| Plan Review Stops For Permit 07070169 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-08-25 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-08-25 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-08-25 |
Time |
08:49 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-08-11 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-08-11 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-08-11 |
Time |
12:03 |
Sent To |
PC |
|
| Notes |
| 2007-08-11 12:31:08 | | | | | | | DENIED | | | | | | 1)PROVIDE THE CORRECT INSULATION R- VALUES ON THE | | | DRAWINGS TO MATCH THE CREDITS TAKEN ON THE ENERGY | | | CALC'S R-30 CEILING, R-11 FRAMED WALL BETWEEN | | | CONDITIONED AND UNCONDITIONED SPACES, ETC. | | | | | | 2)THE 1X HEAVY MULLION PRODUCT APPROVAL WILL NOT MEET | | | THE PRESSURE REQUIREMENTS FOR THE LARGE LIVINGROOM | | | WINDOW. THE 2X6 MULLION UNDER THE SAME FL# IN 2X HEAVY | | | WALL WILL MEET YOUR PRESSURES FOR AN 8'-0" TRIBUTARY | | | WIDTH AND 12'-0" OPENING HEIGHT. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-21 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-07-21 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-07-21 |
Time |
14:45 |
Sent To |
PC |
|
| Notes |
| 2007-07-21 15:19:32 | | | | | | | DENIED | | | | | | 1)DRAWINGS TO COMPLY WITH THE LATEST CODE, PLACE NOTE | | | ON PLANS THAT THEY CONFORM TO THE 2004 FLORIDA BUILDING | | | CODE WITH 2006 REVISIONS | | | | | | 2)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE | | | PROPOSED BUILDING, SERVICE PADS, DRIVEWAY, APPROACH, | | | ETC. WITH ALL SIDE AND REAR SETBACKS | | | | | | 3)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SETS OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL (561) | | | 233-5025 FOR MORE | | | INFORMATION. | | | | | | 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* | | | | | | 5)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON | | | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER | | | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE | | | ADDED TO THE PERMIT APPLICATION FEES | | | | | | NOTE: FEES ARE DUE IN THE AMOUNT OF $ 2013.52FOR | | | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS | | | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW | | | | | | 6)PROVIDE LOCATION (ADDRESS) ON THE DRAWINGS PER | | | 106.1.1 FBC* | | | | | | 7)OWNER INFORMATION ON PERMIT APPLICATION DO NOT | | | MATCH CITY SYSTEM OR PAPA PLEASE PROVIDE DEED TO PERMIT | | | CLERK TO CHANGE OWNER INFO | | | | | | 8)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN | | | COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. | | | | | | 9)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS | | | REQUIRED PER R807.1 FBC RES | | | | | | 10)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE | | | USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC FOR | | | MIN BEARING | | | | | | 11)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 | | | FBC. BE SURE THAT THEY ARE SIGNED AND | | | DATED BY PREPARER AND OWNER/AGENT PRIOR | | | TO SUBMITTAL | | | | | | 12)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER | | | R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES | | | | | | 13)PROVIDE ROOF VENTILATION ON DRAWINGS THAT COMPLIES | | | WITH R806.1 & 806.2 FBC RES. | | | | | | 14)SUBMIT ENGINEERED TRUSS DRAWINGS THAT | | | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR | | | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD | | | | | | 15)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | 16)PROVIDE MEAN ROOF HEIGHT ON DRAWINGS | | | | | | 17)PROVIDE DESIGN PRESSURES FOR THE GARAGE DOOR | | | OPENINGS ON DRAWINGS | | | | | | 18)THE FLORIDA PRODUCT APPROVAL PAGES FOR THE BERMUDA | | | ROOF TILES ARE INCORRECT FOR THE MIAMI-DADE REPORT THAT | | | WAS SUBMITTED THE CORRECT FL# IS 7804 | | | | | | 19)PROVIDE PRODUCT APPROVALS FOR THE CASTCRETE | | | LINTELS AND PGT MULLIONS | | | | | | 20)PER R803.2.3.1 FBC RES. 8D NAILS FOR THE | | | ATTACHEMENT OF ROOF SHEATHING SHALL BE RING SHANK, | | | PLEASE CHANGE NOTE ON THE ROOF NAILING DIAGRAM TO | | | INDICATE THIS | | | | | | 21)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING, | | | ELECTRICAL AND MECHANICAL AND ROOFING | | | | | | REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF | | | NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY | | | FOR REFERENCE | | | | | | NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006 | | | AMENDMENTS | | | FBC* = WEST PALM BEACH ADMINISTRATIVE | | | AMENDMENTS TO FBC | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | FBC RES. = FLORIDA BUILDING CODE | | | RESIDENTIAL 2004 W/2006 AMENDMENTS | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2008-02-11 |
