Plan Review Details - Permit 07070072
Plan Review Stops For Permit 07070072
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-09-02 Cont ID  
Sent By rmcdouga Date 2008-09-02 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2008-09-02 Time 11:35 Sent To Z
Notes
2008-09-02 11:39:32BUILDING PROVISO
  
 1) ELEVATION CERTIFICATE IS REQUIRED BEFORE FINAL
 INSPECTION.
  
 2) SUBMIT SHOP DRAWINGS FOR THE SPIRAL STAIRS FOR
 REVIEW BEFORE INSTALLING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-11 Cont ID  
Sent By rmcdouga Date 2008-02-11 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2008-02-11 Time 14:32 Sent To M
Notes
2008-02-11 16:23:312004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A NOTICE OF COMMENCEMENT WILL BE REQUIRED.
  
 2) THE PBC PROPERTY APPRAISER LISTS THE VALUE OF THE
 STRUCTURE AS $ 20,552.00 AND THE VALUE OF THE WORK IS
 $100,000.00, WHICH IS MORE THAN FIFTY PER CENT OF THE
 VALUE OF THE STRUCTURE. THEREFORE, THE EXISTING
 RESIDENTIAL STRUCTURE IS REQUIRED TO HAVE THE LOWEST
 FLOOR ELEVATED TO SIX INCHES ABOVE BASE FLOOD
 ELEVATION. SEE ITEM #2 OF PREVIOUS REVIEW. SEE SECTION
 94-546 (B) (1) OF THE CITY CODE.
  
 3) SHOP DRAWINGS FOR THE SPIRAL STAIRS WILL BE REQUIRED
 TO BE SUBMITTED FOR PLAN REVIEW APPROVAL PRIOR TO
 INSTALLATION. FBC 106.1.1* CITY AMENDMENTS.
  
 4) SUBMIT PRODUCT APPROVALS/MANUFACTURER'S
 SPECIFICATIONS FOR THE SECOND AND THIRD FLOOR DECK
 WATERPROOFING. FAC RULE 9B-72 AND FBC 106.1.1* CITY
 AMENDMENTS.
  
 5)ON SHEET A-4 SEVERAL OF THE CONNECTIONS FOR THE
 BEAMS AND GIRDERS ARE NOT SPECIFIED. FBC 106.1.1* CITY
 AMENDMENTS.
  
 6) THE WALL SECTION ON A-5 SPECIFIES R-30 INSULATION IN
 A 4 INCH SPACE AT THE UPPER ROOF. PLEASE CLARIFY. SEE
 FBC 13-6.
  
 7)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE HARDIPLANK PRODUCT
 APPROVALS HAVE NOT BEEN APPROVED BY THE DESIGNER OF
 RECORD.
  
 8) SUBMIT THE INSTALLATION INSTRUCTIONS/EVALUATION
 REPORT OR NOA FOR THE PGT EXTERIOR DOOR, SINGLE HUNG
 AND FIXED WINDOWS AS REQUIRED BY FAC RULE 9B-72.
  
 9) SPECIFY THE SIZE OF THE BASE PLATE FOR THE STEEL AND
 ALUMINUM COLUMNS. INDICATE THE LOCATIONS AND SIZE OF
 THE HOLES FOR THE ANCHOR BOLTS. FBC 106.1.2* CITY
 AMENDMENTS.
  
 10) THE HEIGHT OF THE BALCONY GUARDRAIL IS SPECIFIED AS
 BOTH 42" AND 36" ON SHEET A-3. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By rmcdouga Date 2007-07-17 Time 18:27 Rev Time 0.00
Received By rmcdouga Date 2007-07-17 Time 18:27 Sent To Z
Notes
2007-07-17 18:28:06DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ELEVATION CERTIFICATE THAT WAS SUBMITTED
 INDICATES THE FIRST FLOOR ELEVATION TO BE 7.3 FEET NGVD
 AND THE EQUIPMENT ELEVATION AS 7.1 NGVD. THIS DOES NOT
 MEET THE REQUIREMENTS OF THE CITY CODE WHICH REQUIRES
 AN ADDITIONAL 6 INCHES ABOVE THE BFE OF 7 FEET NGVD.
 SECTION 94-546 (B) (1) OF THE CITY CODE REQUIRES ALL
 NEW RESIDENTIAL CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT
 OF ANY EXISTING RESIDENTIAL STRUCTURE TO HAVE THE
 LOWEST FLOOR, INCLUDING BASEMENT, ELEVATED TO SIX
 INCHES ABOVE BASE FLOOD ELEVATION.SUBSTANTIAL
 IMPROVEMENTMEANS ANY COMBINATION OF REPAIRS,
 RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO A
 STRUCTURE, TAKING PLACE DURING THE LIFE OF A STRUCTURE,
 IN WHICH THE CUMULATIVE COST EQUALS OR EXCEEDS 50
 PERCENT OF THE MARKET VALUE OF THE STRUCTURE. THE
 MARKET VALUE OF THE STRUCTURE SHOULD BE THE APPRAISED
 VALUE OF THE STRUCTURE PRIOR TO THE START OF THE
 INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF
 DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE
 OCCURRING. FOR THE PURPOSES OF THIS DEFINITION,
 "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN
 THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR
 OTHER STRUCTURAL PART OF THE BUILDING COMMENCES,
 WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL
 DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL
 IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT
 OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH,
 SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO
 ENSURE SAFE LIVING CONDITIONS.
  
  
 3) THE ELEVATION CERTIFICATE THAT WAS SUBMITTED DOES
 NOT CONCUR WITH THE EXISTING FIRST FLOOR ELEVATION OF
 7.7 FEET NGVD THAT IS SPECIFIED ON THE SITE PLAN.
 PLEASE CORRECT.
  
 4) THE WINDMILL FOUNDATION IS REQUIRED TO BE DESIGNED
 TO COMPLY WITH THE 2004 FBC FOR 140 MPH WIND SPEED. THE
 SPECIFICATIONS AND DETAILS FOR THE COMPLETE WINDMILL
 INCLUDING THE TOWER, TURBINE, ETC. WITH WINDLOAD AND
 DEAD LOAD CALCULATIONS FROM A FLORIDA LICENSED ENGINEER
 IS REQUIRED. THE EQUIPMENT IS REQUIRED TO BE 6 INCHES
 ABOVE BASE FLOOD ELEVATION.
  
 5) THE SUBSURFACE SOIL ENGINEER'S REPORT INDICATES THAT
 SUSTANTIAL SETTLEMENT WILL OCCUR DUE TO THE NEW LOADS
 FROM THE PROPOSED SECOND STORY AND DIFFERENTIAL
 SETTLEMENT IS TO BE EXPECTED. SUBMIT A SIGNED AND
 SEALED LETTER FROM THE DESIGNER OF RECORD STATING THAT
 THE ENGINEER'S REPORT HAS BEEN REVIEWED AND THE
 SETTLEMENT IS ACCEPTABLE OR SUBMIT DOCUMENTATION
 SPECIFYING WHAT METHODS WILL BE EMPLOYED TO IMPROVE THE
 SOIL.
  
 6) THE STRUCTURE IS LOCATED IN EXPOSURE C, HOWEVER, THE
 WIND LOAD PRESSURES FOR THE WINDOWS, DOORS AND ROOF ARE
 FROM TABLE R301.2(2) FOR EXPOSURE B AND ARE TOO LOW.
 USE THE ADJUSTMENT COEFFICENTS IN TABLE R301.2(3) FOR
 EXPOSURE C WITH MEAN ROOF HEIGHT OF 28 FEET TO INCREASE
 THE PRESSURES.
  
 7)R1002.1 FACTORY-BUILT CHIMNEYS
 FACTORY BUILT CHIMNEYS SHALL BE LISTED
 AND SHALL BE INSTALLED IN ACCORDANCE
 WITH THE CONDITIONS OF THE LISTING, AND MANUFACTURER'S
 INSTRUCTION.SUBMIT MANUFACTURER'S SPECIFICATIONS,
 INSTALLATION INSTRUCTIONS AND LISTING INFORMATION.
  
 8) R1004.1 GENERAL.
 FACTORY-BUILT FIREPLACES SHALL BE LISTED AND LABELED
 AND SHALL BE INSTALLED IN ACCORDANCE WITH THE
 CONDITIONS OF THE LISTING. FACTORY-BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH UL 127. SUBMIT
 MANUFACTURE'S SPECIFICATIONS, INSTALLATION INSTRUCTIONS
 AND LISTING INFORMATION.
  
