| 2007-07-18 12:48:40 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW |
| | |
| | 1} DECLARE OCCUPANCY TYPE FOR THIS BUILDING PER CHAPTER |
| | 3, FLORIDA BUILDING CODE. |
| | |
| | 2} DECLARE THE LEVEL OF ALTERATION THAT WAS DONE TO THE |
| | BUILDING PER 301.5 FBC EXISTING BUILDING CODE. |
| | |
| | 3} PROVIDE A RISER DIAGRAM, INDICATE THE LOCATION OF |
| | THE SERVICE EQUIPMENT, NEW AND EXISTING. |
| | |
| | 4} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL |
| | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO |
| | BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 |
| | NEC 2005. |
| | |
| | 5} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| | DEVICES AND LIGHTING. SHOW COMPLIANCE WITH 700.12(F)(4) |
| | WHERE BATTERY PACK EMERGENCY LIGHTS ARE LOCATED. |
| | |
| | 6} INDICATE WHAT EQUIPMENT THE "NEW DISCONNECTS" SHOWN |
| | ON THE PLAN SERVE. |
| | |
| | 7} PROVIDE FORMS TO SHOW COMPLIANCE WITH CHAPTER 13 |
| | FBC.PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER |
| | 13-415.2.AND CERTIFICATION PER 13-103.1.2. |
| | |
| | 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS PER 471FS ARE APPLICABLE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |