Plan Review Details - Permit 07070144
Plan Review Stops For Permit 07070144
Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-03-12 Cont ID  
Sent By mawillia Date 2008-03-11 Time 18:48 Rev Time 0.00
Received By mawillia Date 2008-03-06 Time 18:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-15 Cont ID  
Sent By mawillia Date 2008-01-15 Time 16:57 Rev Time 0.00
Received By mawillia Date 2008-01-15 Time 16:30 Sent To  
Notes
2008-01-15 16:50:09*****APPROVED REVISION*****
  
 REVISED PLAN SHEETS FP1 AND FP2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-12-27 Cont ID  
Sent By mawillia Date 2007-12-27 Time 13:29 Rev Time 0.00
Received By mawillia Date 2007-12-27 Time 12:54 Sent To  
Notes
2007-12-27 13:24:15*****UNSAT*****
  
  
 1. THE LOCATION OF THE FDC AS SHOWN ON SHEET FP 0.1
 DOES NOT CORRELATE WITH THE LOCATION SHOWN ON SHEET FP
 1.PLEASE SUBMIT REVISED FP 1 SHOWING THE
 REVISION(S).
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-27 Cont ID  
Sent By mawillia Date 2007-08-27 Time 15:19 Rev Time 0.00
Received By mawillia Date 2007-08-27 Time 14:32 Sent To  
Notes
2007-08-27 14:54:18*****APPROVED*****
  
  
 PLAN SHEETS FP1 AND FP2 WERE STAMPED, INITIALED, AND
 DATED;READY FOR PERMIT ISSUANCE.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By mawillia Date 2007-08-09 Time 11:37 Rev Time 0.00
Received By mawillia Date 2007-08-09 Time 09:50 Sent To  
Notes
2007-08-09 11:37:39*****DENIED*****
  
  
 1.THE CORRECT ADDRESS OF THE PROJECT SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.THE
 ADDRESS CURRENTLY SHOWS ADDRESS AS 1825 MERRY PLACE.
  
 2.SPEC SHEETS APPEAR TO BE OK, HOWEVER AMEND THE
 APPROPIATE COVER SHEETS TO REFLECT THE CORRECT
 ADDRESS.
  
 3.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 4.COORDINATE WITH THE GENERAL AND/OR OTHER APPROPIATE
 CONTRACTOR(S) THAT THE DOUBLE DETECTOR CHECK ASSEMBLY
 BE CHAINED AND LOCKED UPON COMPLETION OF THE FIRE FINAL
 INSPECTION.
  
 5.COORDINATE WITH THE GENERAL AND/OR OTHER APPROPIATE
 CONTRACTOR(S) THAT THE REQUIRED KNOX LOCKING CAPSBE
 INSTALLED ON THE FIRE DEPARTMENT CONNECTIONS.FOR
 APPLICATIONS, CONTACT WEST PALM BEACH FIRE PREVENTION
 AT 561-805-6722.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 14:53 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 14:53 Sent To FIRE
Notes
2008-02-28 14:54:40TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-09 Cont ID  
Sent By adarroug Date 2008-01-09 Time 08:56 Rev Time 0.00
Received By adarroug Date 2008-01-09 Time 08:56 Sent To FIRE
Notes
2008-01-09 08:57:15TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 12:12 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 12:12 Sent To FIRE
Notes
2007-12-19 12:12:40TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 16:42 Sent To FIRE
Notes
2007-08-21 16:43:13TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-09 Cont ID  
Sent By mawillia Date 2007-08-09 Time 09:50 Rev Time 0.00
Received By mawillia Date 2007-07-09 Time 11:09 Sent To  
Notes
2007-07-09 11:09:59TO "F" BOX