWO COPIES) OF
 MANUFACTURER"S SPECIFICATIONS VERIFYING THE BTU LOAD OF
 THE PROPOSED GENERATOR AND THAT THE GENERATOR IS LISTED
 BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 2. **OK**
  
 3. **OK**
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-30 Cont ID  
Sent By mperson Date 2007-07-30 Time 14:10 Rev Time 0.45
Received By mperson Date 2007-07-30 Time 14:10 Sent To B
Notes
2007-07-30 14:23:00DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE SUBMIT (TWO COPIES) MANUFACTURER'S
 SPECIFICATIONS VERIFYING THE BTU LOAD OF THE PROPOSED
 GENERATOR AND THAT THE GENERATOR IS LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 2. PLEASE SUBMIT MANFACTURER'S INSTALLATION
 INSTRUCTIONS INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 3. PLEASE INDICATE ON THE RESUBMITTED SURVEY THE
 DIMENSIONS OF THE PROPOSED GENERATOR TO PROPERTY LINES
 AND ADJACENT STRUCTURES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 12:34 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 12:34 Sent To G
Notes
2007-09-18 12:34:18TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 09:40 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 09:40 Sent To Z
Notes
2007-08-24 09:41:24TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-24 Cont ID  
Sent By btrobaug Date 2007-08-22 Time 09:35 Rev Time  
Received By adarroug Date 2007-07-12 Time 09:49 Sent To Z
Notes
2007-07-16 10:49:09 
2007-07-12 09:49:53TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-12 Cont ID  
Sent By tgordon Date 2007-09-12 Time 09:09 Rev Time 0.20
Received By tgordon Date 2007-09-12 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By btrobaug Date 2007-07-17 Time 09:25 Rev Time 0.20
Received By tgordon Date 2007-07-17 Time 09:25 Sent To G
Notes
2007-07-17 09:30:35*** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 GENERATOR.
 *** ADVISORY ***
 1 PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By choops Date 2007-08-28 Time 14:09 Rev Time 0.00
Received By choops Date 2007-08-28 Time 14:09 Sent To E
Notes
2007-08-28 14:10:38***APPROVED**** ***RESUB #1***
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-08-24 Time 09:35 Rev Time 0.00
Received By choops Date 2007-07-12 Time 16:08 Sent To E
Notes
2007-07-12 16:09:43***FAILED***
  
  
 1)INDICATE ON SURVEYS THE SETBACK DIMENSIONS FROM
 THE PROPOSED GENERATOR TO THE FRONT AND SIDE PROPERTY
 LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720