Plan Review Details - Permit 07070123
Plan Review Stops For Permit 07070123
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By mjacobs Date 2007-07-23 Time 12:13 Rev Time 0.00
Received By mjacobs Date 2007-07-20 Time 14:33 Sent To  
Notes
2007-07-20 17:09:16BUILDING PLAN REVIEW
 PERMIT: 07070123
 ADD: 210 S.OLIVE AVE
 CONT: EAST COAST CONST.
 TEL: (561)935-9536
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) SUBMIT THE LIFE SAFETY PLAN.
 . -------------------------------------
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 1004.6 MEZZANINE LEVELS.
 THE OCCUPANT LOAD OF A MEZZANINE LEVEL WITH EGRESS ONTO
 A ROOM OR AREA BELOW SHALL BE ADDED TO THAT ROOM OR
 AREA?S OCCUPANT LOAD, AND THE CAPACITY OF THE EXITS
 SHALL BE DESIGNED FOR THE TOTAL OCCUPANT LOAD THUS
 ESTABLISHED.
  
 3)(2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL. SHOW CLEARLY WHAT IS EXISTING AND
 WHAT IS NEW.
  
 4)FBC 106.1THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A DESIGN PROFESSIONAL. IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE REGULATING THE
 PRACTICE OFARCHITECTURE AS PROVIDED FOR IN CHAPTER 481,
 FLORIDA STATUTES, PART I, OR ENGINEERING AS PROVIDED
 FOR IN CHAPTER 471, FLORIDA STATUTES, THEN HE OR SHE
 SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE AND
 DATE TO SSAID DRAWINGS.
  
 5) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 6)2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 7)INDICATE THE NAME AND ADDRESS OF THE PROJECT ON
 EACH SHEET.
  
 8)FBC 803.5INTERIOR WALL AND CEILING FINISH SHALL
 HAVE A FLAME SPREAD INDEX NOT GREATER THAN THAT
 SPECIFIED IN TABLE 803.5 FOR THE GROUP AND LOCATION
 DESIGNATED. SEE 803.1 ALSO.INDICATE THE FLAME SPREAD
 ON THE DRAWINGS. SUBMIT A FINISH SCHEDULE FOR EACH
 ROOM. A WALL DETAIL SHALL BE SUBMITTED INDICATING ALL
 MATERIALS.
  
 9)FBC. 1210.2WALLS WITHIN 2 FEET OF UNIRALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, "HARD" NONABOSRBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR, NOTE:
 PAINT IS NOT CONSICERED A HARD SURFACE.
  
 10)THE RECPTIONIST DESK ON SHEET A-2 SHALL MEET THE
 REQUIREMENTS OF FBC. 11-7.A PORTION OF THE DESK SHALL
 BE 36 INCHES IN LENGTH AND 36 INCHES IN HEIGHT. PROVICE
 ELEVATION DETAIL DRAWINGS OFTHE RECPTIONIST DESK.
  
 11)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 12)INDICATE WHAT WILL BE STORED IN THE STORAGE ROOM,
 AND INDICATE IF THE STORAGE USE S-1 OR S-2.
  
 13)THE TOILET STALL ON SHEET A-1, SHOWS ONLY ONE GRAB
 BAR. TOILET STALL SHALL MEET THE REQUIREMENTS OF FBC.
 11-4.17. STATE WHAT TYPE OF MATERIAL WILL BE USED FOR
 THE GRAPBARS BACKING. ALSO SEE 11-4.26.3 FOR MORE
 INFORMATION.
  
 14)A FRONT ELEVATION OF THE LOFT ISREQUIRED
 SHOWNING THE HEIGHT AND STRUCTUREOF THE GUARD GUARD
 RAIL. SEE FBC 1607.4 DISTRIBUTED FLOOR LOADS AND
 FBC.1607.7.1 HANDRAILS AND GUARDRAILS. SHOW THIS
 INFORMATION ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By btrobaug Date 2007-07-16 Time 12:19 Rev Time 0.00
Received By btrobaug Date 2007-07-13 Time 17:32 Sent To  
Notes
2007-07-13 17:46:14 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} DECLARE THE USE OF THE BUILDING PER CHAPTER 3, FBC..
 CHANGE OF OCCUPANCY. A CHANGE IN THE PURPOSE OR LEVEL
 OF ACTIVITY WITHIN A BUILDING THAT INVOLVES A CHANGE IN
 APPLICATION OF THE REQUIREMENTS OF THIS CODE.
  
