Plan Review Details - Permit 07070203
Plan Review Stops For Permit 07070203
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2008-10-31 Cont ID  
Sent By jnguyen Date 2008-10-31 Time 15:10 Rev Time 0.00
Received By jnguyen Date 2008-10-31 Time 8:00 Sent To  
Notes
2008-10-31 15:09:12THIS ADDRESS LOCATION IS VALID. HOWEVER, I ALSO WANTED
 TO NOTE THAT JAMES & I HANDLED A PALM BEACH COUNTY
 UNITY OF TITLE DEED THAT MENTIONED THAT THESE TWO
 PARCELS PCN# 74434404010000141 & PCN# 74434404020070010
 WERE GOING TO BE MERGED. THEY BOTH SHARE THE SAME
 PRIMARY ADDRESS OF 4805 S DIXIE HWY. I E-MAILED &
 CALLED THE APPROPRIATE PERSONNEL AT THE COUNTY TO TRY
 TO DISCERN WHICH PCN# WAS GOING TO TAKE PRECEDENT OR IF
 A COMPLETELY NEW ONE WAS GOING TO BE ISSUED (AS A
 RESULT OF THE MERGER). UNFORTUNATELY, NO ONE YET AT THE
 COUNTY HAS GOTTEN BACK TO ME IN TIME. I JUST WANTED TO
 INFORM ALL INTERESTED PARTIES THAT THIS PERMIT RECORD
 MAY "POSSIBLY" NEED TO BE MOVED UNDER A "POTENTIALLY"
 DIFFERENT PCN# (DEPENDING ON WHICH PCN# GETS ISSUED BY
 THE COUNTY FROM THE MERGER OF PCN# 74434404010000141 &
 PCN# 74434404020070010).

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2008-04-21 Cont ID  
Sent By lursu Date 2008-04-21 Time 11:26 Rev Time 0.00
Received By lursu Date 2008-04-21 Time 11:26 Sent To  
Notes
2008-04-21 11:32:26THE SITE ADDRESS IN USE 4805 S DIXIE HWY DOES NOT
 REFLECT THE EXACT LOCATION OF THE WORK .PERMIT
 APPLICATION DESCRIBES THE ADDRESS AS 4805-4815 S DIXIE
 HWY AND THE " LEFT SIDE OF THE BUILDING" .SINCE ARE 2
 BUILDINGS AND 2 PARCELS ,PCN = 74434404020070010 & PCN=
 74434404010000141 WITH SAME ADDRESS 4805 S DIXIE HWY
 ,PLEASE SPECIFY WHERE THE SITE ADDRESS OF 4815 S DIXIE
 HWY IS LOCATED AND IF THIS ADDRESS IS POSTED ON THE
 STRUCTURE.
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By rsimolo Date 2007-07-25 Time 15:29 Rev Time 4.44
Received By jwitmer Date 2007-08-08 Time 15:00 Sent To  
Notes
2007-08-08 15:44:504805 S DIXIE HWY/ 07070203
  
 BUILDING PLAN REVIEW
 PERMIT: 07070203
 ADD: 4805 S DIXIE HWY
 CONT: MOUW ASSOCIATES INC
 TEL: (561)715-0845
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE PERMIT APPLICATION DESCRIPTION OF PROJECT NEEDS
 TO ACCURATE TO THE WORK THAT IS ILLUSTRATED IN THE
 PLANS, PLEASE CORRECT APPLICATION OR DELETE WORK FROM
 PLAN. 106.1.1*
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4) THE APPLICATION HAS AN ADDRESS RANGE FROM 4805- 4815
 S DIXIE, THE CITY RECORDS AS WELL AS THE PROPERTY
 APPRAISERS OFFICE LIST THIS PROPERTY UNDER THE PROPERTY
 CONTROL NUMBER AS 4805 S DIXIE, PLEASE CORRECT. IF
 ADDITIONAL SUITE ADDRESSES WILL BE REQUIRED CONTACT
 LILY URSA (MIS DEPARTMENT) AT(561)822-1239.
  
 5) 04.2.1.3 THE BUILDING OFFICIAL MAY SET STANDARDS
 THROUGH DEPARTMENTAL POLICY STANDARDS FOR PLANS AND
 SPECIFICATIONS. "NO WHITE OUT" ALLOWED ON PLANS. SEE
 SHEET A1.01 BOTH IN THE HEADER STRIP AND IN THE BODY OF
 THE PLAN SEE GENERAL PROJECT DATA.
  
 6) SHEET A1.01 PLEASE UPDATE THE CODE REFERENCE TO THE
 2004 FBC BUILDING W/ 2006 AMENDMENTS.
  
 7) PLEASE PROVIDE THE LAST KNOWN OCCUPANCY TYPE?
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 8) THE PERMIT APPLICATION DESCRIPTION OF PROJECT MAY
 NEED TO BE MODIFIED TO SHOW INTENDED USE BUT AS THE
 PLANS INDICATE NOW THIS WILL BE A SINGLE MERCANTILE
 TENANT WITH 22,164 SQ FT WITHIN THE TENANT SPACE.
 PLEASE SEE,903.2.6 GROUP M.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT BUILDINGS CONTAINING A GROUP M OCCUPANCY
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1.WHERE A GROUP M FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M 2 );
 PLEASE UPDATE PLANS PROVIDING AN AUTOMATIC FIRE
 SPRINKLER SYSTEM OR SPLIT THE BUILDING INTO 2 FIRE
 AREAS EACH LESS THAN 12,000 SQ FT.
 DEFINITION: FIRE AREA. THE AGGREGATE FLOOR AREA
 ENCLOSED AND BOUNDED BY FIRE WALLS, FIRE BARRIERS,
 EXTERIOR WALLS OR FIRE-RESISTANCE-RATED HORIZONTAL
 ASSEMBLIES OF A BUILDING.
  
 9) SHEET A1.01 CODE ANALYSIS INDICATES THIS ALTERATION
 IS TO BE A LEVEL II ALTERATION ,PLEASE SEE 2004 EBC
 EXISTING BUILDING CODE 2006 AMENDMENTS SECTION 707.5.2
  
 A LEVEL III IS WHERE 30 % OF THE TOTAL SUM OF THE FLOOR
 AND ROOF AREAS OF THE BUILDING ARE INVOLVED IN
 STRUCTURAL ALTERATIONS WITHIN A 12-MONTH PERIOD, PLEASE
 CORRECT AND SEE THE REQUIREMENTS OF CHAPTER 7, EXISTING
 BUILDING CODE INCLUSIVE OF 708 ENERGY CONSERVATION.
 708.1 MINIMUM REQUIREMENTS. ALTERATIONS SUBJECT TO THIS
 CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER
 13 OF THE FLORIDA BUILDING CODE.
  
 10) SHEET A1.01 EGRESS DATA (NEW ADDITION ONLY) WHAT
 PORTION OF THIS WORK IS THE NEW ADDITION?106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 11) SHEET A1.01 EGRESS DATA ALSO LISTMERCANTILE AS
 WELL AS AN UNCONCENTRATED ASSEMBLY IS THE PURPOSE OF
 THE ASSEMBLY OCCUPANCY FOR A FUTURE TENANT BUILDOUT?.
  
 12)SHEETS A1.01 AND A2.01 BOTH INDICATE (2) AREAS OF
 CONCERN WITH TABLE 601.
  
 12A) THE NORTH WALL OF THE BUILDING SETS WITHIN A FOOT
 OF THE PROPERTY LINE, WITH 3 STOREFRONT OPENINGS, TABLE
 602 WILL REQUIRE THIS WALL TO BE A 3HR RATED WALL AND
 TABLE 704.8 INDICATES THERE CAN BE NO OPENINGS.
  
 12B) THE SOUTHWEST CORNER OF THE BUILDING WHERE THE
 NEWLY RELOCATED ELECTRIC METER IS LOCATED THIS WALL
 WILL ALSO NEED TO STATE THE DISTANCE FROM THE PROPERTY
 LINE SEE TABLE 602 FOR HOURLY RATINGS.
  
