| Plan Review Stops For Permit 07070124 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-08-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-08-20 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-08-20 |
Time |
12:34 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-07-18 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-18 |
Time |
09:50 |
Sent To |
PC |
|
| Notes |
| 2007-07-18 10:13:54 | BUILDING REVIEW CHECKLIST: | | | 1- SETBACKS SHOWN ON SITE PLAN DON'T MATCH SURVEY. | | | | | | 2- FLOOD ZONE INFORMATION ON SURVEY IS INCORRECT. | | | PROPERTY IS LOCATED IN FLOOD ZONE "C" PER COMMUNITY | | | PANEL # 120229 0020 B DATED MARCH 01, 1979.REVISE AS | | | REQUIRED. THIS IS THE ONLY OFFICIAL MAP TO BE USED FOR | | | FLOOD ZONE DETERMINATION. | | | | | | 3- PROVIDE COMPLETE SPECS FOR ICYNENE INSULATION.AND | | | CLARIFY IF EXISTING RESIDENCE HAS THIS TYPE OF | | | INSULATION TO VERIFY COMPLIANCE WITH ATTIC VENTILATION | | | SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. SEC. | | | 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 4- SPECIFY DESIGN CRITERIA AND CODE TO BE USED AS | | | REQUIRED BY SEC. R301 AND TABLE R301.5 OF 2004 FLORIDA | | | RESIDENTIAL CODE. SPECIFY ALLWIND, LIVE AND DEAD | | | LOADS. | | | | | | 5- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1 | | | FBC 2004. | | | | | | 6- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC. | | | 106.1.1.2 CITY AMENDMENTS TO FBC 2004. PROVIDE COMPLETE | | | SPECS NAIL OR SCREW SIZE AND NUMBER OR SPECIFIC | | | ADHESIVE TO VERIFY COMPLIANCE WITH THE ATTACHMENT | | | RESISTANCE. PRODUCT APPROVAL IS TO VERIFY COMPLIANCE | | | WITH DESIGNER CRITERIA. | | | | | | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) ROOF TILE.NEED TO PROVIDE COMPLETE REPORT AS | | | DONE WITH WINDOWS AND DOORS. ONLY THE FLORIDA PRODUCT | | | APPROVAL COVER PAGES INFORMATION WAS PROVIDED. | | | | | | B) ALL SIMPSON STRUCTURALCONNECTORS SPECIFIED ON | | | PLANS. NEED TO PROVIDE THE PRODUCT APPROVAL COVER PAGE | | | AND THE SPECIFIC PAGE WHERE CONNECTOR IS SHOWN. ONLY | | | THE COVER PAGE WAS PROVIDED. | | | | | | 8- ENERGY CALCULATIONS: | | | A) OWNER/AGENT TO SIGN AND DATE CALCULATIONS AT | | | BOTTOM OF FORM. | | | | | | B) PROVIDE COMPLETE INFORMATION, INCLUDING BUILDER | | | INFORMATION. | | | | | | 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-16 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-16 |
Time |
17:16 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-12 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-12 |
Time |
07:53 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-08-08 |
Time |
18:54 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2007-08-08 |
Time |
18:54 |
Sent To |
B |
|
| Notes |
| 2007-08-08 18:54:28 | SENT TO ZONING MMILLER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-07-18 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-09 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2007-07-09 09:56:25 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-08-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-17 |
Time |
08:49 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-08-17 |
Time |
08:49 |
Sent To |
P |
|
| Notes |
| 2007-08-17 08:53:20 | PASSED MECH. REVIEW 7-13-07. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-13 |
Time |
11:54 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-07-13 |
Time |
11:54 |
Sent To |
P |
|
| Notes |
| 2007-07-13 11:55:20 | *** PROVISO *** | | | 1) PROVIDE FOR RETURN AIR TO PLAY ROOM, SEE 2004 FBC/R | | | M1602.4. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-08-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-17 |
Time |
15:19 |
Rev Time |
0.20 |
| Received By |
mperson |
Date |
2007-08-17 |
Time |
15:19 |
Sent To |
B |
|
| Notes |
| 2007-08-17 15:25:26 | ****************PROVISO**************** | | | PER FBC-2004 PLUMBING, SECTION 608.15.4.2 HOSE | | | CONNECTIONS. HOSE BIBBS SHALL BE PROTECTED BY AN | | | ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM BREAKER OR A | | | PERMANENTLY ATTACHED HOSE CONNECTION VACUUM BREAKER. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-17 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-17 |
Time |
07:29 |
Sent To |
B |
|
| Notes |
| 2007-07-17 07:46:20 | DENIED; | | | THE PERMIT APPLICATION HAS A PLUMBING COMPANY LISTED | | | AND THE FIRST PAGE OF THE PLANS STATES THAT PAGE M/E100 | | | HAS A PLUMBING RISER, NONE FOUND. SHOW PLUMBING WORK TO | | | BE DONE ON PLANS IF NONE REMOVE PLUMBING COMPANY FROM | | | APPLICATION AND CHANGE FIRST PAGE OF PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-13 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-13 |
Time |
13:05 |
Sent To |
E |
|
| Notes |
| 2007-08-13 13:06:23 | ***PASSED*******RESUB #1*** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-09 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-09 |
Time |
16:05 |
Sent To |
E |
|
| Notes |
| 2007-07-09 16:07:20 | ***FAILED*** | | | | | | | | | 1)SETBACK DIMENSIONS DON'T MATCH BETWEEN SITE PLAN | | | AND SURVEY. | | | | | | 2)PLEASE PROVIDE ELEVATION DIMENSION FROM GRADE TO | | | THE MIDPOINT OF THE ROOF'S PITCH (OF THE ADDITION) | | | | | | 3)SHOW SETBACK DIMENSIONS FROM THE PROPOSED ADDITION | | | TO THE PROPERTY LINES. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|