Plan Review Details - Permit 07070044
Plan Review Stops For Permit 07070044
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-17 Cont ID  
Sent By kconrad Date 2008-01-16 Time 17:30 Rev Time 0.00
Received By kconrad Date 2008-01-16 Time 15:45 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By kconrad Date 2007-10-04 Time 19:02 Rev Time 0.00
Received By kconrad Date 2007-10-04 Time 16:10 Sent To I
Notes
2007-10-04 18:59:11PROJECT: 1801 SOUTH FLAGLER DRIVE, SUITE
 1903/#07070044
  
 PROJECT DETAILS: INTERIOR DEMOLITION/ALTERATION
  
 CODE REVIEW: 2004 FLORIDA BUILDING CODE/EXISTING
 BUILDING CODE WITH 2006 REVISIONS.
  
 STATUS: DENIED
  
  
 COMMENTS:
  
 (X) = COMPLIED
  
  
 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE
 MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS
 NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE.
 FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE
 PERMIT ISSUANCE.
  
 2)NEED TO FILE A NOTICE OF COMMENCEMENT, PER F. S.
 713.13 .
  
 (X) 3)301.5 . A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 (X) 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE
 FOLLOWING DATA:
  
 A) BUILDING CONSTRUCTION TYPE
 B) SPRINKLERED OR NON-SPRINKLERED.
  
 (X) 5)PLEASE CONTACT ALEX ORTEGA AT 561.355.3023 EXT.
 1148, AS PER THE FOLLOWING:
  
 105.9 ASBESTOS.
  
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER'S OR OPERATOR'S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 6) PLEASE PROVIDE DEMOLITION PLAN.
  
 (X) 7) PLEASE PROVIDE A DOOR SCHEDULE.
  
 (X) 8) INDICATE WALL TYPES AND CLARIFY TYPICAL INTERIOR
 PARTITION DETAIL. THE DETAIL INDICATES A 1/2 PLYWOOD
 SUB-FLOOR OVER LIGHT WEIGHT.
  
 (X) 9) PLEASE INDICATE FINISHED FLOOR COVERINGS.
  
 (X) 10) PLEASE PROVIDE DETAILS FOR FLOOR/CEILING/WALL
 PENETRATION FIRE PROTECTION.
  
 11) SUBMIT PRODUCT SPECIFICATIONS FOR TRANSLUCENT
 GLAZING.
  
 (X) 12) PLEASE INDICATE KITCHEN CLEARANCES AND COUNTER
 HEIGHTS.
  
 (X)13) PLEASE PROVIDE DETAILS FOR FLOATING GYPSUM BOARD
 CEILING.
  
 14) SUBMIT PRODUCT SPECIFICATIONS FOR SANDSTONE
 PANELS/SHOW EXTERIOR WALL SECTION/MECHANICAL
 ATTACHMENT/FASTENER TYPES/GAGE OF S.S.ANGLES.
  
 15) PLEASE INDICATE CEILING HEIGHTS AND INDICATE IF ALL
 EXISTING FLOORS ARE BUILT-UP.
  
 16) PLEASE SHOW DETAIL OF ENTRY DOOR THRESHOLD AND HOW
 IT WILL COMPLY WITH THE FAIR HOUSING ACT.
  
 17) THE SUBFLOOR IS SHOWN AS PLYWOOD. THE FOLLOWING
 SHALL APPLY:
  
 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II
 CONSTRUCTION.
 COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES
 OF BUILDINGS OF TYPE I OR II CONSTRUCTION.
 EXCEPTIONS:
 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 603.
 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
 3. CLASS A INTERIOR FINISH MATERIALS.
 4. COMBUSTIBLE PIPING WITHIN PARTITIONS OR ENCLOSED
 SHAFTS INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF
 THIS CODE. COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN
 CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE
 FLORIDA BUILDING CODE, PLUMBING.
  
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By kconrad Date 2007-07-23 Time 17:47 Rev Time 0.00
Received By kconrad Date 2007-07-23 Time 15:50 Sent To I
Notes
2007-07-23 15:55:28PROJECT: 1801 SOUTH FLAGLER DRIVE, SUITE
 1903/#07070044
  
 PROJECT DETAILS: INTERIOR DEMOLITION/ALTERATION
  
 CODE REVIEW: 2004 FLORIDA BUILDING CODE/EXISTING
 BUILDING CODE WITH 2006 REVISIONS.
  
