Plan Review Details - Permit 07070113
Plan Review Stops For Permit 07070113
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-17 Cont ID  
Sent By tgordon Date 2007-08-17 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2007-08-17 Time 13:18 Sent To  
Notes
2007-08-17 16:11:472004 FBC W/2007 SUPPLEMENT
 INSTALL A/C
  
 1) MAJOR WORKING DRAWING REVIEW HAS BEEN COMPLETED.
 PLANS AND SUBMITTALS HAVE BEEN FOUND TO BE CODE
 COMPLIANT PENDING ANY CODE CHANGES FROM THE DATE OF THE
 REVIEW AND DATE OF APPLICATION FOR PERMIT. REVIEW
 STATUS WILL BE CHANGED FROM F TO P IF NO CODE CHANGES
 ARE MADE PRIOR TO PERMIT APPLICATION.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By rmcdouga Date 2007-08-09 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2007-08-09 Time 14:55 Sent To  
Notes
2007-08-09 15:51:082004 FBC WITH 2007 REVISIONS
 INSTALL CENTRAL A/C
 PLAN REVIEW
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE FIRM LICENSE NUMBER FOR THE ARCHITECT BUSINESS
 IS REQUIRED IN THE TITLE BLOCK. THE ARCHITECT'S LICENSE
 NUMBER IS LISTED. SEE FAC 61G1-16.004 AND FS 481.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE VENT THROUGH THE
 EXTERIOR WALL IN DETAIL 6 ON M3. SEE FAC RULE 9B-72.
  
 4) SUBMIT THE COMPLETE PRODUCT APPROVAL NOA FOR THE
 ALUMISTAND AND VIBRA DAMA CORP. OF AMERICA A/C STANDS.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 6)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 09:31 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 09:31 Sent To M
Notes
2007-08-16 09:32:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-09 Cont ID  
Sent By rmcdouga Date 2007-08-09 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2007-07-09 Time 10:34 Sent To  
Notes
2007-07-09 10:34:53TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-17 Cont ID  
Sent By tgordon Date 2007-08-16 Time 11:30 Rev Time 0.30
Received By tgordon Date 2007-08-16 Time 11:30 Sent To B
Notes
2007-08-17 16:25:17** FORE PLANS REVIEW ONLW NOT FOR PERMIT**
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) MECHANICAL PLANS ARE OK AT THIS TIME, BUT NEED TO
 APPLY FOR PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-09 Cont ID  
Sent By tgordon Date 2007-07-09 Time 12:02 Rev Time 0.35
Received By tgordon Date 2007-07-09 Time 12:02 Sent To B
Notes
2007-07-09 12:20:20FOR PLAN REVIEW ONLY NOT FOR PERMIT.
 *** DENIED ***
 1) PLEASE PROVIDE COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS, SEE 2004
 FBC/M 401.2. AND PLEASE STATE WHAT TYPE OF BUSINESS
 THESE ARE.
  
 3) SUITE 422, PLEASE PROVIDE RETURN AIR TO WHAT APPEARS
 TO BE AN 8 X 10 FT. OFFICE, SEE 2004 FBC/M 601.4.
  
 4) SUITE 420, PLEASE SHOW HOW AIR WILL RETURN TO THE
 AHU AS IT APPEARS TO BE IN A 9 X 12 FT. OFFICE.
  
 5)INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 (FIRM LICENSE NUMBER) LICENSE NUMBER IN TITLE BLOCK
 AR0011209 IS FOR ROGER GILMAN MORSE NOT FOR THE FIRM
 MORSE ASSOCIATES. PLEASE CORRECT, SEE FAC 61G1-16.004
 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.