Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-13 Cont ID  
Sent By rmcdouga Date 2007-11-13 Time 17:19 Rev Time 0.00
Received By rmcdouga Date 2007-11-13 Time 16:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By rmcdouga Date 2007-08-28 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2007-08-27 Time 18:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-25 Cont ID  
Sent By rmcdouga Date 2007-07-25 Time 17:12 Rev Time 0.00
Received By rmcdouga Date 2007-07-25 Time 17:12 Sent To P
Notes
2007-07-25 17:57:23DENIED BY BUILDING
  
 1)SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE REQUIRES ROOF SHEATHING TO BE FASTENED
 WITH 8D RING SHANK NAILS IN ALL ROOF ZONES. FASTENER
 SPACING IS REQUIRED TO BE 4" OC IN ROOF ZONE 3. PLEASE
 REVISE THE NOTES ON SHEET 2.
  
 2) SAFETY GLAZING IS REQUIRED IN THE MASTER BATHROOM
 WINDOW. PLEASE CLARIFY THAT T. G. IS AN ABBREVIATION
 FOR TEMPERED GLASS. THE ABBREVEATION TEMP. IS TYPICALLY
 USED TO DENOTE TEMPERED GLASS.
  
 3) THE ENERGY CALULATION FORM THAT WAS SUBMITTED HAS
 BEEN REVISED BY THE 2006 REVISIONS TO THE 2004 FBC. THE
 CURRENT FORM IS 600C-04R WHICH IS TWO SIDED. I HAVE
 ATTACHED A COPY OF IT TO THE OLD FORMS. THE OWNER/AGENT
 IS REQUIRED TO SIGN THE FORM. THE OVERHANG OF 2'
 SPECIFIED ON THE FORM DOES NOT CONCUR WITH THE OVERHANG
 OF 1'-6"SPECIFIED ON THE WALL SECTION ON SHEET 2 OF
 THE PLANS. PLEASE CORRECT.
  
 4)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE ROOFING MATERIAL.
  
 6) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 STORM PANELS HAS PARTS THAT ARE NOT LEGIBLE. SUBMIT
 CLEAR LEGIBLE COPIES.
  
 7) SPECIFY THE MOUNTING INSTALLATION, TYPE OF FASTENER
 AND FASTENER SPACING FOR THE STORM PANELS. THIS CAN BE
 DONE BY CIRCLING THE APPROPRIATE ITEMS ON THE PRODUCT
 APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-07-18 Cont ID  
Sent By btrobaug Date 2007-07-18 Time 07:29 Rev Time 0.00
Received By btrobaug Date 2007-07-18 Time 06:58 Sent To M
Notes
2007-07-18 07:28:58 
  
  
  
  
  
 PROVISO
  
 R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-13 Cont ID  
Sent By adarroug Date 2007-11-13 Time 11:26 Rev Time 0.00
Received By adarroug Date 2007-11-13 Time 11:26 Sent To B
Notes
2007-11-13 11:26:44TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 09:50 Sent To B
Notes
2007-08-27 09:50:39TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 09:25 Rev Time 0.00
Received By jleech Date 2007-07-10 Time 10:18 Sent To  
Notes
2007-07-10 10:19:11TO "SFR" "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-18 Cont ID  
Sent By tgordon Date 2007-07-18 Time 14:22 Rev Time 0.20
Received By tgordon Date 2007-07-18 Time 14:22 Sent To P
Notes
2007-07-18 14:22:48NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 09:24 Rev Time 0.00
Received By jleech Date 2007-08-02 Time 09:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-07-12 Cont ID  
Sent By choops Date 2007-07-12 Time 10:30 Rev Time 0.00
Received By choops Date 2007-07-12 Time 10:30 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved