| Plan Review Stops For Permit 07070044 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2008-01-16 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2008-01-16 |
Time |
15:45 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-04 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2007-10-04 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2007-10-04 |
Time |
16:10 |
Sent To |
I |
|
| Notes |
| 2007-10-04 18:59:11 | PROJECT: 1801 SOUTH FLAGLER DRIVE, SUITE | | | 1903/#07070044 | | | | | | PROJECT DETAILS: INTERIOR DEMOLITION/ALTERATION | | | | | | CODE REVIEW: 2004 FLORIDA BUILDING CODE/EXISTING | | | BUILDING CODE WITH 2006 REVISIONS. | | | | | | STATUS: DENIED | | | | | | | | | COMMENTS: | | | | | | (X) = COMPLIED | | | | | | | | | 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE | | | MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS | | | NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE. | | | FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE | | | PERMIT ISSUANCE. | | | | | | 2)NEED TO FILE A NOTICE OF COMMENCEMENT, PER F. S. | | | 713.13 . | | | | | | (X) 3)301.5 . A DESIGN PROFESSIONAL OR AN OWNER MUST | | | ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION | | | PURSUANT TO SECTION | | | 303,304 & 305 OF THIS CODE. | | | | | | (X) 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE | | | FOLLOWING DATA: | | | | | | A) BUILDING CONSTRUCTION TYPE | | | B) SPRINKLERED OR NON-SPRINKLERED. | | | | | | (X) 5)PLEASE CONTACT ALEX ORTEGA AT 561.355.3023 EXT. | | | 1148, AS PER THE FOLLOWING: | | | | | | 105.9 ASBESTOS. | | | | | | THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT | | | FOR THE DEMOLITION OR RENOVATION OF AN EXISTING | | | STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT | | | WHICH INDICATES THE OWNER'S OR OPERATOR'S | | | RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION | | | 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT | | | OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO | | | REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH | | | STATE AND FEDERAL LAW. | | | | | | 6) PLEASE PROVIDE DEMOLITION PLAN. | | | | | | (X) 7) PLEASE PROVIDE A DOOR SCHEDULE. | | | | | | (X) 8) INDICATE WALL TYPES AND CLARIFY TYPICAL INTERIOR | | | PARTITION DETAIL. THE DETAIL INDICATES A 1/2 PLYWOOD | | | SUB-FLOOR OVER LIGHT WEIGHT. | | | | | | (X) 9) PLEASE INDICATE FINISHED FLOOR COVERINGS. | | | | | | (X) 10) PLEASE PROVIDE DETAILS FOR FLOOR/CEILING/WALL | | | PENETRATION FIRE PROTECTION. | | | | | | 11) SUBMIT PRODUCT SPECIFICATIONS FOR TRANSLUCENT | | | GLAZING. | | | | | | (X) 12) PLEASE INDICATE KITCHEN CLEARANCES AND COUNTER | | | HEIGHTS. | | | | | | (X)13) PLEASE PROVIDE DETAILS FOR FLOATING GYPSUM BOARD | | | CEILING. | | | | | | 14) SUBMIT PRODUCT SPECIFICATIONS FOR SANDSTONE | | | PANELS/SHOW EXTERIOR WALL SECTION/MECHANICAL | | | ATTACHMENT/FASTENER TYPES/GAGE OF S.S.ANGLES. | | | | | | 15) PLEASE INDICATE CEILING HEIGHTS AND INDICATE IF ALL | | | EXISTING FLOORS ARE BUILT-UP. | | | | | | 16) PLEASE SHOW DETAIL OF ENTRY DOOR THRESHOLD AND HOW | | | IT WILL COMPLY WITH THE FAIR HOUSING ACT. | | | | | | 17) THE SUBFLOOR IS SHOWN AS PLYWOOD. THE FOLLOWING | | | SHALL APPLY: | | | | | | 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II | | | CONSTRUCTION. | | | COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES | | | OF BUILDINGS OF TYPE I OR II CONSTRUCTION. | | | EXCEPTIONS: | | | 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION | | | 603. | | | 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF | | | THE FLORIDA BUILDING CODE, MECHANICAL. | | | 3. CLASS A INTERIOR FINISH MATERIALS. | | | 4. COMBUSTIBLE PIPING WITHIN PARTITIONS OR ENCLOSED | | | SHAFTS INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF | | | THIS CODE. COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN | | | CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE | | | WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE | | | FLORIDA BUILDING CODE, PLUMBING. | | | | | | | | | | | | PLAN REVIEW: KEN CONRAD | | | PHONE: 561.805.6666 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-23 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2007-07-23 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2007-07-23 |
Time |
15:50 |
Sent To |
I |
|
| Notes |
| 2007-07-23 15:55:28 | PROJECT: 1801 SOUTH FLAGLER DRIVE, SUITE | | | 1903/#07070044 | | | | | | PROJECT DETAILS: INTERIOR DEMOLITION/ALTERATION | | | | | | CODE REVIEW: 2004 FLORIDA BUILDING CODE/EXISTING | | | BUILDING CODE WITH 2006 REVISIONS. | | | | | | STATUS: DENIED | | | | | | | | | COMMENTS: | | | | | | | | | 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE | | | MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS | | | NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE. | | | FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE | | | PERMIT ISSUANCE. | | | | | | 2)NEED TO FILE A NOTICE OF COMMENCEMENT, PER F. S. | | | 713.13 . | | | | | | 3)301.5 . A DESIGN PROFESSIONAL OR AN OWNER MUST | | | ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION | | | PURSUANT TO SECTION | | | 303,304 & 305 OF THIS CODE. | | | | | | 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE FOLLOWING | | | DATA: | | | | | | A) BUILDING CONSTRUCTION TYPE | | | B) SPRINKLERED OR NON-SPRINKLERED. | | | | | | 5)PLEASE CONTACT ALEX ORTEGA AT 561.355.3023 EXT. | | | 1148, AS PER THE FOLLOWING: | | | | | | 105.9 ASBESTOS. | | | | | | THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT | | | FOR THE DEMOLITION OR RENOVATION OF AN EXISTING | | | STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT | | | WHICH INDICATES THE OWNER'S OR OPERATOR'S | | | RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION | | | 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT | | | OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO | | | REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH | | | STATE AND FEDERAL LAW. | | | | | | 6) PLEASE PROVIDE DEMOLITION PLAN. | | | | | | 7) PLEASE PROVIDE A DOOR SCHEDULE. | | | | | | 8) INDICATE WALL TYPES AND CLARIFY TYPICAL INTERIOR | | | PARTITION DETAIL. THE DETAIL INDICATES A 1/2 PLYWOOD | | | SUB-FLOOR OVER LIGHT WEIGHT. | | | | | | 9) PLEASE INDICATE FINISHED FLOOR COVERINGS. | | | | | | 10) PLEASE PROVIDE DETAILS FOR FLOOR/CEILING/WALL | | | PENETRATION FIRE PROTECTION. | | | | | | 11) SUBMIT PRODUCT SPECIFICATIONS FOR TRANSLUCENT | | | GLAZING. | | | | | | 12) PLEASE INDICATE KITCHEN CLEARANCES AND COUNTER | | | HEIGHTS. | | | | | | 13) PLEASE PROVIDE DETAILS FOR FLOATING GYPSUM BOARD | | | CEILING. | | | | | | 14) SUBMIT PRODUCT SPECIFICATIONS FOR SANDSTONE | | | PANELS. | | | | | | PLAN REVIEW: KEN CONRAD | | | PHONE: 561.805.6666 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-08 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-08 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-05 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-05 |