 STATUS: DENIED
  
  
 COMMENTS:
  
  
 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE
 MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS
 NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE.
 FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE
 PERMIT ISSUANCE.
  
 2)NEED TO FILE A NOTICE OF COMMENCEMENT, PER F. S.
 713.13 .
  
 3)301.5 . A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE FOLLOWING
 DATA:
  
 A) BUILDING CONSTRUCTION TYPE
 B) SPRINKLERED OR NON-SPRINKLERED.
  
 5)PLEASE CONTACT ALEX ORTEGA AT 561.355.3023 EXT.
 1148, AS PER THE FOLLOWING:
  
 105.9 ASBESTOS.
  
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER'S OR OPERATOR'S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 6) PLEASE PROVIDE DEMOLITION PLAN.
  
 7) PLEASE PROVIDE A DOOR SCHEDULE.
  
 8) INDICATE WALL TYPES AND CLARIFY TYPICAL INTERIOR
 PARTITION DETAIL. THE DETAIL INDICATES A 1/2 PLYWOOD
 SUB-FLOOR OVER LIGHT WEIGHT.
  
 9) PLEASE INDICATE FINISHED FLOOR COVERINGS.
  
 10) PLEASE PROVIDE DETAILS FOR FLOOR/CEILING/WALL
 PENETRATION FIRE PROTECTION.
  
 11) SUBMIT PRODUCT SPECIFICATIONS FOR TRANSLUCENT
 GLAZING.
  
 12) PLEASE INDICATE KITCHEN CLEARANCES AND COUNTER
 HEIGHTS.
  
 13) PLEASE PROVIDE DETAILS FOR FLOATING GYPSUM BOARD
 CEILING.
  
 14) SUBMIT PRODUCT SPECIFICATIONS FOR SANDSTONE
 PANELS.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-08 Cont ID  
Sent By btrobaug Date 2008-01-08 Time 11:34 Rev Time 0.00
Received By btrobaug Date 2008-01-08 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-05 Cont ID  
Sent By btrobaug Date 2007-10-05 Time 14:57 Rev Time 0.00
Received By btrobaug Date 2007-10-05 Time 12:29 Sent To M
Notes
2007-10-05 14:17:59 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, *
 INDICATES FURTHER COMMENT FOR CLARITY.
  
 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED, FOR
 THE RESIDENCE SERVICE, AND THE EXISTING LOAD ON THE
 EQUIPMENT THATS TO FEED THE NEW SERVICE.* THE EXISTING
 LOAD CALCULATION AND RATING ARE NEEDED TO INSURE THE
 ADDED LOAD WILL NOT EXCEED THE SERVICE RATING OF THE
 GEAR. 230.79 NEC.
  
 5} PER 250.122 AN EQUIPMENT GROUNDING CONDUCTOR IS
 REQUIRED FROM THE FIRST MEANS OF DISCONNECT TO THE
 GUTTER, AND PANELS.* REQUIRED ON THE RISER DIAGRAM.
 215.5 NEC, 106.3.5.4 FBC AS AMENDED.
  
 7} INCLUDE BRANCH CIRCUIT WIRE SIZES ON PANEL SCHEDULES
 * THIS IS REQUIRED TO REVIEW FOR COMPLIANCE WITH 310.16
 AND240.4. NOTE #7 OF THE ELECTRICAL RESPONSES
 INDICATES ALL WIRE IS #12THERE ARE SEVERAL CIRCUIT
 BREAKERS LISTED OVER 20 AMPS.
  
 10} 210.52(B)(1) DINING ROOM CIRCUITS, VIOLATION,
 CIRCUIT 27B.* 210.52(B)(2) NO OTHER OUTLETS THE TWO OR
 MORE SMALL-APPLIANCE BRANCH CIRCUITS SPECIFIED IN
 210.52(B)(1) SHALL HAVE NO OTHER OUTLETS. SEE THE
 TERRACE IS LISTED ON THIS CIRCUIT.
  