Time |
16:40 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2008-02-11 |
Time |
16:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-02-08 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-08-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-17 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-17 |
Time |
16:42 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-08 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-07 |
Time |
17:56 |
Sent To |
P |
|
| Notes |
| 2007-08-08 08:07:23 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH | | | THE FOLLOWING: | | | | | | 1} A SMOKE ALARM MUST BE INSTALLED OUTSIDE BEDROOM #4 | | | TO COMPLY WITH THE REQUIREMENT "OUTSIDE EACH SEPARATE | | | SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE | | | BEDROOMS." R313.1.1 FBC, 2004 REVISED 2006. | | | | | | ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 | | | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID | | | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE | | | LOCATIONS OF THE SOUNDING DEVICES. | | | | | | 2} THE DISCONNECTS FOR CONDENSERS #1 & #2 DO NOT MEET | | | THE CLEARANCE REQUIREMENTS OF 110.26, 2005 NEC. | | | | | | 3} PANEL "A", CIRCUIT #10, #12 CONDUCTOR ON A60 AMP | | | CIRCUIT BREAKER IS IN VIOLATION OF 310.16 NEC. | | | | | | 4} PANEL "A", CIRCUIT #16, #14 CONDUCTOR ON 20 AMP | | | CIRCUIT BREAKER, VIOLATION OF 310.16 NEC. | | | | | | THE FOLLOWING , ALTHOUGH NOT VIOLATIONS WILL NEED TO BE | | | REVISED IF NOT ACTUALLY INTENDED TO BE INSTALLED: PANEL | | | "A"CIRCUITS 9 & 11, #10 CONDUCTORS, 20 AMP BREAKERS. | | | PANEL "B", CIRCUIT #6, #6 CONDUCTOR, WHICH WON'T | | | PHYSICALLY FIT, ON A 20 AMP BREAKER. CIRCUIT #10, #10 | | | WIRE ON A 20 AMP BREAKER, CIRCUIT #'S 18, 23, 25, 26 & | | | 29 ALL HAVE #12 CONDUCTORS ON15 AMP CIRCUIT BREAKERS. | | | CIRCUIT #5 IS LISTED AS A #6 CONDUCTOR ON A 20 AMP | | | BREAKER, CIRCUIT #9, #10 WIRE, 20 AMP BREAKER, CIRCUIT | | | #13, #8 WIRE, 20 AMP BREAKER, CIRCUIT #17, #10 WIRE, | | | 20AMP BREAKER. THESE ITEMS NEED TO BE CLARIFIED BY THE | | | DESIGNER OF RECORD TO VERIFY HIS DESIGN INTENTIONS | | | PRIOR TO BEING INCORRECTLY INSTALLED IN THE FIELD. | | | | | | NOTE: | | | THE GFI RECEPTACLES PLACED IN THE ISLAND BETWEEN THE | | | FAMILY ROOM AND THE KITCHEN MAY NOT BE IN COMPLIANCE | | | WITH 210.52(C)(5) IF UNDER THE OVERHANGING COUNTERTOP | | | THAT EXTENDS 6" OR MORE, SEE THE EXCEPTION, THAT | | | ARTICLE. | | | | | | PLEASE MAKE THE CORRECTIONS NEEDED FOR CODE COMPLIANCE | | | AND TO SHOW DESIGN INTENTION, AND RESUBMIT FOR REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-13 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-13 |
Time |
12:45 |
Sent To |
M |
|
| Notes |
| 2007-07-13 15:49:27 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE ELECTRICAL RISER INDICATES 150 AMP MAIN BREAKERS | | | IN THE DISCONNECTS AND 150 AMP PANELS. THE LOAD | | | CALCULATIONS FOR EACH PANEL EXCEEDS THAT AMPERAGE. | | | 220.40 NEC. ALSO THE RATING FOR THE PANELS SCHEDULES AT | | | 200 AMP, DO NOT CORRELATE WITH THE RISER. PROVIDE LOAD | | | CALCULATIONS PER 220 SECTION I, STANDARD CALCULATION, | | | IF DERATING THE NEUTRAL, OR 220.SECTION III, OPTIONAL | | | CALCULATIONS. | | | | | | 2} THERE ARE FEEDS TO THE POOL HEATER, PUMP AND LIGHTS | | | FROM PANEL "B", THE RISER FEEDS A 60 AMP POOL PANEL | | | FROM PANEL "B", WITH THOSE CIRCUITS LISTED IN THAT | | | PANEL.CORRELATE THE PANELS. | | | | | | 3} THE POOL PANEL LISTS THE HEATER ON A 20 AMP CIRCUIT, | | | PANEL "B" LISTS THE HEATER ON A 50 AMP CIRCUIT. | | | CORRELATE SAME. | | | | | | 4} CIRCUITS 9-11 PANEL "B", WATER