Time |
12:29 |
Sent To |
M |
|
| Notes |
| 2007-10-05 14:17:59 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, * | | | INDICATES FURTHER COMMENT FOR CLARITY. | | | | | | 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, | | | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED, FOR | | | THE RESIDENCE SERVICE, AND THE EXISTING LOAD ON THE | | | EQUIPMENT THATS TO FEED THE NEW SERVICE.* THE EXISTING | | | LOAD CALCULATION AND RATING ARE NEEDED TO INSURE THE | | | ADDED LOAD WILL NOT EXCEED THE SERVICE RATING OF THE | | | GEAR. 230.79 NEC. | | | | | | 5} PER 250.122 AN EQUIPMENT GROUNDING CONDUCTOR IS | | | REQUIRED FROM THE FIRST MEANS OF DISCONNECT TO THE | | | GUTTER, AND PANELS.* REQUIRED ON THE RISER DIAGRAM. | | | 215.5 NEC, 106.3.5.4 FBC AS AMENDED. | | | | | | 7} INCLUDE BRANCH CIRCUIT WIRE SIZES ON PANEL SCHEDULES | | | * THIS IS REQUIRED TO REVIEW FOR COMPLIANCE WITH 310.16 | | | AND240.4. NOTE #7 OF THE ELECTRICAL RESPONSES | | | INDICATES ALL WIRE IS #12THERE ARE SEVERAL CIRCUIT | | | BREAKERS LISTED OVER 20 AMPS. | | | | | | 10} 210.52(B)(1) DINING ROOM CIRCUITS, VIOLATION, | | | CIRCUIT 27B.* 210.52(B)(2) NO OTHER OUTLETS THE TWO OR | | | MORE SMALL-APPLIANCE BRANCH CIRCUITS SPECIFIED IN | | | 210.52(B)(1) SHALL HAVE NO OTHER OUTLETS. SEE THE | | | TERRACE IS LISTED ON THIS CIRCUIT. | | | | | | 11} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE | | | PLAN. | | | | | | 12} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE | | | EFFECTIVE 8 DECEMBER 2006. PLEASE INDICATE SAME IN THE | | | ELECTRICAL NOTES. REMOVE ALL REFERENCES OF NEW YORK | | | CITY LICENSED ELECTRICIANS, BUREAU OF ELECTRICAL | | | CONTROL AND OTHER REFERENCES NOT PERTINENT TO THIS | | | APPLICATION, FROM THE ELECTRICAL SPECIFICATIONS. * | | | COULD NOT FIND REFERENCE TO THE 2005 NEC. | | | | | | PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD | | | SHEETS TO EXPEDITE REVIEW AND SUBMIT WRITTEN RESPONSE | | | TO THE COMMENTS MADE IN THIS REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-07-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-11 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-11 |
Time |
07:24 |
Sent To |
|
|
| Notes |
| 2007-07-11 07:57:36 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE | | | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE | | | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE | | | ARTICLE.PUT A COMMENT REGARDING THIS IN THE ELECTRICAL | | | SPECIFICATION. | | | | | | 1} THE RISER IS NOT CLEAR AS TO THE MAINS, DISCONNECTS | | | OR METER LOCATIONS. INDICATE THE EXISTING LOCATION AS | | | WELL AS THE INTENDED LOCATION OF THE NEW METER AND MAIN | | | DISCONNECT SHOWN ON THE RISER. (WHAT FLOOR, ELECTRICAL | | | ROOM ETC.) | | | | | | 2} INDICATE THE FEEDER CONDUCTOR TYPE ( IG: THHW, | | | COPPER) AND CONDUIT TYPE FOR THE NEW FEEDER. | | | | | | 3} SUBMIT THE SPECIFICATIONS (VOLTAGE, AMPERAGE, SYSTEM | | | PHASE TYPE) OF THE