 11} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE
 PLAN.
  
 12} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. PLEASE INDICATE SAME IN THE
 ELECTRICAL NOTES. REMOVE ALL REFERENCES OF NEW YORK
 CITY LICENSED ELECTRICIANS, BUREAU OF ELECTRICAL
 CONTROL AND OTHER REFERENCES NOT PERTINENT TO THIS
 APPLICATION, FROM THE ELECTRICAL SPECIFICATIONS. *
 COULD NOT FIND REFERENCE TO THE 2005 NEC.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD
 SHEETS TO EXPEDITE REVIEW AND SUBMIT WRITTEN RESPONSE
 TO THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By btrobaug Date 2007-07-11 Time 11:21 Rev Time 0.00
Received By btrobaug Date 2007-07-11 Time 07:24 Sent To  
Notes
2007-07-11 07:57:36 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.PUT A COMMENT REGARDING THIS IN THE ELECTRICAL
 SPECIFICATION.
  
 1} THE RISER IS NOT CLEAR AS TO THE MAINS, DISCONNECTS
 OR METER LOCATIONS. INDICATE THE EXISTING LOCATION AS
 WELL AS THE INTENDED LOCATION OF THE NEW METER AND MAIN
 DISCONNECT SHOWN ON THE RISER. (WHAT FLOOR, ELECTRICAL
 ROOM ETC.)
  
 2} INDICATE THE FEEDER CONDUCTOR TYPE ( IG: THHW,
 COPPER) AND CONDUIT TYPE FOR THE NEW FEEDER.
  
 3} SUBMIT THE SPECIFICATIONS (VOLTAGE, AMPERAGE, SYSTEM
 PHASE TYPE) OF THE EQUIPMENT THE PROPOSED FEED IS
 ORIGINATING FROM.
  
 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED, FOR
 THE RESIDENCE SERVICE, AND THE EXISTING LOAD ON THE
 EQUIPMENT THATS TO FEED THE NEW SERVICE.
  
 5} PER 250.122 AN EQUIPMENT GROUNDING CONDUCTOR IS
 REQUIRED FROM THE FIRST MEANS OF DISCONNECT TO THE
 GUTTER, AND PANELS.
  
 6} INDICATE THE GUTTER SIZE, SEE ARTICLE 376.22.
  
 7} INCLUDE BRANCH CIRCUIT WIRE SIZES ON PANEL
 SCHEDULES.
  
 8} CIRCUIT #21B DOES NOT COMPLY WITH 210.11(C)(3) BATH
 CIRCUIT, 20 AMP CIRCUIT.
  
 9} 210.11(C)(1) KITCHEN 20 AMP SMALL APPLIANCE
 CIRCUITS.REQUIRED . SEE ARTICLE.
  
 10} 210.52(B)(1) DINING ROOM CIRCUITS, VIOLATION,
 CIRCUIT 27B.
  
 11} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE
 PLAN.
  
 12} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. PLEASE INDICATE SAME IN THE
 ELECTRICAL NOTES. REMOVE ALL REFERENCES OF NEW YORK
 CITY LICENSED ELECTRICIANS, BUREAU OF ELECTRICAL
 CONTROL AND OTHER REFERENCES NOT PERTINENT TO THIS
 APPLICATION, FROM THE ELECTRICAL SPECIFICATIONS.
  
 13} THERE ARE FLOOR BOXES SHOWN ON THE PLAN. PROVIDE A
 DETAIL OF THE FLOOR STRUCTURE COMPONENTS AND A DETAIL ,
 INCLUDING DEPTHS OF CUTS, CONDUIT RUNS AND BOX
 SETTINGS. AN ENGINEER WILL NEED TO PERFOM TESTING TO
 VERIFY THE STRUCTURAL INTEGRITY OF THE FLOOR WILL NOT
 BE IN ANY WAY DIMINISHED BY THIS INSTALLATION. A LETTER
 FROM THE CONDOMINIUM MANAGEMENT ACKNOWLEDGING AWARENESS
 AND THEIR APPROVAL OF THIS INSTALLATION IS ALSO
 REQUIRED.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-01-16 Cont ID  
Sent By mwennerg Date 2008-01-16 Time 10:47 Rev Time 0.00
Received By mwennerg Date 2008-01-16 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-12 Cont ID  
Sent By mwennerg Date 2007-10-12 Time 14:53 Rev Time 0.00
Received By mwennerg Date 2007-10-12 Time 14:53 Sent To  
Notes
2007-10-12 14:59:26***DENIED***
  
 1) OK
  
 2) OK
  
 3) PROVIDE INTERIOR FINISH CLASSIFICATION FOR WALLS AND
 CEILING USING THE TERM CLASSA,B OR C.
  
 4) CLEARLY ILLUSTRATE THE LOCATION OF REQUIRED SMOKE
 ALARMS.
  
 5) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-27 Cont ID  
Sent By mwennerg Date 2007-07-27 Time 14:59 Rev Time 0.00
Received By mwennerg Date 2007-07-27 Time 14:59 Sent To  
Notes
2007-07-27 15:04:35***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
 PLEASE ADD ADOPTED EDITION TO GENERAL NOTES.
  
 2) WILL THIS WORK IMPACT ANY EXISTING FIRE PROTECTION
 EQUIPMENT?
  
 3) PLEASE INDICATE MINIMUM FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 4) PLEASE SHOW LOCATION OF REQUIRED SMOKE ALARMS THAT
 ARE REQUIRED TO BE HARD WIRED TO HOUSE ELECTRIC.
 ACTIVATION OF ONE (1) ALARM SHALL CAUSE ALL ALARMS IN
 UNIT TO ACTIVATE.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-07 Cont ID  
Sent By adarroug Date 2008-01-07 Time 09:34 Rev Time 0.00
Received By adarroug Date 2008-01-07 Time 09:34 Sent To  
Notes
2008-01-07 09:34:16TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 09:36 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 09:36 Sent To  
Notes
2007-10-03 16:39:05TO "BOB"#2
2007-09-28 09:36:25WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-27 Cont ID  
Sent By mwennerg Date 2007-07-27 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2007-07-06 Time 09:07 Sent To  
Notes
2007-07-10 14:09:15TO "BOB"#16
2007-07-06 09:07:53WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-01-11 Cont ID  
Sent By rregueir Date 2008-01-11 Time 15:48 Rev Time 0.00
Received By rregueir Date 2008-01-11 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-18 Cont ID  
Sent By rregueir Date 2007-10-18 Time 10:41 Rev Time 0.00
Received By rregueir Date 2007-10-18 Time 08:14 Sent To  
Notes
2007-10-18 10:41:08REVIEW #: 2
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. ENERGY CODE: THIS BUILDING IS A RESIDENTIAL BUILDING
 GREATER THAN 3 STORIES, THEREFORE IT IS SUBJECT TO FBC
 SUBCHAPTER 13-4, NOT 13-6. ALSO, METHOD A COMPLIANCE IS
 NOT AVAILABLE FOR THIS JOB AS IT IS NOT A WHOLE
 BUILDING. SEE FBC 13-400.0.C.4. THIS DOES NOT MEET THE
 DEFINITION OF A RENOVATION UNDER FBC 13-202.
  
 COMMENTS 2 THROUGH 5: OK
  
 6. THE KITCHEN EXHAUST IS NOT AN EXISTING CONDITION AND
 AS SUCH SHALL COMPLY WITH FBC,M 601.3. DUCT MAY BE
 ISOLATED FROM PLENUM AREAS OR THE FAN MAY BE LOCATED AT
 THE LOUVER TO ELIMINATE POSITIVE PRESSURE DUCT.
  
 7 THROUGH 9: OK
  
 10. OK, EXCEPT HOOD MANUFACTURER'S INSTRUCTIONS SHALL
 BE ON SITE AT TIME OF INSPECTION IN ACCORDANCE WITH
 FBC,M 304.1.
  
 11. WHETHER THE WORK IS IN ANOTHER CONDO OR A COMMON
 AREA, IT IS STILL OUTSIDE THE PROPERTY OF UNIT 1903,
 WHICH IS THE BOUNDARY OF THE SCOPE OF THIS PERMIT. ANY
 WORK PERFORMED OUTSIDE OF THIS BOUNDARY MAY NOT BE
 PERFORMED UNDER THE SCOPE OF THIS PERMIT. THE NAME AND
 ADDRESS OF THE OWNER OF THE REAL PROPERTY, AS WELL AS A
 LEGAL DESCRIPTION OF THE REAL PROPERTY WHERE THE WORK
 IS TO TAKE PLACE SHALL BE CONTAINED ON ALL PERMIT
 APPLICATIONS IN ACCORDANCE WITH F.S. 713.135(5)
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-20 Cont ID  
Sent By rregueir Date 2007-07-20 Time 16:05 Rev Time 0.00
Received By rregueir Date 2007-07-20 Time 15:33 Sent To  
Notes
2007-07-20 15:22:12--------------DENIED----------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO EQUIPMENT SCCHEDULE OR ENERGY CALCULATIONS WERE
 PROVIDED. FBC 106.3.5.1.4
  
 2. PG M-1 SHOWS CHILLED WATER BEING SUPPLIED TO FAN
 COIL UNITS. THIS BUILDING DOES NOT HAVE A CHILLED WATER
 SYSTEM. PG M-2 SHOWS A DIAGRAM FOR PIPING ON A
 WATER-COOLED HEAT PUMP. PLEASE COORDINATE DRAWINGS.
  
 3. AC NOTE #15. HOW IS CONDENSATE TO BE PIPED TO GRADE
 AT EXTERIOR OF THE BUILDING FROM THE 19TH FLOOR?
  
 4. NOTE ON M-1 SAYS "REFER TO DWG M103 FOR PIPING
 DIAGRAM." NO DRAWING M103 COULD BE FOUND IN PLANS.
  
 5. PG M-1 SHOWS TOILET EXHAUST DUCTS ATTACHING TO
 (EXISTING?) RISER. DUCT PENETRATIONS OF SHAFTS SHALL BE
 PROTECTED BY FIRE AND SMOKE DAMPERS PER FBC,M
 607.5.5.1. ALSO, PLAN SHOWS EXISTING EXHAUST DUCT TO BE
 CAPPED AT SHAFT. THIS BECOMES AN UNPROTECTED OPENING.
 THE DUCT PENETRATION SHOULD BE COMPLETELY REMOVED WITH
 THE SHAFT REPAIRED, OR A FIRE/SMOKE DAMPER IS
 REQUIRED.
  
 6. EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT BE
 LOCATED IN A PLENUM PER FBC,M 601.3. ALL 3 TX FANS AND
 KITCHEN HOOD SHOW EXHAUST DUCT UNDER POSITIVE PRESSURE
 IN THE PLENUM CEILING.
  
 7. PG M-1 NOTE ON FLOOR PLAN CALLS FOR NEOPRENE
 VIBRATION ISOLATORS IN THE PLENUM.MATERIALS EXPOSED
 WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84. FBC,M 602.2.1
  
 8. PLANS SHOW FCU'S ABOVE HARD CEILINGS THROUGHOUT THE
 SPACE. ACCESS FOR INSPECTION, SERVICE, REPAIR OR
 REPLACEMENT SHALL BE PROVIDED PER FBC,M 306.1 AND
 306.3.
  
 9. EACH HYDRONIC HEAT PUMP SHALL HAVE A TWO-POSITION
 AUTOMATIC VALVE INTERLOCKED TO SHUT OFF WATER FLOW WHEN
 THE COMPRESSOR IS OFF. FBC 13-411.1.ABC.1.4
  
 10. PLEASE PROVIDE PRODUCT APPROVAL FOR OUTDOOR LOUVER
 SHOWN AT OFFICE/GUEST ROOM. ALSO, PROVIDE SUBMITTAL FOR
 KITCHEN HOOD. FBC 106.1.1.
  