 3} PANEL MAY NOT BE LOCATED IN A STORAGE CLOSET PER
 240.24(D).
  
 4} INDICATE IF ALL WORK SHOWN IS NEW UNDER THIS
 APPLICATION. IF THERE IS EXISTING INDICATE SAME.
  
 5} PROVIDE CIRCUIT NUMBERS FOR ALL DEVICES 106.3.5.1.2
 FBC. SEE LOFT.
  
 6} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 7} 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT
 ONE OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT
 TO SECTIONS 303, 304 AND 305 OF THIS CODE. EXISTING
 BUILDING CODE, 2004 FBC.
  
 8} INDICATE COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BLDG CODE. 13.413,
 13.414, 13.415. SHOW TIME CLOCK AND/OR
 OCCUPANCY SENSOR LOCATIONS ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-27 Cont ID  
Sent By mwennerg Date 2007-07-27 Time 14:20 Rev Time 0.00
Received By mwennerg Date 2007-07-27 Time 14:20 Sent To  
Notes
2007-07-27 14:33:11***DENIED***
  
 1) PLANS ARE REQUIRED TO BE SIGNED, SEALED AND DATED BY
 DESIGN PROFESSIONAL.
  
 2) PLEASE INDICATE IF THIS PROJECT IS PROTECTED BY
 EXISTING FIRE PROTECTION EQUIPMENT.
  
 3) PLEASE SHOW LOCATION OF REQUIRED ILLUMINATED EXIT
 SIGNS AND EMERGENCY LIGHTING FACILITIES. (NEW OR
 EXISTING)
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED, AND
 SHALL BE MOUNTED AT LOCATIONS NOT TO EXCEED (75) FEET
 TRAVEL DISTANCE REQUIREMENT.
  
 5)LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGEN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-31 Cont ID  
Sent By jleech Date 2007-07-31 Time 07:26 Rev Time 0.00
Received By jleech Date 2007-07-06 Time 10:55 Sent To  
Notes
2007-07-12 10:07:49TO "BOB"#1
2007-07-06 10:55:52WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By tgordon Date 2007-07-17 Time 08:06 Rev Time 0.30
Received By tgordon Date 2007-07-17 Time 08:06 Sent To  
Notes
2007-07-17 08:30:57*** DENIED ***
 1) PLANS DO NOT INDICATE WHAT IS NEW, EXISTING, OR
 REPLACEMENT. PLEASE CORRECT.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.1.3.
  
 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 4) PLEASE SHOW ON MECHANICAL PLANS AN A/C EQUIPMENT
 SCHEDULE WITH ALL PERTINENT INFORMATION.
  
 5) SHOW ON MECHANICAL PLANS OUTSIDE AIR CALCULATIONS,
 AND PROVIDE OUTSIDE AIR, SEE 2004 FBC 401.2.
  
 6) SHOW ALL DUCT AND GRILL SIZES ON PLANS.
  
 7) SHOW SUPPLY AIR CFM'S. AT ALL SUPPLY AIR GRILLS.
  
 8) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLANS, SEE
 2004 FBC/M 403.3.
  
 9) SHOW LOCATION OF A/C CONDENSER UNIT ON PLANS.
  
 10) SHOW HOW AIR IS TO RETURN TO THE AIR HANDLER UNIT
 FROM THE FIRST AND SECOND FLOOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By jleech Date 2007-07-31 Time 07:14 Rev Time 0.00
Received By jleech Date 2007-07-31 Time 07:06 Sent To  
Notes
2007-07-31 07:25:52DENIED;
 1. SHOW DETAILS OF HANDICAP BATHROOM FIXTURES WITH ALL
 MESSUREMENTS REQUIRED. SEE FBC-2004 BUILDING CHAPTER 11
 FIG'S 29 & 32.
 2. BATHROOM DOOR CANNOT SWING INTO THE CLEAR FLOOR
 SPACE OF THE LAVATORY.
 3. THE TURNING RADIUS IS 5' NOT 3' AS SHOWN ON
 DRAWING.
 4. SHOW WATER RISER DIAGRAM AS REQUIRED BY FBC-2004
 BUILDING CHAPTER 1, SECTION 106.3.5.1.3. PLUMBING NOTES
 4 AND 9 REFERENCE WATER HEATER, NOT SHOWN ON DRAWINGS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 17:22 Rev Time 0.00
Received By choops Date 2007-07-23 Time 17:22 Sent To  
Notes
2007-07-23 17:22:48*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.