EQUIPMENT THE PROPOSED FEED IS | | | ORIGINATING FROM. | | | | | | 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, | | | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED, FOR | | | THE RESIDENCE SERVICE, AND THE EXISTING LOAD ON THE | | | EQUIPMENT THATS TO FEED THE NEW SERVICE. | | | | | | 5} PER 250.122 AN EQUIPMENT GROUNDING CONDUCTOR IS | | | REQUIRED FROM THE FIRST MEANS OF DISCONNECT TO THE | | | GUTTER, AND PANELS. | | | | | | 6} INDICATE THE GUTTER SIZE, SEE ARTICLE 376.22. | | | | | | 7} INCLUDE BRANCH CIRCUIT WIRE SIZES ON PANEL | | | SCHEDULES. | | | | | | 8} CIRCUIT #21B DOES NOT COMPLY WITH 210.11(C)(3) BATH | | | CIRCUIT, 20 AMP CIRCUIT. | | | | | | 9} 210.11(C)(1) KITCHEN 20 AMP SMALL APPLIANCE | | | CIRCUITS.REQUIRED . SEE ARTICLE. | | | | | | 10} 210.52(B)(1) DINING ROOM CIRCUITS, VIOLATION, | | | CIRCUIT 27B. | | | | | | 11} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE | | | PLAN. | | | | | | 12} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE | | | EFFECTIVE 8 DECEMBER 2006. PLEASE INDICATE SAME IN THE | | | ELECTRICAL NOTES. REMOVE ALL REFERENCES OF NEW YORK | | | CITY LICENSED ELECTRICIANS, BUREAU OF ELECTRICAL | | | CONTROL AND OTHER REFERENCES NOT PERTINENT TO THIS | | | APPLICATION, FROM THE ELECTRICAL SPECIFICATIONS. | | | | | | 13} THERE ARE FLOOR BOXES SHOWN ON THE PLAN. PROVIDE A | | | DETAIL OF THE FLOOR STRUCTURE COMPONENTS AND A DETAIL , | | | INCLUDING DEPTHS OF CUTS, CONDUIT RUNS AND BOX | | | SETTINGS. AN ENGINEER WILL NEED TO PERFOM TESTING TO | | | VERIFY THE STRUCTURAL INTEGRITY OF THE FLOOR WILL NOT | | | BE IN ANY WAY DIMINISHED BY THIS INSTALLATION. A LETTER | | | FROM THE CONDOMINIUM MANAGEMENT ACKNOWLEDGING AWARENESS | | | AND THEIR APPROVAL OF THIS INSTALLATION IS ALSO | | | REQUIRED. | | | | | | PLEASE REMOVE OLD SHEETS, INSERT NEW | | | ONES, SUBMIT OLD SHEETS TO EXPEDITE | | | REVIEW AND SUBMIT WRITTEN RESPONSE TO | | | THE COMMENTS MADE IN THIS REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-01-16 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-01-16 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-10-12 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-10-12 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2007-10-12 14:59:26 | ***DENIED*** | | | | | | 1) OK | | | | | | 2) OK | | | | | | 3) PROVIDE INTERIOR FINISH CLASSIFICATION FOR WALLS AND | | | CEILING USING THE TERM CLASSA,B OR C. | | | | | | 4) CLEARLY ILLUSTRATE THE LOCATION OF REQUIRED SMOKE | | | ALARMS. | | | | | | 5) OK | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-27 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-27 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2007-07-27 15:04:35 | ***DENIED*** | | | | | | 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | PLEASE ADD ADOPTED EDITION TO GENERAL NOTES. | | | | | | 2) WILL THIS WORK IMPACT ANY EXISTING FIRE PROTECTION | | | EQUIPMENT? | | | | | | 3) PLEASE INDICATE MINIMUM FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 4) PLEASE SHOW LOCATION OF REQUIRED SMOKE ALARMS THAT | | | ARE REQUIRED TO BE HARD WIRED TO HOUSE ELECTRIC. | | | ACTIVATION OF ONE (1) ALARM SHALL CAUSE ALL ALARMS IN | | | UNIT TO ACTIVATE. | | | | | | 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-07 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-07 