 13) SHEET A2.01 PLEASE PROVIDE THE ACCESS AISLE FOR THE
 HANDICAPPED PARKING SPACE.
 11-4.6.2(1)ALL SPACES MUST BE LOCATED ON AN
 ACCESSIBLE ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE
 SO THAT USERS WILL NOT BE COMPELLED TO WALK OR WHEEL
 BEHIND PARKED VEHICLES.
  
 14) SHEET A2.02 ROOF PLAN DOESN?T INDICATE ANY ROOF
 DRAINAGE, DIRECTION OF DRAINAGE, PRIMARY OR SECONDARY
 DRAINAGE SYSTEMS. PLEASE PROVIDE ADDITIONAL INFORMATION
 IN REGARDS TO 1503.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES,
 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, PLUMBING ,
 CHAPTER 11 .
  
 15) SHEET A2.02 INDICATES NEW AWNINGS, TO BE COVERED
 UNDER A SEPARATE PERMIT WITH ASSOCIATED FEES AND
 REVIEWS. 3202.3 ENCROACHMENTS 8 FEET OR MORE ABOVE
 GRADE.
 ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE
 SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4 .
  
 AWNINGS
 3202.3.1 AWNINGS , CANOPIES, MARQUEES AND SIGNS.
 AWNINGS , CANOPIES, MARQUEES AND SIGNS SHALL BE
 CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS
 SPECIFIED IN CHAPTER 16 . AWNINGS , CANOPIES, MARQUEES
 AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE
 ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE
 THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM
 THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT
 AWNINGS , CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED
 NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE.
  
 15) SHEET A7.01 THE DETAIL# 3 INDICATES A NEW ENTRY
 AREAS WITH A SECTION THROUGH HOW THIS AREAIS TO BE
 BUILT. THE WALL AREA REMOVED DOES HOWEVER LEAVE 3
 COURSES OF BLOCK IN THE AIR WITH A NOTE SEE STRUCTURAL
 FOR REINFORCEMENT. THE STRUCTURAL SHEET S2.01 HOWEVER
 DOES NOT DETAIL ANY WORK ON THE BUILDING NOT FACING
 DIXIE HWY. ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 16)SHEET A7.01 THE DETAIL# 4 INDICATES A NEW ENTRY
 AREAS WITH A SECTION THROUGH HOW THIS AREAIS TO BE
 BUILT. THE WALL AREA REMOVED DOES HOWEVER LEAVE 3
 COURSES OF BLOCK IN THE AIR WITH A NOTE SEE STRUCTURAL
 FOR REINFORCEMENT. THE STRUCTURAL SHEET S2.01 HOWEVER
 DOES NOT DETAIL ANY WORK ON THE BUILDING NOT FACING
 DIXIE HWY. ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 17) ) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
  
 18)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 19)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT WINDOWS- NO REPORT SUBMITTED
 B) GLAZED DOORS- NO REPORT SUBMITTED
 C) MULLIONS HORIZONTAL OR VERTICAL
 D) LINTELS NO REPORT SUBMITTED
 E) EXTERIOR METAL HOLLOW CORE DOORS NO REPORT
 SUBMITTED
 F) ROOFING ASSEMBLIES SEE NOTE BELOW
 G) STORM SHUTTERS SEE NOTES BLOW
  
 19) ROOFING REPORT:THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 XX___ CONTRACTOR DID NOT PROVIDE THE MEANROOF
 HEIGHT.
  
 XX___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 XX___ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 XX___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR
 ZONE _2& 3__ .
  
 POSSIBLY___ THE SYSTEM PROVIDED STATESLIMITATION#
 7, SHOULD THE FASTENERRESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A
 REVISEDFASTENER SPACING, PREPARED , SIGNEDAND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF CONSULTANT MAY
 BE SUBMITTED.
  
 POSSIBLY___THE SYSTEM PROVIDED INDICATESLIMITATION#
 9, NO ENHANCED FASTENING ALLOWED.
  
 20) HURRICANE MANUFACTURING CORP. SERIES HMC 1000 AL
 STOREFRONT SYSTEM REQUIRES A FLORIDA COVERSHEET AND
 ASSOCIATED REPORT BY ENGCO INC # 05-228.
  
 21) SHEETA3.02DETAIL# 5 IS THE WALL ADJACENT TO THE
 BRAILLE CLUB OF THE PALM BEACHES, THIS APPEARS TO BE A
 ZERO LOT LINE WALL REQUIRING A 3 HR FIRE RATING. AS
 DISCUSSED EARLIER UNDER COMMENT#12A THERE CAN BE NO
 OPENINGS ON THIS WALL, PLEASE LOOK AT SECTION 602.3
  
 TYPE III BUILDINGS: 602.3 TYPE III.
 TYPE III CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN
 WHICH THE EXTERIOR WALLS ARE OF NONCOMBUSTIBLE
 MATERIALS AND THE INTERIOR BUILDING ELEMENTS ARE OF ANY
 MATERIAL PERMITTED BY THIS CODE. FIRE-RETARDANT-TREATED
 WOOD FRAMING COMPLYING WITH SECTION 2303.2 SHALL BE
 PERMITTED WITHIN EXTERIOR WALL ASSEMBLIES OF A 2-HOUR
 RATING OR LESS.
 THIS PARTICULAR WALL AND PARAPET WILL REQUIRE A 3 HOUR
 FIRE RATING!!! PLEASE REVISE DETAILS.
  
 22) THE STRUCTURAL SHEETS DO NOT INDICATE AS TO WHAT
 CODE OR TO WHAT WIND DESIGN THEY DESIGNED THIS BUILDING
 TOO?
  
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 23) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-09-21 Cont ID  
Sent By jwitmer Date 2009-09-21 Time 16:58 Rev Time 1.50
Received By jwitmer Date 2009-09-21 Time 15:33 Sent To  
Notes
2009-09-21 16:57:104805 S DIXIE HWY/ 07070203
  
 BUILDING PLAN REVIEW
 PERMIT: 07070203
 ADD: 4805 S DIXIE HWY
 CONT: MOUW ASSOCIATES INC
 TEL: (561)715-0845
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 1 REVIEW
 ACTION: DENIED
 SEPT. 21/ 2009
  
 1) SHEET A3.01 & A3.02 DETAIL# 3. THE NORTH WALL OF THE
 BUILDING SETS WITHIN A FOOT OF THE PROPERTY LINE, WITH
 2 STOREFRONT OPENINGS, TABLE 602 WILL REQUIRE THIS WALL
 TO BE A 3HR RATED WALL AND TABLE 704.8 INDICATES THERE
 CAN BE NO OPENINGS.
  
 2) SHEET A7.01:
  
 2A) PLANS INDICATE THE USE OF A C10 X 25 CHANNEL TO BE
 MOUNTED TO THE EXISTING BEARING BLOCK WALL, AND TO BE
 GROUTED, WHAT STRENGTH WILL THE DESIGN MIX BE? COURSE
 OR FINE GROUT?
  
 2B) THE PLANS INDICATE THE C10 X 25 CHANNEL BUT THERE
 ARE TWO UNKNOWNS:
 1) HOW FAR DOES THE CHANNEL GO PAST THE COLUMN LINE.
 2) WHERE DOES THE FIRST EMBED START FROM THE END OF THE
 C- CHANNEL.
  
 3) SHEET A7.01; 106.1.2 ADDITIONAL INFORMATION
 REQUIRED, 1609.1.2, & RULE 9B-72.
  
 3A) IN DETAIL 2 & 3 IS ILLUSTRATED A INSET ALCOVE WITH
 STEEL STUD CEILING JOIST. THE PLANS INDICATE A STEEL
 ANGLE 1 1/2" X 11/2" X 1/4" @ 4'-0" O.C. THE PLANS LACK
 THE ATTCHMENT METHOD
 AT THE STEEL ANGLE HEADER NOR DO THEY PROVIDE DETAIL AT
 THE BAR JOIST, WHAT HAPPENS IF THE BAR JOIST DO NOT
 LINE UP WITH THE FOUR FT ON CENTER?
  
 3B) THE SECOND ISSUE IS THE STEEL ANGLE HEADER NO
 SIZING INFORMATION HAS BEEN PROVIDED, THE ONLY DETAIL
 PROVIDED IS THE BACK WALL, THE PLANS DO NOT PROVIDE A
 CUT SECTION THROUGH THE SIDE WALL OF THE ALCOVE TO SEE
 IF THE HEADER IS CONTINIOUS AND WHAT TYPE OF BRACING IS
 REQUIRED FROM THE BAR JOIST FOR LATERAL SUPPORT.
  
