Plan Review Details - Permit 07070169
Plan Review Stops For Permit 07070169
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-25 Cont ID  
Sent By amorse Date 2007-08-25 Time 08:49 Rev Time 0.00
Received By amorse Date 2007-08-25 Time 08:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-11 Cont ID  
Sent By amorse Date 2007-08-11 Time 12:03 Rev Time 0.00
Received By amorse Date 2007-08-11 Time 12:03 Sent To PC
Notes
2007-08-11 12:31:08 
  
 DENIED
  
 1)PROVIDE THE CORRECT INSULATION R- VALUES ON THE
 DRAWINGS TO MATCH THE CREDITS TAKEN ON THE ENERGY
 CALC'S R-30 CEILING, R-11 FRAMED WALL BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES, ETC.
  
 2)THE 1X HEAVY MULLION PRODUCT APPROVAL WILL NOT MEET
 THE PRESSURE REQUIREMENTS FOR THE LARGE LIVINGROOM
 WINDOW. THE 2X6 MULLION UNDER THE SAME FL# IN 2X HEAVY
 WALL WILL MEET YOUR PRESSURES FOR AN 8'-0" TRIBUTARY
 WIDTH AND 12'-0" OPENING HEIGHT.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-21 Cont ID  
Sent By amorse Date 2007-07-21 Time 14:45 Rev Time 0.00
Received By amorse Date 2007-07-21 Time 14:45 Sent To PC
Notes
2007-07-21 15:19:32 
  
 DENIED
  
 1)DRAWINGS TO COMPLY WITH THE LATEST CODE, PLACE NOTE
 ON PLANS THAT THEY CONFORM TO THE 2004 FLORIDA BUILDING
 CODE WITH 2006 REVISIONS
  
 2)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING, SERVICE PADS, DRIVEWAY, APPROACH,
 ETC. WITH ALL SIDE AND REAR SETBACKS
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL (561)
 233-5025 FOR MORE
 INFORMATION.
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 5)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 2013.52FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 6)PROVIDE LOCATION (ADDRESS) ON THE DRAWINGS PER
 106.1.1 FBC*
  
 7)OWNER INFORMATION ON PERMIT APPLICATION DO NOT
 MATCH CITY SYSTEM OR PAPA PLEASE PROVIDE DEED TO PERMIT
 CLERK TO CHANGE OWNER INFO
  
 8)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 9)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES
  
 10)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC FOR
 MIN BEARING
  
 11)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 12)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES
  
 13)PROVIDE ROOF VENTILATION ON DRAWINGS THAT COMPLIES
 WITH R806.1 & 806.2 FBC RES.
  
 14)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 15)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 16)PROVIDE MEAN ROOF HEIGHT ON DRAWINGS
  
 17)PROVIDE DESIGN PRESSURES FOR THE GARAGE DOOR
 OPENINGS ON DRAWINGS
  
 18)THE FLORIDA PRODUCT APPROVAL PAGES FOR THE BERMUDA
 ROOF TILES ARE INCORRECT FOR THE MIAMI-DADE REPORT THAT
 WAS SUBMITTED THE CORRECT FL# IS 7804
  
 19)PROVIDE PRODUCT APPROVALS FOR THE CASTCRETE
 LINTELS AND PGT MULLIONS
  
 20)PER R803.2.3.1 FBC RES. 8D NAILS FOR THE
 ATTACHEMENT OF ROOF SHEATHING SHALL BE RING SHANK,
 PLEASE CHANGE NOTE ON THE ROOF NAILING DIAGRAM TO
 INDICATE THIS
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICAL AND MECHANICAL AND ROOFING
  
 REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF
 NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY
 FOR REFERENCE
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-02-11 Cont ID  
Sent By jleahy Date 2008-02-11 Time 16:40 Rev Time 0.45
Received By jleahy Date 2008-02-11 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2008-02-08 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-17 Cont ID  
Sent By btrobaug Date 2007-08-17 Time 16:58 Rev Time 0.00
Received By btrobaug Date 2007-08-17 Time 16:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-08 Cont ID  
Sent By btrobaug Date 2007-08-08 Time 08:07 Rev Time 0.00
Received By btrobaug Date 2007-08-07 Time 17:56 Sent To P
Notes
2007-08-08 08:07:23 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} A SMOKE ALARM MUST BE INSTALLED OUTSIDE BEDROOM #4
 TO COMPLY WITH THE REQUIREMENT "OUTSIDE EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS." R313.1.1 FBC, 2004 REVISED 2006.
  
 ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 2} THE DISCONNECTS FOR CONDENSERS #1 & #2 DO NOT MEET
 THE CLEARANCE REQUIREMENTS OF 110.26, 2005 NEC.
  
 3} PANEL "A", CIRCUIT #10, #12 CONDUCTOR ON A60 AMP
 CIRCUIT BREAKER IS IN VIOLATION OF 310.16 NEC.
  
 4} PANEL "A", CIRCUIT #16, #14 CONDUCTOR ON 20 AMP
 CIRCUIT BREAKER, VIOLATION OF 310.16 NEC.
  
 THE FOLLOWING , ALTHOUGH NOT VIOLATIONS WILL NEED TO BE
 REVISED IF NOT ACTUALLY INTENDED TO BE INSTALLED: PANEL
 "A"CIRCUITS 9 & 11, #10 CONDUCTORS, 20 AMP BREAKERS.
 PANEL "B", CIRCUIT #6, #6 CONDUCTOR, WHICH WON'T
 PHYSICALLY FIT, ON A 20 AMP BREAKER. CIRCUIT #10, #10
 WIRE ON A 20 AMP BREAKER, CIRCUIT #'S 18, 23, 25, 26 &
 29 ALL HAVE #12 CONDUCTORS ON15 AMP CIRCUIT BREAKERS.
 CIRCUIT #5 IS LISTED AS A #6 CONDUCTOR ON A 20 AMP
 BREAKER, CIRCUIT #9, #10 WIRE, 20 AMP BREAKER, CIRCUIT
 #13, #8 WIRE, 20 AMP BREAKER, CIRCUIT #17, #10 WIRE,
 20AMP BREAKER. THESE ITEMS NEED TO BE CLARIFIED BY THE
 DESIGNER OF RECORD TO VERIFY HIS DESIGN INTENTIONS
 PRIOR TO BEING INCORRECTLY INSTALLED IN THE FIELD.
  
 NOTE:
 THE GFI RECEPTACLES PLACED IN THE ISLAND BETWEEN THE
 FAMILY ROOM AND THE KITCHEN MAY NOT BE IN COMPLIANCE
 WITH 210.52(C)(5) IF UNDER THE OVERHANGING COUNTERTOP
 THAT EXTENDS 6" OR MORE, SEE THE EXCEPTION, THAT
 ARTICLE.
  
 PLEASE MAKE THE CORRECTIONS NEEDED FOR CODE COMPLIANCE
 AND TO SHOW DESIGN INTENTION, AND RESUBMIT FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By btrobaug Date 2007-07-13 Time 17:18 Rev Time 0.00
Received By btrobaug Date 2007-07-13 Time 12:45 Sent To M
Notes
2007-07-13 15:49:27 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ELECTRICAL RISER INDICATES 150 AMP MAIN BREAKERS
 IN THE DISCONNECTS AND 150 AMP PANELS. THE LOAD
 CALCULATIONS FOR EACH PANEL EXCEEDS THAT AMPERAGE.
 220.40 NEC. ALSO THE RATING FOR THE PANELS SCHEDULES AT
 200 AMP, DO NOT CORRELATE WITH THE RISER. PROVIDE LOAD
 CALCULATIONS PER 220 SECTION I, STANDARD CALCULATION,
 IF DERATING THE NEUTRAL, OR 220.SECTION III, OPTIONAL
 CALCULATIONS.
  
 2} THERE ARE FEEDS TO THE POOL HEATER, PUMP AND LIGHTS
 FROM PANEL "B", THE RISER FEEDS A 60 AMP POOL PANEL
 FROM PANEL "B", WITH THOSE CIRCUITS LISTED IN THAT
 PANEL.CORRELATE THE PANELS.
  
 3} THE POOL PANEL LISTS THE HEATER ON A 20 AMP CIRCUIT,
 PANEL "B" LISTS THE HEATER ON A 50 AMP CIRCUIT.
 CORRELATE SAME.
  
 4} CIRCUITS 9-11 PANEL "B", WATER HEATER LISTS #10 WIRE
 ON A 40 AMP BREAKER. SEE 310.16.
  
 5} CIRCUITS 10-12, ELEVATOR, SAME AS ABOVE.
  
 6} CIRCUIT #29, PANEL "B", MASTER BATH GFCI MUST BE ON
 A 20 BREAKER PER 210.11(C)(3).
  
 7} THERE ARE 4 A/C SYSTEMS ON THE PANEL SCHEDULE, BUT
 ONLY 3 LOCATED ON THE PLAN.
  