HEATER LISTS #10 WIRE | | | ON A 40 AMP BREAKER. SEE 310.16. | | | | | | 5} CIRCUITS 10-12, ELEVATOR, SAME AS ABOVE. | | | | | | 6} CIRCUIT #29, PANEL "B", MASTER BATH GFCI MUST BE ON | | | A 20 BREAKER PER 210.11(C)(3). | | | | | | 7} THERE ARE 4 A/C SYSTEMS ON THE PANEL SCHEDULE, BUT | | | ONLY 3 LOCATED ON THE PLAN. | | | | | | 8} PER 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY | | | DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS | | | AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET | | | ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ | | | 2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND | | | BACK OF THE DWELLING. SEE ONE MISSING IN FRONT. | | | | | | 9}.SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 | | | RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON PLANS | | | | | | 10} 210.52(H) HALLWAYS IN DWELLING UNITS, HALLWAYS OF | | | 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE | | | RECEPTACLE OUTLET. SEE HALLWAY AT BEDROOM #3 AND | | | LAUNDRY. | | | | | | 11} AT LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET | | | SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE | | | EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE | | | LEVEL ACCESS. SEE DOORS IN THE DINING ROOM. | | | 210.70(A)(2)(B). | | | | | | 12} THERE ARE "THEATER" LIGHTS AND RECEPTACLES LISTED | | | ON THE PANEL SCHEDULE, BUT NO ROOM DESIGNATED FOR THAT | | | PURPOSE. PLEASE CLARIFY. | | | | | | 13} LOCATE THE ELEVATOR ON THE PLANS, CIRCUIT 10-12 | | | PANEL "B". | | | | | | 14} THE GFI RECEPTACLE LOCATED IN BATH #4 EXCEEDS THE | | | 3' RECEPTACLE SPACING REQUIRED BY 210.52(D) | | | | | | 15} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) | | | AND 210.52(A)(2) BEDROOM #3. | | | | | | 16} LOCATE THE POOL AND "AQUA LOGIC" PANELS ON THE | | | PLAN. | | | | | | NOTE: SHEETS A9 AND A10 ARE MISSING, PLEASE INCLUDE | | | WHEN RESUBMITTING. | | | | | | FLORIDA BUILDING CODE-2004. | | | | | | PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE | | | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE | | | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE | | | ARTICLE. | | | | | | SEE 13-606.1.ABC.1.2.3 FBC FOR REQUIREMENTS FOR | | | RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT | | | ABUT AN ATTIC SPACE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-15 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-15 |
Time |
11:08 |
Sent To |
E |
|
| Notes |
| 2007-08-15 11:08:48 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-07-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-30 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-30 |
Time |
13:14 |
Sent To |
Z |
|
| Notes |
| 2007-07-30 13:14:31 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-07-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-10 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2007-07-10 09:34:54 | TO "SFR" "E" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-15 |
Time |
15:17 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-08-15 |
Time |
15:17 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-08-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-09 |
Time |
08:01 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2007-08-09 |
Time |
08:00 |
Sent To |
B |
|
| Notes |
| 2007-08-09 08:31:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | | | *** DENIED *** | | | 1) MECHANICAL PLANS SUBMITTED GRAYED OUT AREAS AND | | | OTHER DARKEN LINES THAT MAKE IT DIFFICULT TO SEE ALL | | | MECHANICAL DETAIL ON THE PLAN THEIR FOR SOME ITEMS MAY | | | BE MISSED ON THIS PLAN REVIEW. CONSTRUCTION DOCUMENTS | | | SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC 106.1.1. | | | PLEASE CORRECT. | | | | | | 2) MECHANICAL PLANS (EQUIPMENT INFORMATION) LISTS TWO | | | A/C SYSTEMS AS #1, PLEASE CORRECT. | | | | | | 3) AS NOTED IN LAST REVIEW 7-16-07 NOTE #6, PLEASE SHOW | | | ON MECHANICAL PLANS COMBUSTION AIR CALCULATIONS FOR GAS | | | CLOTHES DRYER IN LAUNDRY ROOM AND PROVIDE COMBUSTION | | | AIR AND MAKE-UP AIR IF REQUIRED, SEE 2004 FBC/R G2407.1 | | | (304.1). | | | | | | 4) SHOW ON MECHANICAL PLAN THE CLOTHES DRYER VENT AND | | | STATE WERE IT WILL VENT TO, SEE 2004 FBC/R R303.4.2. | | | | | | 5) SHOW ON MECHANICAL PLAN THE CFM'S. AT ALL BATHROOM | | | EXHAUST FANS, SEE 2004 FBC/R R303.3. | | | | | | 6) THE ELECTRICAL PLAN SHOWS A BATHROOM EXHAUST FAN IN | | | THE MASTER BATH NEAR THE TUB, AS THE WINDOWS APPEAR TO | | | BE FIXED AT THAT LOCATION SEE 2004 FBC/R R303.3 AND | | | PLEASE CORRECT PLANS SO THEY COINCIDE. | | | | | | 7) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLAN SHOWING | | | A/C DUCTS THAT NEED TO BE SIZED. | | | | | | 8) MECHANICAL PLAN DOES NOT SHOW WHICH AIR HANDLER AND | | | CONDENSER UNIT IS #1, PLEASE CORRECT. | | | | | | 9) PLEASE ADD A SECOND COPY OF THE INSTALLATION | | | INSTRUCTIONS FOR THE UNVENTED GAS LOG HEATER, AS ONLY | | | ONE WAS SUBMITTED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-16 |
Time |
08:47 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-07-16 |
Time |
08:47 |
Sent To |
P |
|
| Notes |
| 2007-07-16 09:23:39 | *** DENIED *** | | | 1) PLEASE STATE ON PLANS THE BUILDING CODE BEING USED | | | FOR THIS PROJECT, PRESENTLY 2004 FBC W/ 2006 REVISIONS, | | | SEE 2004 FBC 106.1.1. | | | | | | 2) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK, SEE | | | 2004 FBC 106.1.1. | | | | | | 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS FOR REVIEW, SEE | | | 2004 FBC CITY WPB AMEND. 106.3.5.4 (10). | | | | | | 4) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-101.2.1. | | | | | | 5) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 | | | FBC 13-607.1.ABC.1. | | | | | | 6) SHOW ON MECHANICAL PLAN COMBUSTION AIR CALCULATION | | | FOR GAS VENT FREE FIREPLACE IN CLUB ROOM, AND GAS | | | CLOTHES DRYER IN LAUNDRY ROOM. PROVIDE COMBUSTION AND | | | MAKE-UP AIR IF REQUIRED, SEE 2004 FBC/R G2407.1 | | | (304.1). | | | | | | 7) ELECTRICAL PLANS PANEL LISTS 4 A/C SYSTEMS BUT PLANS | | | ONLY SHOW 3 A/C SYSTEMS, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-08-08 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-08-08 |
Time |
13:06 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-20 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-20 |
Time |
09:14 |
Sent To |
B |
|
| Notes |
| 2007-07-20 09:22:13 | DENIED; | | | RISER DIAGRAM DOES NOT MATCH FLOOR PLAN. | | | A) 9-W/C'S ON RISER DIAGRAM 7- ON PLAN | | | B) MISSING BIDET'S | | | C) MISSING AUTO MATIC CLOTHES WASHER. | | | D) LAUNDRY TUB TO DISCHARGE DOWN STREAM OF | | | BATHROOM GROUP. SEC. 909.1 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-06 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-06 |
Time |
16:11 |
Sent To |
PC |
|
| Notes |
| 2008-03-06 16:12:16 | ***APPROVED - LANDSCAPE PLAN SUBMITTAL*** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-31 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-31 |
Time |
11:23 |
Sent To |
E |
|
| Notes |
| 2007-07-31 11:26:37 | PROVISO:1)1000 SQ.FT. MINIMUM TO REMAIN LANDSCAPE | | | WITHIN FRONT YARD.2)POOL / POOL EQUIPMENT / | | | GENERATOR TO BE ON SEPERATE PERMIT AS INDICATED ON SITE | | | PLAN. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-11 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-11 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-11 |
Time |
09:45 |
Sent To |
E |
|
| Notes |
| 2007-07-11 09:54:31 | ***FAILED*** | | | | | | | | | 1)SCOPE OF WORK NOT CLEAR.DRIVEWAY INCLUDED UNDER | | | THIS PERMIT?IF SO, INCLUDE ALL DIMENSIONS AND SQUARE | | | FOOTAGE.POOL EQUIPMENT/HEATER AND POOL/SPA SHOWN ON | | | PLANS...REMOVE IF NOT INCLUDED IN SCOPE OF WORK FOR | | | THIS PROJECT.GENERATOR SHOWN ON PLANS...REMOVE IF NOT | | | INCLUDED IN SCOPE OF WORK FOR THIS PROJECT.(IF | | | POOL/EQUIPMENT AND GENERATOR IS INCLUDED PROVIDE | | | DETAILS AND SETBACK DIMENSIONS FROM PROPERTY LINES. | | | | | | 2)PLEASE PROVIDE SETBACK DIMENSIONS FROM PROPOSED | | | A/C EQUIPMENT TO THE PROPERTY LINES. | | | | | | 3)PROVIDE ALL OVERHANG DIMENSIONS FROM THE WALL TO | | | THE OUTERMOST POINT OF THE ROOF.NOTE:OVERHANGS MAY | | | NOT ENCROACH MORE THAN 3' INTO ANY REQUIRED SETBACK. | | | | | | 4)PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE WITH | | | SECTION 94-442 OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|