 3C) THE DETAIL ALSO DOES NOT INDICATE THE USE OF ANY
 CORNER POST MAKING THE ALCOVE HANG INDEPNDENTLY FROM
 THE STRUCTURAL ELEMENTS LOCATED ABOVE THE NEW ALCOVE
 FRAMING. WHILE SHEET A9.01 DOES INDICATE A 90 DEGREE
 OUTSIDE CORNER THE PLANS NOR ANY PRODUCT APPROVALS
 INDICATE ANY INSIDE CORNERS WITH THE SILL AND HEADER
 LOCATED WITHIN THE INTERIOR SPACE. PLEASE PROVIDE
 PRODUCT TESTING INDICATING LARGE MISSILE TESTING AS
 WELL AS WIND PRESSURE. SHEET 18, 19 & 19A ALL INDICATE
 WHERE TTHE EXTERIOR OF THE WINDOW FRAME IS LOCATED
 MAKING THE DETAIL A OUTSIDE OR EXTERIOR CORNER WITH THE
 FRAMING LOCATED WITHIN THE TENANT SPACE.
  
 3D) WITHIN THE PRODUCT APPROVAL (NOA 08-1104.03) PLEASE
 INDICATE THE GLAZING OPTION AND MULLION FOR THIS
 EFFECTS THE SIZE AND PRESSURE OF THE WINDOW OPENINGS.
  
 4) THE SCOPE OF WORK HAS DRAMATICALLY CHANGED PLEASE
 UPDATE THE VALUE OF WORK TO BE COMPLETED UNDERTHIS
 PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-20 Cont ID  
Sent By jwitmer Date 2008-10-20 Time 11:39 Rev Time 0.77
Received By jwitmer Date 2008-10-20 Time 11:10 Sent To  
Notes
2008-10-20 11:40:54NO ROOFING CONTRACTOR SIGNED ON NOR NO ROOFING PRODUCT
 APPROVALS WERE SUBMITTED, WILL REQUIRE A SEPERATE
 PERMIT, FEES AND REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-17 Cont ID  
Sent By jwitmer Date 2008-04-17 Time 13:21 Rev Time 2.22
Received By jwitmer Date 2008-04-17 Time 13:21 Sent To  
Notes
2008-04-17 13:36:14BUILDING PLAN REVIEW
 PERMIT: 07070203
 ADD: 4805 S DIXIE HWY
 CONT: MOUW ASSOCIATES INC
 TEL: (561)715-0845
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 APRIL 17,2008
  
 3RDREVIEW
 ACTION: DENIED
  
 1)PLEASE SEE ATTACHED SHEETS FROM THE PROPERTY
 APPRAISERS OFFICE IT APPEARS THERE IS A LOT LINE THAT
 RUNS THROUGH THE PROPERTY REQUIRING A UNITY OF TITLE.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 2) IT HAS BEEN BROUGHT TO MY ATTENTION THAT THE ENERGY
 CODE COMPLIANCE FORMS ARE IN ERROR AND WOULD NEED
 CORRECTING:
  
 2A)WINDOWS NEED TO BE UPDATED TO INDICATE THE CURRENT
 NUMBER OF WINDOWS AND SQ FOOTAGE.
 2B) EXTERIOR GLAZED DOORS INDICATES NONE!
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-29 Cont ID  
Sent By jwitmer Date 2007-10-29 Time 16:20 Rev Time 3.33
Received By jwitmer Date 2007-10-29 Time 16:20 Sent To  
Notes
2007-10-29 16:38:204805 S DIXIE HWY/ 07070203
  
 BUILDING PLAN REVIEW
 PERMIT: 07070203
 ADD: 4805 S DIXIE HWY
 CONT: MOUW ASSOCIATES INC
 TEL: (561)715-0845
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 OCT.29, 2007
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED
  
 4) THE APPLICATION HAS AN ADDRESS RANGE FROM 4805- 4815
 S DIXIE, THE CITY RECORDS AS WELL AS THE PROPERTY
 APPRAISERS OFFICE LIST THIS PROPERTY UNDER THE PROPERTY
 CONTROL NUMBER AS 4805 S DIXIE, PLEASE CORRECT. IF
 ADDITIONAL SUITE ADDRESSES WILL BE REQUIRED CONTACT
 LILY URSA (MIS DEPARTMENT) AT(561)822-1239.
  
 5-7) COMPLIED.
  
 8)PLANS NOW INDICATE THE BUILDING WILL BE FULLY
 SPRINKLERED,SHEET A1.01 INDICATES AS SUCH AND ALSO
 INDICATES THE AREA INCREASES TAKEN FOR THE FIRE
 SPRINKLERS. BEFORE A PERMIT CAN BE ISSUED FOR THE
 REMODELING OF
 THIS BUILDING FIRE SPRINKLER LAYOUT PLANS WILL NEED TO
 ACCOMPANY THE BUILDING PLANS. NOTE ONCE THE BUILDING
 PERMIT IS ISSUED, THE FIRE SPINKLER COMPANY WILL NEED
 TO APPLY FOR THEIR OWN PLANS AND PERMIT, AT THIS TIME
 THE FIRE DEPARTMENT REVIEWS THE FIRE SPRINKLER PLANS
 AND ISSUES THE PERMIT FOR FIRE SPRINKLERS. 506.3
 AUTOMATIC FIRE SPRINKLER INCREASES, & 106.3.5.1.1(5)
 SCHEMATIC FIRE SPRINKLERS, MINIMUM PLAN REVIEW
 CRITERIA.
  
 9-12)
  
 13) 2ND REQUEST, SHEET A2.01 PLEASE PROVIDE THE ACCESS
 AISLE FOR THE HANDICAPPED PARKING SPACE. 11-4.6.2(1)
 ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE ROUTE NO
 LESS THAN 44 INCHES (1118 MM)WIDE SO THAT USERS WILL
 NOT BE COMPELLED TO WALK OR WHEEL BEHIND PARKED
 VEHICLES.
  
 14) GUTTERS & DOWNSPOUTS. COMPIED.
  
 15) AWNINGS TO BE UNDER SEPERATE PERMIT. COMPLIED.
  
 16)COMPLIED.
  
 17) ) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
  
 18) 2ND REQUEST,PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 19)2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) STOREFRONT WINDOWS- NO REPORT SUBMITTED
 B) GLAZED DOORS- NO REPORT SUBMITTED
 C) MULLIONS HORIZONTAL OR VERTICAL
 D) LINTELS NO REPORT SUBMITTED
 E) EXTERIOR METAL HOLLOW CORE DOORS NO REPORT
 SUBMITTED
 F) ROOFING ASSEMBLIES SEE NOTE BELOW, NO REPORT
 SUBMITTED
 G) STORM SHUTTERS SEE NOTES BLOW
  
 19) ROOFING REPORT:THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 XX___ CONTRACTOR DID NOT PROVIDE THE MEANROOF
 HEIGHT.
  
 XX___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 XX___ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 XX___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR
 ZONE _2& 3__ .
  
 POSSIBLY___ THE SYSTEM PROVIDED STATESLIMITATION#
 7, SHOULD THE FASTENERRESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A
 REVISEDFASTENER SPACING, PREPARED , SIGNEDAND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF CONSULTANT MAY
 BE SUBMITTED.
  
 POSSIBLY___THE SYSTEM PROVIDED INDICATESLIMITATION#
 9, NO ENHANCED FASTENING ALLOWED.
  
 20) HURRICANE MANUFACTURING CORP. SERIES HMC 1000 AL
 STOREFRONT SYSTEM REQUIRES A FLORIDA COVERSHEET AND
 ASSOCIATED REPORT BY ENGCO INC # 05-228.
  
