| 2007-07-23 15:24:22 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE SUBMITTED ISOMETRIC DOES NOT REFLECT THE MASTER |
| | PERMIT #07030410 FLOOR PLAN BATHROOM LAYOUTS. THERE ARE |
| | NO SHOWERS BEING INDICATED ON THE MASTER PERMIT |
| | #07030410 ONLY TUBS. PLEASE RESUBMIT WITH THE FOLLOWING |
| | INFORMATION A} A FLOOR PLAN WITH THE EXISTING LAYOUT. |
| | B} A REVISED FLOOR PLAN THAT CLEARLY REFLECTS THE |
| | SUBMITTED BATHROOM ISOMETRIC WITH A WATER/CLOSET, |
| | LAVATORY AND SHOWER. |
| | |
| | 2. CLARIFY WHAT THE THREE INCH (3") STACK IS FOR ON |
| | THE RESUBMITTAL. |
| | |
| | 3. TRAPS ARE REQUIRED FOR THE SHOWER AND LAVATORY PER |
| | FBC-2004 PLUMBING, SECTION 1002.1. PLEASE CLEARLY |
| | INDICATE THEM ON THE RESUBMITTAL. |
| | |
| | 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED AND |
| | PROVIDE ONE COPY OF OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | |
| | END OF COMMENTS: |
| | |