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2008-01-07 09:34:16 | TO "BOB"#9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-28 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-28 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2007-10-03 16:39:05 | TO "BOB"#2 | | 2007-09-28 09:36:25 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-27 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-06 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2007-07-10 14:09:15 | TO "BOB"#16 | | 2007-07-06 09:07:53 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-01-11 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-01-11 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-18 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-18 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2007-10-18 10:41:08 | REVIEW #: 2 | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. ENERGY CODE: THIS BUILDING IS A RESIDENTIAL BUILDING | | | GREATER THAN 3 STORIES, THEREFORE IT IS SUBJECT TO FBC | | | SUBCHAPTER 13-4, NOT 13-6. ALSO, METHOD A COMPLIANCE IS | | | NOT AVAILABLE FOR THIS JOB AS IT IS NOT A WHOLE | | | BUILDING. SEE FBC 13-400.0.C.4. THIS DOES NOT MEET THE | | | DEFINITION OF A RENOVATION UNDER FBC 13-202. | | | | | | COMMENTS 2 THROUGH 5: OK | | | | | | 6. THE KITCHEN EXHAUST IS NOT AN EXISTING CONDITION AND | | | AS SUCH SHALL COMPLY WITH FBC,M 601.3. DUCT MAY BE | | | ISOLATED FROM PLENUM AREAS OR THE FAN MAY BE LOCATED AT | | | THE LOUVER TO ELIMINATE POSITIVE PRESSURE DUCT. | | | | | | 7 THROUGH 9: OK | | | | | | 10. OK, EXCEPT HOOD MANUFACTURER'S INSTRUCTIONS SHALL | | | BE ON SITE AT TIME OF INSPECTION IN ACCORDANCE WITH | | | FBC,M 304.1. | | | | | | 11. WHETHER THE WORK IS IN ANOTHER CONDO OR A COMMON | | | AREA, IT IS STILL OUTSIDE THE PROPERTY OF UNIT 1903, | | | WHICH IS THE BOUNDARY OF THE SCOPE OF THIS PERMIT. ANY | | | WORK PERFORMED OUTSIDE OF THIS BOUNDARY MAY NOT BE | | | PERFORMED UNDER THE SCOPE OF THIS PERMIT. THE NAME AND | | | ADDRESS OF THE OWNER OF THE REAL PROPERTY, AS WELL AS A | | | LEGAL DESCRIPTION OF THE REAL PROPERTY WHERE THE WORK | | | IS TO TAKE PLACE SHALL BE CONTAINED ON ALL PERMIT | | | APPLICATIONS IN ACCORDANCE WITH F.S. 713.135(5) | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-20 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-07-20 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2007-07-20 15:22:12 | --------------DENIED---------------- | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NO EQUIPMENT SCCHEDULE OR ENERGY CALCULATIONS WERE | | | PROVIDED. FBC 106.3.5.1.4 | | | | | | 2. PG M-1 SHOWS CHILLED WATER BEING SUPPLIED TO FAN | | | COIL UNITS. THIS BUILDING DOES NOT HAVE A CHILLED WATER | | | SYSTEM. PG M-2 SHOWS A DIAGRAM FOR PIPING ON A | | | WATER-COOLED HEAT PUMP. PLEASE COORDINATE DRAWINGS. | | | | | | 3. AC NOTE #15. HOW IS CONDENSATE TO BE PIPED TO GRADE | | | AT EXTERIOR OF THE BUILDING FROM THE 19TH FLOOR? | | | | | | 4. NOTE ON M-1 SAYS "REFER TO DWG M103 FOR PIPING | | | DIAGRAM." NO DRAWING M103 COULD BE FOUND IN PLANS. | | | | | | 5. PG M-1 SHOWS TOILET EXHAUST DUCTS ATTACHING TO | | | (EXISTING?) RISER. DUCT PENETRATIONS OF SHAFTS SHALL BE | | | PROTECTED BY FIRE AND SMOKE DAMPERS PER FBC,M | | | 607.5.5.1. ALSO, PLAN SHOWS EXISTING EXHAUST