 21-22)
  
 23) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By jwitmer Date 2007-09-05 Time 14:50 Rev Time 3.33
Received By jwitmer Date 2007-09-05 Time 14:50 Sent To PC
Notes
2007-09-05 14:51:214805 S DIXIE HWY/ 07070203
  
 BUILDING PLAN REVIEW
 PERMIT: 07070203
 ADD: 4805 S DIXIE HWY
 CONT: MOUW ASSOCIATES INC
 TEL: (561)715-0845
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE PERMIT APPLICATION DESCRIPTION OF PROJECT NEEDS
 TO ACCURATE TO THE WORK THAT IS ILLUSTRATED IN THE
 PLANS, PLEASE CORRECT APPLICATION OR DELETE WORK FROM
 PLAN. 106.1.1*
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4) THE APPLICATION HAS AN ADDRESS RANGE FROM 4805- 4815
 S DIXIE, THE CITY RECORDS AS WELL AS THE PROPERTY
 APPRAISERS OFFICE LIST THIS PROPERTY UNDER THE PROPERTY
 CONTROL NUMBER AS 4805 S DIXIE, PLEASE CORRECT. IF
 ADDITIONAL SUITE ADDRESSES WILL BE REQUIRED CONTACT
 LILY URSA (MIS DEPARTMENT) AT (561)822-1239.
  
 5) 04.2.1.3 THE BUILDING OFFICIAL MAY SET STANDARDS
 THROUGH DEPARTMENTAL POLICY STANDARDS FOR PLANS AND
 SPECIFICATIONS. "NO WHITE OUT" ALLOWED ON PLANS. SEE
 SHEET A1.01 BOTH IN THE HEADER STRIP AND IN THE BODY OF
 THE PLAN SEE GENERAL PROJECT DATA.
  
 6) SHEET A1.01 PLEASE UPDATE THE CODE REFERENCE TO THE
 2004 FBC BUILDING W/ 2006 AMENDMENTS.
  
 7) PLEASE PROVIDE THE LAST KNOWN OCCUPANCY TYPE?
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 8) THE PERMIT APPLICATION DESCRIPTION OF PROJECT MAY
 NEED TO BE MODIFIED TO SHOW INTENDED USE BUT AS THE
 PLANS INDICATE NOW THIS WILL BE A SINGLE MERCANTILE
 TENANT WITH 22,164 SQ FT WITHIN THE TENANT SPACE.
 PLEASE SEE, 903.2.6 GROUP M.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT BUILDINGS CONTAINING A GROUP M OCCUPANCY
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1. WHERE A GROUP M FIRE AREA EXCEEDS 12,000 SQUARE FEET
 (1115 M 2 );
 PLEASE UPDATE PLANS PROVIDING AN AUTOMATIC FIRE
 SPRINKLER SYSTEM OR SPLIT THE BUILDING INTO 2 FIRE
 AREAS EACH LESS THAN 12,000 SQ FT.
 DEFINITION: FIRE AREA. THE AGGREGATE FLOOR AREA
 ENCLOSED AND BOUNDED BY FIRE WALLS, FIRE BARRIERS,
 EXTERIOR WALLS OR FIRE-RESISTANCE-RATED HORIZONTAL
 ASSEMBLIES OF A BUILDING.
  
 9) SHEET A1.01 CODE ANALYSIS INDICATES THIS ALTERATION
 IS TO BE A LEVEL II ALTERATION ,PLEASE SEE 2004 EBC
 EXISTING BUILDING CODE 2006 AMENDMENTS SECTION 707.5.2
  
 A LEVEL III IS WHERE 30 % OF THE TOTAL SUM OF THE FLOOR
 AND ROOF AREAS OF THE BUILDING ARE INVOLVED IN
 STRUCTURAL ALTERATIONS WITHIN A 12-MONTH PERIOD, PLEASE
 CORRECT AND SEE THE REQUIREMENTS OF CHAPTER 7, EXISTING
 BUILDING CODE INCLUSIVE OF 708 ENERGY CONSERVATION.
 708.1 MINIMUM REQUIREMENTS. ALTERATIONS SUBJECT TO THIS
 CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER
 13 OF THE FLORIDA BUILDING CODE.
  
 10) SHEET A1.01 EGRESS DATA (NEW ADDITION ONLY) WHAT
 PORTION OF THIS WORK IS THE NEW ADDITION? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 11) SHEET A1.01 EGRESS DATA ALSO LIST MERCANTILE AS
 WELL AS AN UNCONCENTRATED ASSEMBLY IS THE PURPOSE OF
 THE ASSEMBLY OCCUPANCY FOR A FUTURE TENANT BUILDOUT?.
  
 12) SHEETS A1.01 AND A2.01 BOTH INDICATE (2) AREAS OF
 CONCERN WITH TABLE 601.
  
 12A) THE NORTH WALL OF THE BUILDING SETS WITHIN A FOOT
 OF THE PROPERTY LINE, WITH 3 STOREFRONT OPENINGS, TABLE
 602 WILL REQUIRE THIS WALL TO BE A 3HR RATED WALL AND
 TABLE 704.8 INDICATES THERE CAN BE NO OPENINGS.
  
 12B) THE SOUTHWEST CORNER OF THE BUILDING WHERE THE
 NEWLY RELOCATED ELECTRIC METER IS LOCATED THIS WALL
 WILL ALSO NEED TO STATE THE DISTANCE FROM THE PROPERTY
 LINE SEE TABLE 602 FOR HOURLY RATINGS.
  
 13) SHEET A2.01 PLEASE PROVIDE THE ACCESS AISLE FOR THE
 HANDICAPPED PARKING SPACE.
 11-4.6.2(1) ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE
 ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT
 USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
  
 14) SHEET A2.02 ROOF PLAN DOESN?T INDICATE ANY ROOF
 DRAINAGE, DIRECTION OF DRAINAGE, PRIMARY OR SECONDARY
 DRAINAGE SYSTEMS. PLEASE PROVIDE ADDITIONAL INFORMATION
 IN REGARDS TO 1503.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES,
 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, PLUMBING ,
 CHAPTER 11 .
  
 15) SHEET A2.02 INDICATES NEW AWNINGS, TO BE COVERED
 UNDER A SEPARATE PERMIT WITH ASSOCIATED FEES AND
 REVIEWS. 3202.3 ENCROACHMENTS 8 FEET OR MORE ABOVE
 GRADE.
 ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE
 SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4 .
  
 AWNINGS
 3202.3.1 AWNINGS , CANOPIES, MARQUEES AND SIGNS.
 AWNINGS , CANOPIES, MARQUEES AND SIGNS SHALL BE
 CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS
 SPECIFIED IN CHAPTER 16 . AWNINGS , CANOPIES, MARQUEES
 AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE
 ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE
 THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM
 THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT
 AWNINGS , CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED
 NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE.
  
 15) SHEET A7.01 THE DETAIL# 3 INDICATES A NEW ENTRY
 AREAS WITH A SECTION THROUGH HOW THIS AREA IS TO BE
 BUILT. THE WALL AREA REMOVED DOES HOWEVER LEAVE 3
 COURSES OF BLOCK IN THE AIR WITH A NOTE SEE STRUCTURAL
 FOR REINFORCEMENT. THE STRUCTURAL SHEET S2.01 HOWEVER
 DOES NOT DETAIL ANY WORK ON THE BUILDING NOT FACING
 DIXIE HWY. ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 16) SHEET A7.01 THE DETAIL# 4 INDICATES A NEW ENTRY
 AREAS WITH A SECTION THROUGH HOW THIS AREA IS TO BE
 BUILT. THE WALL AREA REMOVED DOES HOWEVER LEAVE 3
 COURSES OF BLOCK IN THE AIR WITH A NOTE SEE STRUCTURAL
 FOR REINFORCEMENT. THE STRUCTURAL SHEET S2.01 HOWEVER
 DOES NOT DETAIL ANY WORK ON THE BUILDING NOT FACING
 DIXIE HWY. ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 17) ) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
  
 18) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 19) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT WINDOWS- NO REPORT SUBMITTED
 B) GLAZED DOORS- NO REPORT SUBMITTED
 C) MULLIONS HORIZONTAL OR VERTICAL
 D) LINTELS NO REPORT SUBMITTED
 E) EXTERIOR METAL HOLLOW CORE DOORS NO REPORT
 SUBMITTED
 F) ROOFING ASSEMBLIES SEE NOTE BELOW
 G) STORM SHUTTERS SEE NOTES BLOW
  
 19) ROOFING REPORT: THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 XX___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF
 HEIGHT.
  
 XX___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 XX___ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 XX___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2& 3__ .
  
 POSSIBLY___ THE SYSTEM PROVIDED STATES LIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A
 REVISED FASTENER SPACING, PREPARED , SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF CONSULTANT MAY
 BE SUBMITTED.
  
 POSSIBLY___ THE SYSTEM PROVIDED INDICATES LIMITATION#
 9, NO ENHANCED FASTENING ALLOWED.
  
 20) HURRICANE MANUFACTURING CORP. SERIES HMC 1000 AL
 STOREFRONT SYSTEM REQUIRES A FLORIDA COVERSHEET AND
 ASSOCIATED REPORT BY ENGCO INC # 05-228.
  
 21) SHEET A3.02 DETAIL# 5 IS THE WALL ADJACENT TO THE
 BRAILLE CLUB OF THE PALM BEACHES, THIS APPEARS TO BE A
 ZERO LOT LINE WALL REQUIRING A 3 HR FIRE RATING. AS
 DISCUSSED EARLIER UNDER COMMENT# 12A THERE CAN BE NO
 OPENINGS ON THIS WALL, PLEASE LOOK AT SECTION 602.3
  
 TYPE III BUILDINGS: 602.3 TYPE III.
 TYPE III CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN
 WHICH THE EXTERIOR WALLS ARE OF NONCOMBUSTIBLE
 MATERIALS AND THE INTERIOR BUILDING ELEMENTS ARE OF ANY
 MATERIAL PERMITTED BY THIS CODE. FIRE-RETARDANT-TREATED
 WOOD FRAMING COMPLYING WITH SECTION 2303.2 SHALL BE
 PERMITTED WITHIN EXTERIOR WALL ASSEMBLIES OF A 2-HOUR
 RATING OR LESS.
 THIS PARTICULAR WALL AND PARAPET WILL REQUIRE A 3 HOUR
 FIRE RATING!!! PLEASE REVISE DETAILS.
  
 22) THE STRUCTURAL SHEETS DO NOT INDICATE AS TO WHAT
 CODE OR TO WHAT WIND DESIGN THEY DESIGNED THIS BUILDING
 TOO?
  
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 23) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 08:32 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 08:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-08 Cont ID  
Sent By dpalmer Date 2008-04-08 Time 09:42 Rev Time 0.00
Received By dpalmer Date 2008-04-08 Time 09:42 Sent To  
Notes
2008-04-08 09:42:52** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE STILL BEING SUBMITTED FOR METHOD *A* WHICH IS FOR
 WHOLE BUILDING COMPLIANCE. HOW IS THIS POSSIBLE WHEN
 THE SCOPE OF WORK IS NOT FOR THE WHOLE BUILDING? PLANS
 STILL SHOW SEVERAL ITEMS ARE STILL SHOWN AS EXISTING OR
 AREAS WHICH ARE NOT TO BE INCLUDED IN WORK.
 PLEASE KNOW THAT IN ORDER TO USE METHOD A, ALL BUILDING
 COMPONENTS MUST BE KNOWN, INSERTED AND MEETING CURRENT
 MINIMUM CODES. THIS IS NOT THE CASE ON THE CALCULATIONS
 SUBMITTED.
 PLEASE SEE RESPONSE AS THIS SPECIFICALLY SPEAKS OF A
 *SHELL* BUILDING. PLEASE SEE 13-101.1.6 WHICH IS FOR
 SHELL BUILDINGS AND IT DOES NOT PERMIT THE USE OF
 METHOD *A* YET METHOD *A* IS STILL BEING SUBMITTED.
 PLEASE SEE 13-101.1.3, 13-400.0.C.4,13-400.0.B,
 13-400.3.B, 13-400.3.C, 13-415.2, 13-415.2.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE ALSO KNOW AS NOTED IN SECTIONS ABOVE THE VERSION
 SUBMITTED IS 3.0 WHICH IS NOT YET ADOPTED PER FBC.
 PLEASE SEE FBC 13-400.3.B, C AND EVEN A AS THIS SHOULD
 BE "VERSION" 2.5 WHICH INCORPORATES ENERGY GAUGE SUMMIT
 VERSIONS 3.0-3.14 WHICH ARE GENERATED BY VERSION 2.5.
 PLEASE SEE THERE ARE SEVERAL ITEMS ON PLANS WHICH DO
 NOT CORRELATE WITH THE SUBMITTED CALCULATIONS.
 FOR EXAMPLES:
 ** NOT WHOLE BUILDING.
  
 ** PLEASE SEE THE EXTERIOR LIGHTING ON PLANS AND EVEN
 ON SHEET E-2.1 DOES NOT CORRELATE WITH THE INPUT DATA
 REPORT OR SUMMARY SHEETS. THIS TABLE ON PLANS ALSO
 SHOWS A TABLE FOR METHOD B SPACE BY SPACE FOR EXTERIOR
 ONLY. IN EITHER CASE PLANS OR LIGHTING AS SHOWN DOES
 NOT CORRELATE WITH THE SUBMITTED CALCULATIONS.
  
 ** PLEASE SEE THE LIGHTING INFORMATION ON THE EXTERIOR
 FIXTURES ON THE INPUT DATA REPORT ALSO DOES NOT
 CORRELATE WITH THE SUMMARY SHEETS SUBMITTED IN THE SAME
 CALCULATIONS.
  
 ** NO FIXTURE LEGEND ON PLANS.
  
 ** PLEASE SEE FOR ANOTHER EXAMPLE THE INPUT DATA
 REPORT/ENERGY CALCULATIONS SUBMITTED ARE NOT COMPLETE:
 SEE *DOORS* AS THIS SECTION IN BLANK AND CONTAINS NO
 INFORMATION. PLEASE LOOK FOR COMMENTS FROM OTHER TRADES
 FOR THIS ITEM AS THIS IS BEING GIVEN FOR INFORMATION.
 ALL BUILDING COMPONENTS AS WELL AS ELECTRICAL ETC ON
 PLANS SHALL COORDINATE WITH CALCULATIONS SUBMITTED.
  
 ** THESE ITEMS ABOVE GIVEN AS SOME EXAMPLES AND IS IN
 NO WAY ALL ITEMS WHICH REQUIRE ATTENTION.
 NOTE #64 ON SHEET E-0.1 STATES ALL LIGHTING SHOWN IN
 COMPLIANCE WITH FBC AND CHAPTER 13. IT IS UNCLEAR WHERE
 THE MINIMUM CODE COMPLIANCE DETAILS ARE AT THIS TIME ON
 PLANS.
  
 2) NOTE: ONCE AGAIN PLEASE CORRELATE SCOPE OF WORK AS
 ELECTRICAL PLANS SHOW WORK BEING DONE IN ADJACENT SPACE
 YET ARCHITECTURAL PLANS SPECIFICALLY MAKE NOTES TO * NO
 DEMO WORK*, * EXISTING TO REMAIN* ETC.
  
 3) NOTE: PLEASE SEE NO LIGHTING CONTROLS ADDED TO PLANS
 PER 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4
 A NOTE WAS ADDED FOR EXTERIOR LIGHTING HOWEVER NO TIME
 CLOCK ETC WAS SHOWN.
 PLEASE SEE NO OTHER LIGHTING CONTROLS WERE LOCATED ON
 PLANS AND NOT SHOWN ONCE AGAIN.
  
 4) NOTE: PLEASE VERIFY THE ADDITIONAL METER AND WHAT
 APPEARS TO BE A SERVICE AND PANELS NOW SHOWN ON THE
 WEST ELEVATION ON BUILDING INCLUDING THE INTERIOR WALL
 OF THE WEST ELEVATION. THESE ARE NO LABELED AND ARE NOT
 ON THE RISER.
 FBC 106.1.2 AND 106.3.5.1.2 FOR ADDITIONAL INFORMATION
 AND COORDINATION AS ADOPTED PER THE CITY OF WEST PALM
 BEACH.
  