 11. NOTE ON FLOOR PLANS THAT A PORTION OF THE WORK TO
 BE DONE TO THE PIPING SYSTEM IS TO TAKE PLACEON THE
 18TH FLOOR. THE 18TH FLOOR IS OUTSIDE THE BOUNDARIES OF
 THE ADDRESS ON THIS PERMIT APPLICATION. IF ANY WORK IS
 TO BE DONE OUTSIDE OF THIS SPACE, PLEASE COORDINATE
 WITH ANY OTHER PROPERTY OWNER WHO'S SPACE MAY BE
 AFFECTED AS WELL AS BUILDING MANAGEMENT. ADDITIONAL
 PERMITS WILL BE REQUIRED FOR ANY WORK TO BE DONE
 OUTSIDE THIS SPACE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-18 Cont ID  
Sent By jleech Date 2008-01-18 Time 09:02 Rev Time 0.00
Received By jleech Date 2008-01-18 Time 09:02 Sent To  
Notes
2008-01-18 09:04:46THE ARCHITECT RED LINE DRAWINGS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-01-09 Cont ID  
Sent By jleech Date 2008-01-09 Time 09:24 Rev Time 0.00
Received By jleech Date 2008-01-09 Time 08:39 Sent To  
Notes
2008-01-09 09:53:19DENIED;
 LAST PLUMBING REVIEW COMMENTS WERE NOT ADDRESSED; COPY
 OF LAST PLAN REVIEW ATTACHED
 1. (NOT ADDRESSED) PAGE M-3 "COLD WATER MAKE-UP DETAIL"
 JUMPER AROUND BACKFLOW PREVENTER IS NOT PERMITED.
 SUBMIT INFORMATION ON BACKFLOW TO BE INSTALLED.
 2. (NOT ADDRESSED) SANITARY RISER DIAGRAM; (ONE SET
 MARKED)
 A)KITCHEN SINK SHOWN IN TWO PLACES, SINK
 CANNOT DISCHARGE THRU A BATHROOM GROUP. SECTION 909.1.
 B) HORIZONTAL DRY VENTS NOT PERMITED
 SECTION 905.3
 C) W/M STAND PIPE NOT REQUIRED TO HAVE AN
 AIR HAMMER DEVISE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-20 Cont ID  
Sent By jleech Date 2007-10-20 Time 09:23 Rev Time 0.00
Received By jleech Date 2007-10-20 Time 08:55 Sent To  
Notes
2007-10-20 09:46:02DENIED;
 1. PAGE M-3 COLD WATER MAKE-UP DETAIL; 1" COLD WATER
 JUMPER AROUND BACKFLOW PREVENTER NOT PERMITED. CHECK
 VALVES CAN NOT BE TESTED AND MAY FAIL (INSTALLED ON
 BY-PASS). SUBMIT MANUFACTURE AND MOTEL NUMBER OF
 BACKFLOW.
 2. SANITARY RISER DIAGRAM; ( MARKED ON ONE SET OF
 PLANS.
 A) 2 KITCHEN SINKS SHOWN ON RISER DIAGRAM ONLY
 ONE ON PLANS, PLEASE CORRECT.
 B) HORIZONTALDRY VENTS NOT PERMITED SEE FBC
 PLUMBING SECTION 905.3
 C) AUTOMATIC CLOTHES WASHER STAND PIPE IS NOT
 REQUIRED TO HAVE AN AIR HAMMER DEVISE IN THE DRAINAGE
 SYSTEM PLEASE REMOVE.
 D)AIR ADMITTANCE VALVE IS NOT REQUIRED IF THE
 WASTE ARE IS LESS THAN 6 FEET. SHOW ON PLANS. FBC
 PLUMBING 906.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By jleech Date 2007-07-26 Time 07:13 Rev Time 0.00
Received By jleech Date 2007-07-26 Time 07:13 Sent To  
Notes
2007-07-26 07:20:46DENIED;
 1. ADD NOTE TO PLAN; ICE MACHINE DISCHARGE THROUGH AN
 AIR GAP FITTING.
 2. PLUMBING FLOOR PLAN SHOWS TWO WATER HEATERS WATER
 RISER DIAGRAM SHOWS ONLY ONE. PLEASE EXPLAIN.
 3.SHOW DEMO PLAN. ITS NOT CLEAR WHAT PLUMBING IS BEING
 ALTERED.
 4. SUPPLY CUT SHEET ON HEAT PUMP.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 08:55 Rev Time 0.00
Received By choops Date 2007-07-23 Time 08:55 Sent To  
Notes
2007-07-23 08:55:15*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved