| 2007-08-30 09:04:14 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2004 (WITH 2007 |
| | AMENDMENTS) |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC* 106.1 AND 471.025 F.S.ENGINEERS SEAL AND |
| | SIGNATURE.THE SUBMITTED PLANS HAVE AN ENGINEER'S |
| | TITLE BLOCK BUT THE PLANS ARE PHOTOCOPIES.THEY DO NOT |
| | HAVE THE ORIGINAL SIGNATURE AND RAISED SEAL OF THE |
| | ENGINEER.SUBMIT SIGNED AND SEALED ORIGINALS. |
| | |
| | 2) FBC 2002.4TRAC SELF MATING BEAM.SHEET 2 OF THE |
| | SUBMITTED PRODUCT APROVAL FL 7350.1 STATES THAT "SITE |
| | SPECIFIC ENGINEERING MUST ACCOMPANY THIS PRODUCT |
| | APPROVAL FOR EACH STRUCTURE INSTALLED".NO SITE SITE |
| | SPECIFIC ENGINEERING WAS SUBMITTED.SUBMIT SITE |
| | SPECIFIC ENGINEERING TO JUSTIFY THE MEMBER SIZES FOR |
| | THE PROPOSED SPANS AND CONFIGURATION. |
| | |
| | 3) FBC 2002.4CORNER POSTS.THE CORNER POST SIZE (AND |
| | WALL THICKNESS) IS NOT STATED ON THE PLANS. |
| | |
| | 4) FBC 2002.4PURLIN AND ROOF BRACE SIZES ARE STATED |
| | ON THE CONNECTION DETAILS BUT ARE NOT STATED ON THE |
| | PLAN VIEW OF THE STRUCTURE.THE CONNECTION DETAILS ARE |
| | ENGINEERED (SEE COMMENT 1) BUT THEY ARE NOT CORRELATED |
| | WITH THE LAYOUT PLAN (SEE COMMENT 2 ABOVE). |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: |
| | (561) 805 6652ROBERT BROWN |
| | E-MAIL: [email protected] |