 8} PER 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS
 AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/
 2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND
 BACK OF THE DWELLING. SEE ONE MISSING IN FRONT.
  
 9}.SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON PLANS
  
 10} 210.52(H) HALLWAYS IN DWELLING UNITS, HALLWAYS OF
 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET. SEE HALLWAY AT BEDROOM #3 AND
 LAUNDRY.
  
 11} AT LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE
 EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE
 LEVEL ACCESS. SEE DOORS IN THE DINING ROOM.
 210.70(A)(2)(B).
  
 12} THERE ARE "THEATER" LIGHTS AND RECEPTACLES LISTED
 ON THE PANEL SCHEDULE, BUT NO ROOM DESIGNATED FOR THAT
 PURPOSE. PLEASE CLARIFY.
  
 13} LOCATE THE ELEVATOR ON THE PLANS, CIRCUIT 10-12
 PANEL "B".
  
 14} THE GFI RECEPTACLE LOCATED IN BATH #4 EXCEEDS THE
 3' RECEPTACLE SPACING REQUIRED BY 210.52(D)
  
 15} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1)
 AND 210.52(A)(2) BEDROOM #3.
  
 16} LOCATE THE POOL AND "AQUA LOGIC" PANELS ON THE
 PLAN.
  
 NOTE: SHEETS A9 AND A10 ARE MISSING, PLEASE INCLUDE
 WHEN RESUBMITTING.
  
 FLORIDA BUILDING CODE-2004.
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.
  
 SEE 13-606.1.ABC.1.2.3 FBC FOR REQUIREMENTS FOR
 RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT
 ABUT AN ATTIC SPACE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-15 Cont ID  
Sent By adarroug Date 2007-08-15 Time 11:08 Rev Time 0.00
Received By adarroug Date 2007-08-15 Time 11:08 Sent To E
Notes
2007-08-15 11:08:48TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 13:14 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 13:14 Sent To Z
Notes
2007-07-30 13:14:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-21 Time   Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 09:34 Sent To  
Notes
2007-07-10 09:34:54TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-15 Cont ID  
Sent By tgordon Date 2007-08-15 Time 15:17 Rev Time 0.30
Received By tgordon Date 2007-08-15 Time 15:17 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-09 Cont ID  
Sent By tgordon Date 2007-08-09 Time 08:01 Rev Time 1.00
Received By tgordon Date 2007-08-09 Time 08:00 Sent To B
Notes
2007-08-09 08:31:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) MECHANICAL PLANS SUBMITTED GRAYED OUT AREAS AND
 OTHER DARKEN LINES THAT MAKE IT DIFFICULT TO SEE ALL
 MECHANICAL DETAIL ON THE PLAN THEIR FOR SOME ITEMS MAY
 BE MISSED ON THIS PLAN REVIEW. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC 106.1.1.
 PLEASE CORRECT.
  
 2) MECHANICAL PLANS (EQUIPMENT INFORMATION) LISTS TWO
 A/C SYSTEMS AS #1, PLEASE CORRECT.
  
 3) AS NOTED IN LAST REVIEW 7-16-07 NOTE #6, PLEASE SHOW
 ON MECHANICAL PLANS COMBUSTION AIR CALCULATIONS FOR GAS
 CLOTHES DRYER IN LAUNDRY ROOM AND PROVIDE COMBUSTION
 AIR AND MAKE-UP AIR IF REQUIRED, SEE 2004 FBC/R G2407.1
 (304.1).
  
 4) SHOW ON MECHANICAL PLAN THE CLOTHES DRYER VENT AND
 STATE WERE IT WILL VENT TO, SEE 2004 FBC/R R303.4.2.
  
 5) SHOW ON MECHANICAL PLAN THE CFM'S. AT ALL BATHROOM
 EXHAUST FANS, SEE 2004 FBC/R R303.3.
  
 6) THE ELECTRICAL PLAN SHOWS A BATHROOM EXHAUST FAN IN
 THE MASTER BATH NEAR THE TUB, AS THE WINDOWS APPEAR TO
 BE FIXED AT THAT LOCATION SEE 2004 FBC/R R303.3 AND
 PLEASE CORRECT PLANS SO THEY COINCIDE.
  
 7) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLAN SHOWING
 A/C DUCTS THAT NEED TO BE SIZED.
  
 8) MECHANICAL PLAN DOES NOT SHOW WHICH AIR HANDLER AND
 CONDENSER UNIT IS #1, PLEASE CORRECT.
  
 9) PLEASE ADD A SECOND COPY OF THE INSTALLATION
 INSTRUCTIONS FOR THE UNVENTED GAS LOG HEATER, AS ONLY
 ONE WAS SUBMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By tgordon Date 2007-07-16 Time 08:47 Rev Time 0.30
Received By tgordon Date 2007-07-16 Time 08:47 Sent To P
Notes
2007-07-16 09:23:39*** DENIED ***
 1) PLEASE STATE ON PLANS THE BUILDING CODE BEING USED
 FOR THIS PROJECT, PRESENTLY 2004 FBC W/ 2006 REVISIONS,
 SEE 2004 FBC 106.1.1.
  
 2) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK, SEE
 2004 FBC 106.1.1.
  
 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS FOR REVIEW, SEE
 2004 FBC CITY WPB AMEND. 106.3.5.4 (10).
  
 4) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.1.
  
 5) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 6) SHOW ON MECHANICAL PLAN COMBUSTION AIR CALCULATION
 FOR GAS VENT FREE FIREPLACE IN CLUB ROOM, AND GAS
 CLOTHES DRYER IN LAUNDRY ROOM. PROVIDE COMBUSTION AND
 MAKE-UP AIR IF REQUIRED, SEE 2004 FBC/R G2407.1
 (304.1).
  
 7) ELECTRICAL PLANS PANEL LISTS 4 A/C SYSTEMS BUT PLANS
 ONLY SHOW 3 A/C SYSTEMS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-08 Cont ID  
Sent By jleech Date 2007-08-08 Time 13:06 Rev Time 0.00
Received By jleech Date 2007-08-08 Time 13:06 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-20 Cont ID  
Sent By jleech Date 2007-07-20 Time 09:14 Rev Time 0.00
Received By jleech Date 2007-07-20 Time 09:14 Sent To B
Notes
2007-07-20 09:22:13DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 A) 9-W/C'S ON RISER DIAGRAM 7- ON PLAN
 B) MISSING BIDET'S
 C) MISSING AUTO MATIC CLOTHES WASHER.
 D) LAUNDRY TUB TO DISCHARGE DOWN STREAM OF
 BATHROOM GROUP. SEC. 909.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-06 Cont ID  
Sent By choops Date 2008-03-06 Time 16:11 Rev Time 0.00
Received By choops Date 2008-03-06 Time 16:11 Sent To PC
Notes
2008-03-06 16:12:16***APPROVED - LANDSCAPE PLAN SUBMITTAL***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-31 Cont ID  
Sent By choops Date 2007-07-31 Time 11:23 Rev Time 0.00
Received By choops Date 2007-07-31 Time 11:23 Sent To E
Notes
2007-07-31 11:26:37PROVISO:1)1000 SQ.FT. MINIMUM TO REMAIN LANDSCAPE
 WITHIN FRONT YARD.2)POOL / POOL EQUIPMENT /
 GENERATOR TO BE ON SEPERATE PERMIT AS INDICATED ON SITE
 PLAN.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By choops Date 2007-07-11 Time 09:46 Rev Time 0.00
Received By choops Date 2007-07-11 Time 09:45 Sent To E
Notes
2007-07-11 09:54:31***FAILED***
  
  
 1)SCOPE OF WORK NOT CLEAR.DRIVEWAY INCLUDED UNDER
 THIS PERMIT?IF SO, INCLUDE ALL DIMENSIONS AND SQUARE
 FOOTAGE.POOL EQUIPMENT/HEATER AND POOL/SPA SHOWN ON
 PLANS...REMOVE IF NOT INCLUDED IN SCOPE OF WORK FOR
 THIS PROJECT.GENERATOR SHOWN ON PLANS...REMOVE IF NOT
 INCLUDED IN SCOPE OF WORK FOR THIS PROJECT.(IF
 POOL/EQUIPMENT AND GENERATOR IS INCLUDED PROVIDE
 DETAILS AND SETBACK DIMENSIONS FROM PROPERTY LINES.
  
 2)PLEASE PROVIDE SETBACK DIMENSIONS FROM PROPOSED
 A/C EQUIPMENT TO THE PROPERTY LINES.
  
 3)PROVIDE ALL OVERHANG DIMENSIONS FROM THE WALL TO
 THE OUTERMOST POINT OF THE ROOF.NOTE:OVERHANGS MAY
 NOT ENCROACH MORE THAN 3' INTO ANY REQUIRED SETBACK.
  
 4)PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTION 94-442 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720