 5) NOTE: PLEASE SEE FS 553.80(2) (B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THE FOLLOWING SECTIONS OF THE CODE WERE GIVEN IN THREE
 REVIEWS AND PLANS DO NOT SHOW COMPLIANCE AND IN SOME
 CASES NO CHANGES HAVE BEEN MADE TO PLANS.
 13-415.1.ABC.1.1, .1.2, .1.3,.1.4 AND 13-415.2 WERE
 GIVEN IN ALL THREE REVIEWS.
 PLEASE SEE THE STATUTORY REQUIRED FEE IS NOW ASSESSED
 DUE TO THESE SAME SECTIONS BEING REPEATED. THIS IS NOT
 A FEE REQUIRED BY LOCAL RULING; THIS IS A REQUIRED FEE
 PER STATUTE GIVEN ABOVE.
 THE FEE OF $4,920 WILL BE DUE BEFORE PLANS MAY BE
 RESUBMITTED. THE STATUTE REQUIRES THE FEE TO BE PAID
 BEFORE PLANS MAY BE RESUBMITTED.
 ** ONE SET OF ELECTRICAL PLANS AND CALCULATIONS ARE
 BEING RETAINED BY THIS OFFICE.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By dpalmer Date 2007-10-16 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2007-10-16 Time 12:29 Sent To  
Notes
2007-10-16 13:05:31 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE THE ADDRESS ON THE TITLE BLOCKS ON
 ARCHITECTURAL SHEETS CALL FOR 4805 S DIXIE, THE
 ELECTRICAL PLANS CALL FOR 4801-4815 AND PERMIT
 APPLICATION STILL INDICATES 4805-4815.
 PLEASE CORRELATE ALL AND SEE COMMENTS FOR ADDRESSING.
 PLEASE ADJUST TITLE BLOCKS AS NEEDED. ** SHEETS WHICH
 DO NOT NEED REVISIONS FOR OTHER COMMENTS, THIS MAY DONE
 BY OTHER MEANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE.
  
 2) NOTE: PLEASE SUBMIT INTERIOR LIGHTING PERFORMANCE
 CALCULATIONS. 13-415.2 HOW IS METHOD *A* BEING
 SUBMITTED FOR A SHELL BUILDING WHICH IS EXISTING?
 PLEASE SEE MECHANICAL REVIEW COMMENTS.
  
 3) NOTE: PLEASE CLARIFY THE METHOD OF CONTROL FOR
 LIGHTING PER 13-415.1.ABC.1.1, .1.2 AND .1.3
 PLEASE SEE THE TYPE OF TIME CLOCK REQUIRED FOR EXTERIOR
 LIGHTING NEED TO BE CLARIFIED. NOT SHOWN ON PLANS.
 PLEASE SEE 13-415.1.ABC.1.4
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT #9 WHICH
 COMMENTED ON THE DISTANCE THE GUTTER WOULD BE IN FRONT
 OF ELECTRICAL EQUIPMENT. THE PLANS ARE NOW SHOWN WITH A
 NOTE WHICH MENTIONS TO MEET CODE. PLEASE PROVIDE A
 MOUNTING/RACK DETAIL AS ALL METER, MAINS EQUIPMENT WILL
 BE MOUNTED OFF THE WALL BY A SUBSTANTIAL DISTANCE.
 ** PREVIOUS NOTE **
 PLEASE SEE THE GUTTER SIZES ARE SHOWN WHICH APPEAR TO
 EXCEED THE DISTANCE IN FRONT OF THE ELECTRICAL SERVICE
 EQUIPMENT PER 110.26A3
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-24 Cont ID  
Sent By dpalmer Date 2007-07-24 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2007-07-23 Time 16:18 Sent To  
Notes
2007-07-24 12:16:15*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE SPACE ON THE PERMIT APPLICATION
 WHICH REQUIRES THE DESCRIPTION OF THE PROJECT TO BE IN
 DETAIL. PLEASE SEE THIS MENTIONS *EXTERIOR IMPROVEMENTS
 AND RE-ROOF* HOWEVER THE SCOPE OF WORK AS PLACE DON
 PLANS FAR EXCEED THIS STATEMENT.
 PLEASE ADJUST PERMIT APPLICATION.
  
 2) NOTE: PLEASE SEE THE PLANS CALL FOR THIS AS A LEVEL
 2 ALTERATION PER FBC EXISTING BUILDING CODE. PLEASE
 VERIFY THIS AND SEE BUILDING REVIEW COMMENTS ALONG WITH
 OTHER TRADES AS THIS BUILDING IS NOT EXISTING AS A
 SHELL FOR FUTURE BUILD OUTS.
 FBC 106.1.2
  
 3) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE SEE THE ARCHITECTURAL SHEETS WHICH ARE LISTING
 SOME OTHER CODES THAN WHAT IS IN EFFECT AT THIS TIME
 AND ALSO SHOWS SOME OTHER SECTIONS NOT CURRENTLY IN
 EFFECT.
 PLEASE SEE PLANS WHICH STATE 2004 FBC MAY NOT BE
 ACCURATE AS THERE HAVE BEEN REVISIONS TO THE CODE FOR
 OTHER ADOPTED CODES. THIS IS WHY THESE SHOULD STATE THE
 2006 REVISION TO THE 2004 FBC.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72 (WHEN IN DESIGN)
 2003 NFPA-101
  
  
 4) NOTE: PLEASE SEE THAT PLANS AND APPLICATION WILL BE
 ROUTED TO THE ADDRESSING REVIEWER. ONCE THE CORRECT
 ADDRESS(S) AND/OR SUITE HAVE BEEN DETERMINED PLEASE
 ADJUST AND CORRECT TITLE BLOCKS.
 FAC 61G15-23.002, FAC 61G1-16.004
  
 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS FOR THE
 BUILDING AS REQUIRED PER 13-415.1.AB.1.1, 13-415.1.B.
 13-415.1.C,AND 13-415.2 FOR PERFORMANCE. EXTERIOR
 LIGHTING, 13-415.2.ABC.1.3, (TABLE). PLEASE SEE THIS IS
 BEING DONE AS A SHELL AND METHOD OF CALCULATIONS ARE
 SPECIFIC.
  
 6) NOTE: PLEASE SEE AS MINIMUM LIGHTING PER THE
 FOLLOWING COMMENT WILL BE REQUIRED ON THE INTERIOR OF
 THE SHELL BUILDING PLEASE SEE THAT LIGHTING CONTROLS OF
 SOME KIND WILL BE REQUIRED PER 13-415.1.ABC.1.1, .1.2
 AND .1.3
 PLEASE SEE THE TYPE OF TIME CLOCK REQUIRED FOR EXTERIOR
 LIGHTING NEED TO BE CLARIFIED.
 PLEASE SEE 13-415.1.ABC.1.4
  
 7) NOTE: PLEASE SEE FIRE MARSHAL AND LIFE SAFETY CODE
 REQUIRES MINIMUM LIGHTING INSIDE SHELL SPACE AND EXIT
 LIGHTING REQUIRED PER FIRE MARSHAL AND LIFE SAFETY
 CODE.
 PLEASE ADJUST PLANS TO INCLUDE ALONG WITH SOME SORT OF
 BATTERY BACK UP FIXTURES.
 LS 101 7.8, 7.9
  
 8) NOTE: PLEASE SEE THE RISER APPEARS TO SHOW THE
 LOCATIONS OF THE MAINS TOO HIGH. PLEASE SEE 110.26,
 230.70, 404.8A.
 PLEASE PROVIDE THE ELEVATIONS OF THE EQUIPMENT AS SHOWN
 ON RISER.
  
 9) NOTE: PLEASE SEE THE GUTTER SIZES ARE SHOWN WHICH
 APPEAR TO EXCEED THE DISTANCE IN FRONT OF THE
 ELECTRICAL SERVICE EQUIPMENT PER 110.26A3
  
 10) NOTE: PLEASE SEE THE RISER SHOWS *STRUCTURAL STEEL*
 AS PART OF THE GROUNDING ELECTRODE SYSTEM. PLEASE
 CLARIFY METHODS. PLEASE SEE THIS IS AN EXISTING
 BUILDING AND UNLESS THE EXISTING FOOTER STEEL IS
 ALREADY A PART OF THE SYSTEM, THE EXISTING FOOTER STEEL
 IS NOT REQUIRED TO BE PART AS THIS WOULD AFFECT THE
 STRUCTURAL INTEGRITY OF THE FOOTER.
 250.50
  
 11) NOTE: PLEASE SEE THAT IN NO CASE MAY *WHITE-OUT* BE
 USED ON PLANS.
 FS 471/481
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-23 16:19:39PLANS REMOVED FROM INCOMING IN ELECTRICAL FOR REVIEW.
 PLANS WILL BE RETURNED TO INCOMING WAITING FOR COMM
 BOARD ONCE REVIEW IS COMPLETED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-10-29 Cont ID  
Sent By mawillia Date 2008-10-29 Time 15:12 Rev Time 0.00
Received By mawillia Date 2008-10-29 Time 14:20 Sent To I
Notes
2008-10-29 14:40:16*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS A2.01, A3.01, E-2.1,
 FA-0.1, FA-1.1, AND FP-1 THRU FP-3 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-04-21 Cont ID  
Sent By mawillia Date 2008-04-21 Time 11:56 Rev Time 0.00
Received By mawillia Date 2008-04-21 Time 10:54 Sent To  
Notes
2008-04-21 11:10:25*****DENIED*****
  
 *THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN STILL NEED TO BE ADDRESSED:
  
  
 5. ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH DIXIE HIGHWAY, POST THE NUMERICAL ADDRESS(ES) ON
 THE BUILDING. AS PER WEST PALM BEACH CODE, ADDRESS
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH. IF THERE ARE REAR DOORS FOR THESE
 TENANT SPACES, 3" IN HEIGHT AND 1" IN WIDTH NUMBERS
 SHALL BE REQUIRED ON THE REAR DOORS. * SHOW/DISPLAY THE
 ACTUAL NUMBERS
  
 *NEW COMMENT:
  
 A. IF THIS STRUCTURE IS TO BE FIRE PROTECTED AS PER THE
 SPRINKLER AND FIRE ALARM NOTE ON SHEET A1.01, PROVIDE A
 LAYOUT OF THE FIRE ALARM/FIRE SPRINKLER SYSTEM FOR THIS
 SITE. * A SPRINKLER LAYOUT WAS PROVIDED, HOWEVER NO
 NUMERICAL ADDRESS IN THE TITLE BLOCK OF THESE SUBMITTED
 FP SHEETS * COULD NOT LOCATE THE FIRE ALARM LAYOUT AS
 PER YOUR RESPONSE
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-25 Cont ID  
Sent By mawillia Date 2007-10-25 Time 15:32 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 14:35 Sent To  
Notes
2007-10-25 14:36:59*****DENIED*****
  
 *THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN STILL NEED TO BE ADDRESSED:
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH DIXIE HIGHWAY, POST THE NUMERICAL ADDRESS(ES) ON
 THE BUILDING.AS PER WEST PALM BEACH CODE, ADDRESS
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.IF THERE REAR DOORS FOR THESE TENANT
 SPACES, 3"IN HEIGHT AND 1" IN WIDTH NUMBERS SHALL BE
 REQUIRED ON THE REAR DOORS.
  
 6.ALL REQUIRED EXIT COMPONENTS (EXIT LIGHTS,
 EMERGENCY LIGHTS), FIRE-RESISTIVE ASSEMBLIES AND
 CONSTRUCTION SHALL BE MAINTAINED.
  
 *NEW COMMENT:
  
 A.IF THIS STRUCTURE IS TO BE FIRE PROTECTED AS PER
 THE SPRINKLER AND FIRE ALARM NOTE ON SHEET A1.01,
 PROVIDE A LAYOUT OF THE FIRE ALARM/FIRE SPRINKLER
 SYSTEM FOR THIS SITE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By mawillia Date 2007-09-05 Time 14:28 Rev Time 0.00
Received By mawillia Date 2007-09-05 Time 13:43 Sent To  
Notes
2007-09-05 14:27:49*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.
  
 2.PLEASE INSERT E1.1 TO SHEET A1.01'S DRAWING LIST.
  
 3.THE ADDRESS (OR RANGE OF ADDRESSES) SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLYT WITH NFPA 241.
  
 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH DIXIE HIGHWAY, POST THE NUMERICAL ADDRESS(ES) ON
 THE BUILDING.AS PER WEST PALM BEACH CODE, ADDRESS
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.IF THERE REAR DOORS FOR THESE TENANT
 SPACES, 3"IN HEIGHT AND 1" IN WIDTH NUMBERS SHALL BE
 REQUIRED ON THE REAR DOORS.
  
 6.ALL REQUIRED EXIT COMPONENTS (EXIT LIGHTS,
 EMERGENCY LIGHTS), FIRE-RESISTIVE ASSEMBLIES AND
 CONSTRUCTION SHALL BE MAINTAINED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-09-16 Cont ID  
Sent By kstevens Date 2009-09-16 Time 08:39 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 08:39 Sent To  
Notes
2009-09-16 08:41:32SENT TO JWITMER.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 17:01 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 17:01 Sent To  
Notes
2008-10-03 17:01:53TO "COMM" BD#62

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-01 Cont ID  
Sent By adarroug Date 2008-04-01 Time 13:52 Rev Time 0.00
Received By adarroug Date 2008-04-01 Time 13:52 Sent To  
Notes
2008-04-01 13:53:08TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 08:24 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 08:24 Sent To  
Notes
2007-10-12 16:31:33TO "COMM" BD#53
2007-09-20 08:24:26WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-05 Cont ID  
Sent By mawillia Date 2007-09-05 Time 13:45 Rev Time 0.00
Received By mawillia Date 2007-07-10 Time 13:21 Sent To  
Notes
2007-07-24 09:07:05TO "COMM" BD#11
2007-07-10 13:21:20WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2008-10-08 Cont ID  
Sent By tgordon Date 2008-10-08 Time 11:12 Rev Time 0.30
Received By tgordon Date 2008-10-08 Time 11:12 Sent To  
Notes
2008-10-08 11:13:21SCOPE OF WORK CHANGED NO MECHANICAL WORK TO BE DONE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-04-08 Cont ID  
Sent By tgordon Date 2008-04-08 Time 11:42 Rev Time 0.45
Received By tgordon Date 2008-04-08 Time 11:42 Sent To  
Notes
2008-04-08 11:45:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #1 REGARDING THE ENERGY
 CALCULATIONS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-23 Cont ID  
Sent By tgordon Date 2007-10-23 Time 13:45 Rev Time 1.00
Received By tgordon Date 2007-10-23 Time 13:45 Sent To  
Notes
2007-10-23 14:30:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ENERGY CALCULATIONS ARE ON FORM 400A, SEE
 13-400.0.C.4 RENOVATED BUILDINGS MAY ONLY USE FORM B OR
 C. ALSO SEE 13-400.2.A.2 SHELL BUILDING MAY ONLY USE
 FORM B OR C. PLEASE CORRECT.
  
 2) SEE ENERGY CALCULATIONS SHOW THIRTEEN A/C SYSTEMS,
 PLANS SHOW ONLY SEVEN A/C SYSTEMS. WHEN REDOING ENERGY
 CALCULATIONS "SYSTEM REPORT" ONLY DO FOR 4805 S. DIXIE
 HWY. SUITES 105 THROUGH 109. PLEASE COORDINATE ALL
 CHANGES WITH ARCHITECT AND MECHANICAL ENGINEER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By tgordon Date 2007-07-26 Time 10:36 Rev Time 0.30
Received By tgordon Date 2007-07-26 Time 10:36 Sent To  
Notes
2007-07-26 10:53:35*** DENIED ***
 1) MECHANICAL PLAN PAGE MP-0.1 MECHANICAL NOTE #2
 STATES THE LATEST EDITION OF THE FBC, PLEASE CHANGE TO
 THE 2004 WITH 2006 REVISIONS FBC.
  
 2) PLEASE STATE ON PLANS PAGE MP-1.2 WERE THE 2" A/C
 CONDENSATE LINE WILL DISCHARGE TO.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS. 2004 FBC
 13-101.1.6 SHELL BUILDINGS.
 NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2008-10-22 Cont ID  
Sent By kstevens Date 2008-10-22 Time 06:33 Rev Time 0.00
Received By kstevens Date 2008-10-22 Time 06:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-04-14 Cont ID  
Sent By kstevens Date 2008-04-14 Time 06:30 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 16:56 Sent To  
Notes
2008-04-14 06:39:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1, OK
  
 2. OK
  
 3. SHT A2.02 SUBMIT CALCULATIONS FOR ROOF DRAINAGE PER
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND TABLES.
 SHOW THE TOTAL SQUARE FOOTAGE OF EACH ROOF AREA ALONG
 WITH 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS
 THAT AFFECT EACH AREA ADDED TO EACH ROOF AREA.--
 INDICATE THE SLOPE OF THE ROOF AND THE DIRECTION OF
 SLOPE.--NOTE INDICATES EXISTING ALUM. GUTTER. SHOW
 ALL GUTTERS, AND INDICATE THE SIZE OF THE GUTTERS.
 INDICATE THE SLOPE OF THE GUTTERS SHOWING THE HIGH
 POINTS AND THE LOW POINTS OF THE GUTTERS. TABLE 1106.6.
 --SHOW THE LOCATION OF ALL AND SIZE OF ALL
 DOWNSPOUTS.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT GUTTERS AND DOWNSPOUTS ARE
 REQUIRED ON ALL ROOF THAT HAVE AN EVE LESS THAN 6".
 DETAIL #2 SHT A7.01 SHOWS NO EVE.
 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 4. SHT A3.01 CALL OUT THE LOCATION OF ALL GUTTERS AND
 DOWNSPOUTS ON ELEVATION #3. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT GUTTERS AND DOWNSPOUTS ARE
 REQUIRED ON ALL ROOF THAT HAVE AN EVE LESS THAN 6".
 DETAIL #2 SHT A7.01 SHOWS NO EVE.
 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 **********NEW COMMENT**********
  
 1B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-24 Cont ID  
Sent By kstevens Date 2007-11-24 Time 16:09 Rev Time 0.00
Received By kstevens Date 2007-11-24 Time 16:09 Sent To  
Notes
2007-11-24 16:13:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1, OK
  
 2. OK
  
 3. SHT A2.02 SUBMIT CALCULATIONS FOR ROOF DRAINAGE PER
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND TABLES.
 SHOW THE TOTAL SQUARE FOOTAGE OF EACH ROOF AREA ALONG
 WITH 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS
 THAT AFFECT EACH AREA ADDED TO EACH ROOF AREA.--
 INDICATE THE SLOPE OF THE ROOF AND THE DIRECTION OF
 SLOPE.--NOTE INDICATES EXISTING ALUM. GUTTER. SHOW
 ALL GUTTERS, AND INDICATE THE SIZE OF THE GUTTERS.
 INDICATE THE SLOPE OF THE GUTTERS SHOWING THE HIGH
 POINTS AND THE LOW POINTS OF THE GUTTERS. TABLE 1106.6.
 --SHOW THE LOCATION OF ALL AND SIZE OF ALL
 DOWNSPOUTS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. SHT A3.01 CALL OUT THE LOCATION OF ALL GUTTERS AND
 DOWNSPOUTS ON ELEVATION #3. SECTION 106.1.1. ****NO
 RESPONSE, NOT ADDRESSED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 **********NEW COMMENT**********
  
 1B. PLEASE CORRECT THE ADDRESS ON THE APPLICATION AND
 ON THE TITLE BLOCK OF EACH SHEET. 4805 S. DIXIE HWY.
 (SEE ELECTRICAL SHEETS).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By kstevens Date 2007-08-31 Time 17:08 Rev Time 0.00
Received By kstevens Date 2007-08-31 Time 17:08 Sent To  
Notes
2007-08-31 17:42:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1, SHT A1.01 PROJECT LOCATION. WHITE OUT IS NOT
 APPROVED ON SIGNED & SEALED PLANS. SECTION 106.3.1.
 PLEASE INDICATE THE CORRECT ADDRESS ON THE PLANS.
 SECTION 106.1.1.
  
 2. SHT A1.01 EGRESS DATA STATES, "NEW ADDITION ONLY",
 BUT THE APPLICATION DESCRIPTION STATES "EXTERIOR
 IMPROVEMENTS/REROOF". ALSO MP SHEETS INDICATE PLUMBING
 WORK INSIDE. PLEASE DESCRIBE PROJECT IN DETAIL ON
 APPLICATION AS REQUIRED. SECTION 105.3.
  
 3. SHT A2.02 SUBMIT CALCULATIONS FOR ROOF DRAINAGE PER
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND TABLES.
 SHOW THE TOTAL SQUARE FOOTAGE OF EACH ROOF AREA ALONG
 WITH 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS
 THAT AFFECT EACH AREA ADDED TO EACH ROOF AREA.--
 INDICATE THE SLOPE OF THE ROOF AND THE DIRECTION OF
 SLOPE.--NOTE INDICATES EXISTING ALUM. GUTTER. SHOW
 ALL GUTTERS, AND INDICATE THE SIZE OF THE GUTTERS.
 INDICATE THE SLOPE OF THE GUTTERS SHOWING THE HIGH
 POINTS AND THE LOW POINTS OF THE GUTTERS. TABLE 1106.6.
 --SHOW THE LOCATION OF ALL AND SIZE OF ALL
 DOWNSPOUTS.
  
 4. SHT A3.01 CALL OUT THE LOCATION OF ALL GUTTERS AND
 DOWNSPOUTS ON ELEVATION #3. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-10-07 Cont ID  
Sent By kdfreema Date 2008-10-07 Time 15:29 Rev Time 0.00
Received By kdfreema Date 2008-10-07 Time 15:29 Sent To  
Notes
2008-10-07 15:32:26***PROVISO***
  
 THE PARKING LOT STRIPING DETAIL SHALL MEET THE MINIMUM
 DIMENSIONAL REQUIREMENTS AS FOUND WITHIN SECTION 94-485
 OF THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS.
 ATTACHED TO THE HARD COPY OF THIS NOTE IS THE CORRECT
 DETAIL.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-16 Cont ID  
Sent By kdfreema Date 2008-04-16 Time 10:34 Rev Time 0.00
Received By kdfreema Date 2008-04-16 Time 10:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-18 Cont ID  
Sent By kdfreema Date 2007-10-18 Time 14:33 Rev Time 0.00
Received By kdfreema Date 2007-10-18 Time 14:33 Sent To  
Notes
2007-10-18 14:38:05***FAILED***
  
 1. PLEASE NOTE THAT THE INCLUDED PARKING LOT STRIPING
 DETAIL DOES NOT CONFORM TO THE CITY OF WEST PALM BEACH
 STANDARDS. THE STRIPING AT THE FOOT OF THE SPACE IS
 REQUIRED TO BE SQUARED OFF, NOT ROUNDED AS SHOWN ON THE
 SUBMITTED DRAWINGS.
  
 2. A UNITY OF TITLE IS REQUIRED JOINING THE NORTH AND
 SOUTH PARCELS.
  
 3. THE EXTENSION OF THE PARAPET WALLS, AS SHOWN, IS NOT
 PERMITTED. AS THE BUILDING ENCROACHES INTO THE REQUIRED
 SETBACK YOU ARE LIMITED TO THE DIMENSIONS OF THE
 EXISTING BUILDING.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-07 Cont ID  
Sent By kdfreema Date 2007-08-07 Time 19:23 Rev Time 0.00
Received By kdfreema Date 2007-08-07 Time 19:26 Sent To  
Notes
2007-08-07 19:26:00***FAILED***
  
 1. AS THE WORK PROPOSED EXCEEDS THE VALUE OF THE
 STRUCTURE BY GREATER THAN 50 PERCENT, THE SITE IS
 REQUIRED TO BE BROUGHT UP TO MEET THE CURRENT
 REQUIREMENTS OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS WITH RESPECT TO LANDSCAPING, PARKING, AND
 SETBACKS.
  
 2. NO SURVEY OF THE PROPERTY WAS PROVIDED; ONE IS
 REQUIRED AND MUST BE NO OLDER THAN ONE YEAR.
  
 3. PLEASE PROVIDE A LANDSCAPE PLAN SIGNED AND SEALED BY
 A REGISTERED LANDSCAPE ARCHITECT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR AT [email protected] WITH QUESTIONS.