 9) SHOW COMPLIANCE WITH R1005.1 EXTERIOR AIR.
 FACTORY-BUILT OR MASONRY FIREPLACES COVERED IN THIS
 CHAPTER SHALL BE EQUIPPED WITH AN EXTERIOR AIR SUPPLY
 TO ASSURE PROPER FUEL COMBUSTION UNLESS THE ROOM IS
 MECHANICALLY VENTILATED AND CONTROLLED SO THAT THE
 INDOOR PRESSURE IS NEUTRAL OR POSITIVE.
  
 10) PROVIDE A DETAIL OF THE SPIRAL STAIRS SHOWING
 COMPLIANCE WITH R311.5.8.1 SPIRAL STAIRWAYS AND R312.1
 FOR GUARDS.
 SPIRAL STAIRWAYS ARE PERMITTED, PROVIDED THE MINIMUM
 WIDTH SHALL BE 26 INCHES (660 MM) WITH EACH TREAD
 HAVING A 7-1/2-INCHES (190 MM) MINIMUM TREAD DEPTH AT
 12 INCHES FROM THE NARROWER EDGE. ALL TREADS SHALL BE
 IDENTICAL, AND THE RISE SHALL BE NO MORE THAN 9-1/2
 INCHES (241 MM). A MINIMUM HEADROOM OF 6 FEET 6 INCHES
 (1982 MM)SHALL BE PROVIDED. HANDRAILS SHALL BE PROVIDED
 ON ONE SIDE.
  
 11)SPECIFY HOW THE SECOND AND THIRD FLOOR DECKS WILL
 BE WATERPROOFED TO PROTECT THE INTERIOR SPACES BELOW.
 SUBMIT PRODUCT APPROVALS.
  
 12) FOR THE BALCONY GUARDRAILS SHOW COMPLIANCE WITH
 R312.2 GUARD OPENING LIMITATIONS.
 REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED
 FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE
 INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN
 DIAMETER.
  
 13) SPECIFY THE MEAN ROOF HEIGHT ON THE PLANS.
  
 14) PROVIDE DETAILS FOR THE ATTACHMENT OF THE 4 PLY
 GIRDERS TO THE EXISTING WALLS AND TO EACH OTHER. SEE
 THE SECOND FLOOR FRAMING PLAN ON A4. CLARIFY THAT THE 4
 PLY GIRDERS ARE BUILT-UP WITH 2 X 12 LUMBER. SPECIFY
 THE LUMBER TYPE AND GRADE.
  
 15) SPECIFY THE CONNECTORS FOR THE HIP GIRDER TRUSSES
 AT THE INTERMEDIATE ROOF FRAMING PLAN ON A4.
  
 16)THE POINT LOADING OF THE CUPOLA ON THE 2 X 12
 SECOND FLOOR FRAMING IS NOT ACCEPTABLE. PLEASE RECHECK
 THE DESIGN.
  
 17) SPECIFY THE BEAM/GIRDER THAT WILL BE INSTALLED TO
 SUPPORT THE SECOND FLOOR WALL AT THE NORTH EAST
 CORNER.
  
 18) REVISE THE ROOF SHEATHING FASTENING NOTES ON A4 TO
 COMPLY WITH R803.2.3.1. WHICH REQUIRES 8D RING SHANK
 NAILS IN ALL ROOF ZONES. THE FASTENER SPACING IN ROOF
 ZONE3 IS REQUIRED TO BE 4" OC FOR EDGES AND FIELD.
  
 19) PROVIDE A DETAIL TO CLARIFY THE UPPER ROOF PLAN.
 WHICH SHOWS 3/4" ROOF SHEATHING,R-30 INSULATION, T& G
 CEILING AND EXPOSED 4 X 8 TIMBERS.
  
 20) PLEASE UPDATE THE CONNECTORS SPECIFIED ON THE
 WINDOW OPENING DETAIL ON A2. HUGHES IS NO LONGER IN
 BUSINESS.
  
 21) THE SCALE SPECIFIED FOR THE ELEVATIONS ON A3 IS
 INCORRECT. IT SHOULD BE 1/4" SCALE.
  
 22) PROVIDE DETAILS OF THE ALUMINUM COLUMN AT THE FIRST
 FLOOR PORCH. ARE THE BASE AND CAP TO BE THE SAME AS THE
 STEEL COLUMN DETAILS?
  
 23) THE SIMPSON H10 CONNECTORS SPECIFIED FOR THE CUPOLA
 ROOF WILL NOT WORK WITH 4 X 8 RAFTERS. THE RAFTER
 OPENING IS ONLY 1-9/16".
  
 24) SUBMIT A TECHNICAL BULLETIN OR SPECIFICATION FROM
 SIMPSON INDICATING THAT THE H6 CONNECTOR CAN BE
 INSTALLED USING TAP CONS RATHER THAN NAILS.
  
 25) SUBMIT A TECHNICAL BULLETIN OR SPECIFICATION FROM
 SIMPSON INDICATING THAT THE TS 18 CONNECTOR CAN BE
 INSTALLED USING TAP CONS RATHER THAN NAILS.
  
 26) ON THE WALL SECTION ON A5 THE LUS 24 CONNECTOR FOR
 THE LOWER ROOF IS SHOWN AT THE WRONG LOCATION. PLEASE
 CORRECT.
  
 27) PROVIDE A DETAIL OF THE BALCONY KNEE WALL.
  
 28) INDICATE THE WIND LOAD PRESSURES FOR THE WINDOWS
 AND DOORS ON THE ELEVATIONS AT THE OPENING.
  
 29) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 30)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 31) THE UPLIFT FOR ROOF ZONE 3 (CORNERS) IN EXPOSURE C
 FOR A 27'-6 "MEAN ROOF HEIGHT IS -83.1 X 1.38 =
 -114.68 PSF, WHICH EXCEEDS THE DESIGN PRESSURE FOR THE
 METAL ROOFING OF -113.1 PSF.
  
 32) SUBMIT PRODUCT APPROVALS FOR THE ACCORDIAN TYPE
 DOORS SPECIFIED ON THE PLANS. THE ONES THAT WERE
 SUBMITTED ARE FOR SLIDING GLASS DOORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-08-26 Cont ID  
Sent By btrobaug Date 2008-08-26 Time 11:03 Rev Time 0.00
Received By btrobaug Date 2008-08-26 Time 10:49 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-25 Cont ID  
Sent By btrobaug Date 2008-01-25 Time 09:08 Rev Time 0.00
Received By btrobaug Date 2008-01-25 Time 06:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By btrobaug Date 2007-07-10 Time 10:02 Rev Time 0.00
Received By btrobaug Date 2007-07-10 Time 07:11 Sent To M
Notes
2007-07-10 08:55:34 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 1} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.408.4 CIRCUIT DIRECTORY OR CIRCUIT
 IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS THE SCHEDULE GIVEN DOES
 NOT REFLECT THE REQUIRED CIRCUITS PER 210.11.
  
 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE.LOCATE SAME ON PLANS
 TO INDICATE COMPLIANCE.
  
 3} THE AHU @ 5KW IN THE CALCULATION (AND PANEL
 SCHEDULE), SHEET E-1, DONOT MATCH THE SPECIFICATIONS ON
 SHEET MP-1, @ 9.6 KW. PLEASE CORRELATE.
  
 4} THE DISCONNECTING MEANS FOR THE RELOCATED CONDENSING
 UNITS MUST COMPLY WITH THE CLEARANCE REQUIREMENTS OF
 110.26.
  
 NOTE: REGARDING ELECTRICAL NOTE #18, SHEET E-1,
 ALTHOUGH THERE IS NO VIOLATION WITH THIS INSTALLATION,
 IT IS REQUIRED IN COMMERCIAL BUILDINGS ONLY. IF THE
 NOTE REMAINS ON THE PLAN, THE SYSTEM MUST BE INSTALLED
 OR A REVISION WILL BE REQUIRED TO REMOVE THE NOTE FROM
 THE PLAN. ALSO VERIFY NOTE #17.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 14:19 Rev Time 0.00
Received By adarroug Date 2008-08-20 Time 14:19 Sent To E
Notes
2008-08-20 14:20:24TO "BTROBAUG" DESK/RESUB--NEW SHEETS ALL TRADES--ZONING
 TO BE THE LAST REVIWER, PER "LMARTINEZ"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 13:57 Rev Time 0.00
Received By tgordon Date 2008-01-22 Time 13:57 Sent To M
Notes
2008-01-22 13:58:35TO "TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By jleech Date 2007-07-26 Time 08:14 Rev Time 0.00
Received By jleech Date 2007-07-05 Time 14:35 Sent To  
Notes
2007-07-05 14:36:08TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 11:49 Rev Time 1.00
Received By tgordon Date 2008-08-26 Time 11:49 Sent To P
Notes
2008-08-26 11:53:25*** PROVISO ***
 1) CEILING FANS TO BE INSTALLED, PER SUBMITTED ENERGY
 CALCULATIONS AND 2004 FBC 13-607.1.A.1.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-12 Cont ID  
Sent By tgordon Date 2008-02-12 Time 13:42 Rev Time 0.30
Received By tgordon Date 2008-02-12 Time 13:42 Sent To  
Notes
2008-02-12 13:48:19PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS PER MY CONVERSATION WITH ARCHITECT JAMES C. PAINE
 NEW MECHANICAL PLANS, ENERGY CALCULATIONS, AND COOLING
 LOAD CALCULATIONS THAT COINCIDE WITH EACH OTHER WILL BE
 SUBMITTED .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By btrobaug Date 2007-07-10 Time 09:19 Rev Time 0.45
Received By tgordon Date 2007-07-10 Time 14:27 Sent To P
Notes
2007-07-10 15:00:30*** DENIED ***
 1) ENERGY CALCULATIONS ARE SHOWING ONE 30,200 BTU A/C
 SYSTEM, PLANS PAGE MP-1 EQUIPMENT SCHEDULE IS SHOWING
 TWO 30,200 BTU A/C SYSTEMS THE TWO MUST COINCIDE,
 PLEASE CORRECT.
  
 2) ENERGY CALCULATIONS ARE SHOWING A 19 SEER A/C
 SYSTEM, PLANS PAGE MP-1 IS SHOWING TWO 13 SEER A/C
 SYSTEMS THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 3) ENERGY CALCULATIONS ARE TAKING A CREDIT FOR CEILING
 FAN, PLANS SHOW NO CEILING FANS, SEE 2004 FBC
 13-607.1.A.1, PLEASE CORRECT.
  
 4) PLANS SHOW THE AIR HANDLERS IN A CLOSET WITH A
 CLOTHES WASHER AND DRYER THIS MAY NOT BE DONE SEE 2004
 FBC 13-601.1.ABC.3.7, PLEASE CORRECT.
  
 5) PLEASE CORRECT COOLING LOAD CALCULATIONS (MANUAL J)
 TO SHOW TWO ZONES AND TWO SYSTEMS.
  
 6) PLEASE SUBMIT MECHANICAL PLANS THAT SHOW THE A/C
 DUCT DESIGN AND ALL OTHER PERTINENT INFORMATION.
  
 7) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR WOOD
 FIRE PLACE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-08-26 Cont ID  
Sent By mperson Date 2008-08-26 Time 13:24 Rev Time 0.00
Received By mperson Date 2008-08-26 Time 13:24 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By btrobaug Date 2008-08-26 Time 11:05 Rev Time 0.00
Received By jleech Date 2008-02-07 Time 14:56 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By jleech Date 2007-07-26 Time 08:00 Rev Time 0.00
Received By jleech Date 2007-07-26 Time 07:56 Sent To  
Notes
2007-07-26 08:13:41DENIED;
 1. THE AUTOMATIC CLOTHES WASHER SHALL DISCHARGE DOWN
 STREAM OF THE BATHROOM GROUP. FBC-2004 SECTION 909.1.
 2. PLUMBING RISER DIAGRAM ON PAGE MP-1, NOTE "DOWN TO
 BATHROOM BELOW". PLEASE SHOW WHERE 2ND FLOOR SANITARY
 WILL TIE INTO THE BUILDING DRAIN. MUST BE DOWN STREAM
 OF BATHROOM GROUP NOT INTO VENT FOR FIRST FLOOR
 BATHROOM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2009-12-21 Cont ID  
Sent By rbrown Date 2009-12-21 Time 11:34 Rev Time 0.00
Received By rbrown Date 2009-12-21 Time 11:34 Sent To  
Notes
2009-12-21 12:21:11DIANE WAS UNABLE TO ENTER AN INSPECTION CODE TO EXTEND
 THE PERMIT BECAUSE THERE ARE INSPECTION HOLDS.
 INSTRUCTED DIANE TO RELEASE THE HOLDS, ENTER THE
 INSPECTION NOTES TO EXTEND THE PERMIT, AND THEN PUT THE
 HOLDS BACK.

Review Stop Z ZONING
Rev No 3 Status P Date 2009-01-13 Cont ID  
Sent By mcruz Date 2009-01-13 Time 13:39 Rev Time 0.00
Received By mcruz Date 2009-01-13 Time 13:23 Sent To I
Notes
2008-09-07 10:40:11ZONING PASSED W/PROVISO: A LANDSCAPE PLAN SHALL BE
 SUBMITTED AND APPROVED PRIOR TO INITIAL INSPECTION.
  
 ERIC SCHNEIDER, PRINCIPLE PLANNER OR MAGGIE CRUZ,
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-24 Cont ID  
Sent By choops Date 2008-01-24 Time 12:21 Rev Time 0.00
Received By choops Date 2008-01-24 Time 12:21 Sent To E
Notes
2008-01-24 12:28:22***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)LOT ILLEGALLY SUBDIVIDED, PROVIDES NO ACCESS.
 PURSUANT TO ATTACHED LETTER, ISSUED MARCH 6, 2003, NO
 PERMITS FOR IMPROVEMENT SHALL BE ISSUED UNTIL ILLEGAL
 SUBDIVISION RESOLVED AND ROADWAY IS ESTABLISHED TO
 PROVIDE ACCESS.
  
  
 ***THE FOLLOWING REPEAT COMMENTS PROVIDED FYI ONLY:
  
 2)DOES NOT MEET SETBACK REQUIREMENTS.THERE IS NOT
 STREET ACCESS, SO A FRONT/REAR/SIDE CANNOT BE
 DETERMINED.HOWEVER, IF THE NORTH/SOUTH PROPERTY LINES
 WERE CONSIDERED THE SIDE, THE PROPOSED ADDITION WOULD
 NOT MEET THE SETBACK REQUIREMENTS.PURSUANT TO SECTION
 94-77 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS:
 MINIMUM REQUIRED SIDE SETBACK = 15 FT. (BOTH SIDES).
  
 3)THE NORTH ELEVATION SHOWS THE MEAN ROOF HEIGHT AT
 27'2" MEASURED FROM A.F.F., THE SOUTH AND EAST
 ELEVATIONS SHOW IT MEASURED FROM GRADE.PLEASE
 CLARIFY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-09 Cont ID  
Sent By choops Date 2007-07-09 Time 08:34 Rev Time 0.00
Received By choops Date 2007-07-09 Time 08:34 Sent To E
Notes
2007-07-09 08:42:41***FAILED***
  
  
 1)PLEASE PROVIDE SITE PLAN AND ELEVATION FOR
 PROPOSED WINDMILL, INCLUDE ALL DIMENSIONS AND SETBACK
 DIMENSIONS TO PROPERTY LINES.
  
 2)PROVIDE ELEVATION DIMENSIONS FROM GRADE TO THE
 MIDPOINT OF THE UPPERMOST ROOF'S PITCH.SHOW CHIMNEY
 DIMENSION.
  
 3)INDICATE ALL SETBACK DIMENSIONS FROM THE PROPOSED
 ADDITION TO THE PROPERTY LINES.
  
 NOTE:AS PER THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS, SECTION 94-77(2)(D):
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDINGS.SIDE: 15
 FT.
  
 4)PROVIDE OVERHANG DIMENSIONS.
  
 5)IF A/C UNIT IS NEW PROVIDE SETBACK DIMENSIONS TO
 THE PROPERTY LINES.
  
 6)LOTS ILLEGALLY SUBDIVIDED.PROVIDES NO ACCESS.NO
 PERMITS TO BE ISSUED UNTIL RESOLVED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720