Plan Review Details - Permit 07070201
Plan Review Stops For Permit 07070201
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-18 Cont ID  
Sent By rmcdouga Date 2008-01-18 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2008-01-18 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By rmcdouga Date 2007-12-03 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2007-12-03 Time 16:32 Sent To  
Notes
2007-12-03 16:32:292004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) SUBMIT 2 COPIES OF THE ENERGY CALC. FORMS THAT HAVE
 BEEN SIGNED BY THE OWNER/AGENT. SEE FBC CHAPTER 13.
  
 2) REVISE THE INTERNAL WALL DETAIL AND THE INSULATION
 SCHEDULE ON SHEET A-2, WHICH SPECIFY R-19 INSULATION IN
 THE CEILING AND R-4.1 ON THE MASONRY WALLS. THE ENERGY
 CALC. FORM SUBMITTED REQUIRES A MINIMUM OF R-30 IN THE
 CEILING AND R-5 ON THE MASONRY WALLS. SEE FBC
 13-600.1.C.
  
 3) SPECIFY THE CONNECTORS/HANGERS THAT WILL BE USED TO
 ATTACH THE 2 X 10 RAFTERS TO THE LEDGER AT THE COVERED
 PORCH.
  
 4) ON SHEET A4 THE STEEL BUCKET DETAIL SPECIFIES 2- 2 X
 12P.T. AND THE FRAMING PLAN SHOWS 2- 2 X 10 . PLEASE
 CLARIFY.
  
 5) IN ADDITION TO THE FLORIDA COVERSHEET THAT WAS
 SUBMITTED FOR THE GLASS BLOCK, SUBMIT 2 COPIES OF
 INSTALLATION INSTRUCTIONS AND EVALUATION REPORTS AS
 REQUIRED BY FAC RULE 9B-72.
  
 6) ON THE NOA FOR THE ALTUSA "S" CLAY ROOF TILE SPECIFY
 THE FASTENING SYSTEM THAT WILL BE USED. CIRCLE THE ITEM
 WITH THE APPROPRIATE ATTACHMENT RESISTANCE ON THE NOA.
 FBC 106.1.2
  
 7) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS
 REQUIRED FOR ALL GLAZED OPENINGS THAT ARE NOT LARGE
 MISSLE IMPACT RESISTANT. SPECIFY THE MOUNT TYPE,
 ANCHORS, ANCHOR SPACING, SPANS, ETC. ON THE PRODUCT
 APPROVAL/NOA. SEE FBC R301.2.1.2.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By rmcdouga Date 2007-07-19 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2007-07-19 Time 17:26 Sent To  
Notes
2007-07-19 18:39:39DENIED BY BUILDING
  
 1) SUBMIT A SURVEY/SITE PLAN INDICATING THE LOCATION OF
 THE ADDITION AND THE DISTANCES TO PROPERTY LINES.
  
 2)) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 3) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC
 CHAPTER 13.
  
 4) THE DESIGN INFORMATION ON ALL OF THE SHEETS
 INCORRECTLY SPECIFY SBC INSTEAD OF FBC 2004.
  
 5) IN THE ROOF NOTES ON A5, FBC 2001 IS INCORRECTLY
 SPECIFIED INSTEAD OF FBC 2004.
  
 6) ON A3 THE FOUNDATION NOTES NEED TO BE UPDATED TO
 SPECIFY ACI 530-02 AND 630-02. WHICH ARE THE EDITIONS
 REFERENCE IN THE 2004 FBC.
  
 7) THE GLASS BLOCK NOTES ON SHEET A2 INCORRECTLY
 SPECIFY SFBC . SEE FBC 2110.
  
 8)R322.1 REQUIRES AT LEAST ONE BATHROOM WITH A DOOR
 THAT HAS A 29" CLEAR OPENING MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE OPPOSITE STOP WITH THE DOOR OPEN 90
 DEGREES.
  
