Plan Review Details - Permit 07070210
Plan Review Stops For Permit 07070210
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-27 Cont ID `
Sent By shill Date 2007-08-27 Time 18:07 Rev Time 0.00
Received By shill Date 2007-08-27 Time 18:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-22 Cont ID  
Sent By shill Date 2007-08-22 Time 14:01 Rev Time 0.00
Received By shill Date 2007-08-22 Time 14:01 Sent To  
Notes
2007-08-22 14:07:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.NOTE THAT THE ANCHOR SPACING ON PAGE 2
 WAS BLANK.ALSO, THE SHUTTER CONNECTION MOUNTING TYPE
 SHOULD CORRELATE WITH THE DETAIL MARKERS ON THE ANCHOR
 SCHEDULE; IN THIS CASE, A THROUGH L.IT APPEARS THAT
 YOU ARE USING A (12).
  
 2ND REVIEW - YOU ARE SPECIFYING A 3" EDGE DISTANCE.
 YOU HAVE WRITTEN "HV 12" ON THE INSTALLATION SCHEDULE.
 THE ANCHOR SCHEDULE ON THE PRODUCT APPROVAL USES A
 THROUGH L FOR SHUTTER CONNECTION MOUNTING TYPES.YOU
 HAVE CIRCLED BOTH A AND H ON THE PRODUCT APPROVAL.3"
 EDGE DISTANCE REQUIRES A FACTOR OF .83, SEE SHEET 14 OF
 THE PRODUCT APPROVAL.TAPCON, 8' SPAN, 3" EDGE
 DISTANCE, CONNECTION H REQUIRES 8.5 X .83 SPACING, YOUR
 INSTALLATION SCHEDULE STATES 8".
  
 PLEASE REVISE INSTALLATION SCHEDULE.
  
 3RD REVIEW - THE ANCHOR SPACING WAS REVISED BUT THE
 SHUTTER CONNECTION MOUNTING TYPE STILL STATES "HV12".
 THIS SHOULD CORRELATE WITH THE ANCHOR SCHEDULE, A
 THROUGH L.YOU'VE CIRCLED INFORMATION ON THE CHART FOR
 A AND H, ARE THESE THE CONNECTION TYPES YOU ARE USING?
 PLEASE INCLUDE THIS INFORMATION AS REQUESTED.REVISE
 INSTALLATION SCHEDULE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-15 Cont ID  
Sent By shill Date 2007-08-15 Time 07:48 Rev Time 0.00
Received By shill Date 2007-08-15 Time 07:48 Sent To  
Notes
2007-08-15 07:52:19****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.NOTE THAT THE ANCHOR SPACING ON PAGE 2
 WAS BLANK.ALSO, THE SHUTTER CONNECTION MOUNTING TYPE
 SHOULD CORRELATE WITH THE DETAIL MARKERS ON THE ANCHOR
 SCHEDULE; IN THIS CASE, A THROUGH L.IT APPEARS THAT
 YOU ARE USING A (12).
  
 YOU ARE SPECIFYING A 3" EDGE DISTANCE.YOU HAVE
 WRITTEN "HV 12" ON THE INSTALLATION SCHEDULE.THE
 ANCHOR SCHEDULE ON THE PRODUCT APPROVAL USES A THROUGH
 L FOR SHUTTER CONNECTION MOUNTING TYPES.YOU HAVE
 CIRCLED BOTH A AND H ON THE PRODUCT APPROVAL.3" EDGE
 DISTANCE REQUIRES A FACTOR OF .83, SEE SHEET 14 OF THE
 PRODUCT APPROVAL.TAPCON, 8' SPAN, 3" EDGE DISTANCE,
 CONNECTION H REQUIRES 8.5 X .83 SPACING, YOUR
 INSTALLATION SCHEDULE STATES 8".
  
 PLEASE REVISE INSTALLATION SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-01 Cont ID  
Sent By shill Date 2007-08-01 Time 15:50 Rev Time 0.00
Received By shill Date 2007-08-01 Time 15:50 Sent To  
Notes
2007-08-01 15:52:10****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.NOTE THAT THE ANCHOR SPACING ON PAGE 2
 WAS BLANK.ALSO, THE SHUTTER CONNECTION MOUNTING TYPE
 SHOULD CORRELATE WITH THE DETAIL MARKERS ON THE ANCHOR
 SCHEDULE; IN THIS CASE, A THROUGH L.IT APPEARS THAT
 YOU ARE USING A (12).
  
 ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 _XX_5.TWO COMPLETE COLLATED SETS OF DOCUMENTS
 REQUIRED FOR PERMITTING.ONLY ONE INSTALLATION
 SCHEDULE WAS SUBMITTED.
  
 ____6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 _XX_8.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.(DESIGN PRESSURE OF -40 IS TOO LOW FOR
 EXPOSURE C.)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 10:06 Sent To B
Notes
2007-08-16 10:07:19TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-07 Cont ID  
Sent By mmiller Date 2007-08-07 Time 17:53 Rev Time 0.00
Received By mmiller Date 2007-08-07 Time 17:52 Sent To B
Notes
2007-08-07 17:53:09SENT TO SAMANTHA HILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-01 Cont ID  
Sent By shill Date 2007-08-01 Time 15:52 Rev Time 0.00
Received By shill Date 2007-07-10 Time 10:11 Sent To  
Notes
2007-07-10 10:11:41TO "MISC" BOX#1