 9) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 10) SPECIFY THE CEILING FINISH THAT WILL BE USED AT THE
 COVERED PORCH.
  
 11) SUBMIT SIGNED AND SEALED GRAVITY LOAD CALCULATIONS
 FOR THE DOUBLE 2 X 10 BEAM CARRYING THE COVERED PORCH
 CEILING/RAFTERS.
  
 12) SPECIFY THE LENGTH/EMBED DEPTH OF THE 5/8" DIAMETER
 ANCHORS FOR THE COVERED PORCH LEDGER.
  
 13) SPECIFY THE CONNECTORS/HANGERS THAT WILL BE USED TO
 ATTACH THE 2 X 10 RAFTERS TO THE COVERED PORCH LEDGER.
  
 14)REVISE THE ROOF SHEATHING FASTENING SPECIFICATIONS
 TO COMPLY WITH FBC R803.2.3.1 WHICH REQURES 8D RING
 SHANK NAILS IN ALL ROOF ZONES.
  
 15)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 16)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 17) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE GLASS
 BLOCK.
  
 18) THE NOA FOR THE ALTUSA "S" CLAY ROOF TILE HAS BEEN
 SUPERSEDED BY NOA NO. 05-0901.06. PLEASE SUBMIT THE
 CURRENT NOA. THIS PRODUCT DOES NOT HAVE A STATE PRODUCT
 APPROVAL. HOWEVER, A CURRENT MIAMI-DADE NOA IS
 ACCEPTABLE.
  
 19)A FLORIDA COVERSHEET WAS SUBMITTED FOR MONIER ROOF
 TILE WITHOUT THE INSTALLATION INSTRUCTIONS OR
 EVALUATION REPORT. PLEASE CLARIFY. ONLY SUBMIT THE
 PRODUCT APPROVAL FOR THE ROOF TILE THAT WILL BE
 INSTALLED.
  
 20) THE NOA FOR THE TRACO SINGLE HUNG WINDOWS HAS BEEN
 REVISED BY NOA NO. 05-0930.03. SUBMIT THE NEW NOA.
  
 21) THE VALUE OF THE PROJECT HAS BEEN INCREASED TO
 $29312.00. ADDITIONAL FEES ARE DUE.
  
 22) IF THE SHEETS THAT HAVE THE COUNTY IMPACT FEE STAMP
 ARE REVISED, RETURN THEM WITH THE RESUBMITTED PLANS OR
 THE NEW PLANS WILL HAVE TO BE RESTAMPED BY THE COUNTY.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-08 Cont ID  
Sent By btrobaug Date 2008-01-08 Time 07:55 Rev Time 0.00
Received By btrobaug Date 2008-01-08 Time 07:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-15 Cont ID  
Sent By btrobaug Date 2007-11-15 Time 07:17 Rev Time 0.00
Received By btrobaug Date 2007-11-15 Time 06:48 Sent To P
Notes
2007-11-15 07:17:26 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS ARE THE SAME AS THE PREVIOUS REVIEW . AN
 ELECTRICAL PERMIT WAS APPLIED FOR UNDER THE
 OWNER/BUILDER STATUTE 489, THEREFORE THE NOTE ON SHEET
 A-2 REGARDING THE "CONTRACTOR SHALL SUBMIT ELECTRICAL
 LAYOUT" IS IRRELEVANT. COMMENTS MUST BE ADDRESSED. SEE
 FS 553.80(2)(B) ATTACHED WITH COMMENT SHEET.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). THE ONE ON THE PLAN DOES
 NOT COMPLY WITH 210.52(D) FOR SPACING REQUIREMENTS.
 ALSO PLEASE NOTE 210.(C)(3) COMPLIANCE ON THE PLAN.
  
 2} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. SHOW
 LOCATION ON PLANS.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE ENGINEER THAT SEALED THE
 ELECTRICAL PLAN STATES RESPONSIBILITY FOR STUCTURAL
 ONLY AND THEREFORE NO ONE HAS TAKEN RESPONSIBILITY FOR
 THE ELECTRICAL PLAN.
  
 4} THE LUMINAIRE SHOWN OVER THE TUB MUST COMPLY WITH
 410.4(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By btrobaug Date 2007-07-13 Time 09:22 Rev Time 0.00
Received By btrobaug Date 2007-07-13 Time 06:50 Sent To M
Notes
2007-07-13 09:22:36 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). THE ONE ON THE PLAN DOES
 NOT COMPLY WITH 210.52(D) FOR SPACING REQUIREMENTS.
 ALSO PLEASE NOTE 210.(C)(3) COMPLIANCE ON THE PLAN.
  
 2} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. SHOW
 LOCATION ON PLANS.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE ENGINEER THAT SEALED THE
 ELECTRICAL PLAN STATES RESPONSIBILITY FOR STUCTURAL
 ONLY AND THEREFORE NO ONE HAS TAKEN RESPONSIBILITY FOR
 THE ELECTRICAL PLAN.
  
 4} THE LUMINAIRE SHOWN OVER THE TUB MUST COMPLY WITH
 410.4(D).
  
 5} THE REFERENCE TO THE "SBC" IN THE KEYED NOTES, ALL
 SHEETS, DOES NOT APPLY AS THAT CODE IS NO LONGER USED.
 REMOVE FROM PLANS TO AVOID CONFUSION IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 14:33 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 14:33 Sent To Z
Notes
2008-01-04 14:33:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 10:08 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 10:08 Sent To Z
Notes
2007-11-08 10:09:09TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-19 Cont ID  
Sent By rmcdouga Date 2007-07-19 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2007-07-10 Time 15:41 Sent To  
Notes
2007-07-10 15:41:10TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-13 Cont ID  
Sent By tgordon Date 2007-07-13 Time 14:22 Rev Time 0.20
Received By tgordon Date 2007-07-13 Time 14:22 Sent To P
Notes
2007-07-13 14:22:58NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By jleech Date 2007-12-03 Time 08:06 Rev Time 0.00
Received By jleech Date 2007-12-03 Time 08:05 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-07-18 Cont ID  
Sent By jleech Date 2007-07-18 Time 08:16 Rev Time 0.00
Received By jleech Date 2007-07-18 Time 08:12 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-07 Cont ID  
Sent By choops Date 2008-01-07 Time 15:11 Rev Time 0.00
Received By choops Date 2008-01-07 Time 15:11 Sent To E
Notes
2008-01-07 15:17:32***APPROVED - RESUB #2***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-14 Cont ID  
Sent By choops Date 2007-11-14 Time 10:04 Rev Time 0.00
Received By choops Date 2007-11-14 Time 10:04 Sent To E
Notes
2007-11-14 10:06:56***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 ADDITION TO THE PROPERTY LINES.NOTE:MUST BE A
 MINIMUM OF 12.5' TO THE SOUTH PROPERTY LINE, MUST BE A
 MINIMUM OF 11' TO THE EAST PROPERTY LINE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By choops Date 2007-07-11 Time 14:06 Rev Time 0.00
Received By choops Date 2007-07-11 Time 14:06 Sent To E
Notes
2007-07-11 14:12:12***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF AN UPDATED SURVEY
 (WITHIN THE LAST YEAR) ACCURATELY REFLECTING WHAT IS ON
 THE SITE.
  
 2)SHOW SCOPE OF WORK ON BOTH SURVEYS WITH DIMENSIONS
 AND SETBACK DIMENSIONS FROM PROPOSED ADDITION TO THE
 PROPERTY LINES.
  
 3)PROVIDE ELEVATION DIMENSION FROM GRADE TO THE
 MIDPOINT OF THE ROOF'S PITCH (OF THE PROPOSED
 ADDITION)
  
 4)INDICATE OVERHANG DIMENSIONS FROM WALL TO THE
 OUTERMOST POINT OF THE ROOF.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720