DUCT TO BE | | | CAPPED AT SHAFT. THIS BECOMES AN UNPROTECTED OPENING. | | | THE DUCT PENETRATION SHOULD BE COMPLETELY REMOVED WITH | | | THE SHAFT REPAIRED, OR A FIRE/SMOKE DAMPER IS | | | REQUIRED. | | | | | | 6. EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT BE | | | LOCATED IN A PLENUM PER FBC,M 601.3. ALL 3 TX FANS AND | | | KITCHEN HOOD SHOW EXHAUST DUCT UNDER POSITIVE PRESSURE | | | IN THE PLENUM CEILING. | | | | | | 7. PG M-1 NOTE ON FLOOR PLAN CALLS FOR NEOPRENE | | | VIBRATION ISOLATORS IN THE PLENUM.MATERIALS EXPOSED | | | WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A | | | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED | | | IN ACCORDANCE WITH ASTM E 84. FBC,M 602.2.1 | | | | | | 8. PLANS SHOW FCU'S ABOVE HARD CEILINGS THROUGHOUT THE | | | SPACE. ACCESS FOR INSPECTION, SERVICE, REPAIR OR | | | REPLACEMENT SHALL BE PROVIDED PER FBC,M 306.1 AND | | | 306.3. | | | | | | 9. EACH HYDRONIC HEAT PUMP SHALL HAVE A TWO-POSITION | | | AUTOMATIC VALVE INTERLOCKED TO SHUT OFF WATER FLOW WHEN | | | THE COMPRESSOR IS OFF. FBC 13-411.1.ABC.1.4 | | | | | | 10. PLEASE PROVIDE PRODUCT APPROVAL FOR OUTDOOR LOUVER | | | SHOWN AT OFFICE/GUEST ROOM. ALSO, PROVIDE SUBMITTAL FOR | | | KITCHEN HOOD. FBC 106.1.1. | | | | | | 11. NOTE ON FLOOR PLANS THAT A PORTION OF THE WORK TO | | | BE DONE TO THE PIPING SYSTEM IS TO TAKE PLACEON THE | | | 18TH FLOOR. THE 18TH FLOOR IS OUTSIDE THE BOUNDARIES OF | | | THE ADDRESS ON THIS PERMIT APPLICATION. IF ANY WORK IS | | | TO BE DONE OUTSIDE OF THIS SPACE, PLEASE COORDINATE | | | WITH ANY OTHER PROPERTY OWNER WHO'S SPACE MAY BE | | | AFFECTED AS WELL AS BUILDING MANAGEMENT. ADDITIONAL | | | PERMITS WILL BE REQUIRED FOR ANY WORK TO BE DONE | | | OUTSIDE THIS SPACE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-01-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-01-18 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-01-18 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2008-01-18 09:04:46 | THE ARCHITECT RED LINE DRAWINGS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2008-01-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-01-09 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-01-09 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2008-01-09 09:53:19 | DENIED; | | | LAST PLUMBING REVIEW COMMENTS WERE NOT ADDRESSED; COPY | | | OF LAST PLAN REVIEW ATTACHED | | | 1. (NOT ADDRESSED) PAGE M-3 "COLD WATER MAKE-UP DETAIL" | | | JUMPER AROUND BACKFLOW PREVENTER IS NOT PERMITED. | | | SUBMIT INFORMATION ON BACKFLOW TO BE INSTALLED. | | | 2. (NOT ADDRESSED) SANITARY RISER DIAGRAM; (ONE SET | | | MARKED) | | | A)KITCHEN SINK SHOWN IN TWO PLACES, SINK | | | CANNOT DISCHARGE THRU A BATHROOM GROUP. SECTION 909.1. | | | B) HORIZONTAL DRY VENTS NOT PERMITED | | | SECTION 905.3 | | | C) W/M STAND PIPE NOT REQUIRED TO HAVE AN | | | AIR HAMMER DEVISE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-10-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-10-20 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-10-20 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2007-10-20 09:46:02 | DENIED; | | | 1. PAGE M-3 COLD WATER MAKE-UP DETAIL; 1" COLD WATER | | | JUMPER AROUND BACKFLOW PREVENTER NOT PERMITED. CHECK | | | VALVES CAN NOT BE TESTED AND MAY FAIL (INSTALLED ON | | | BY-PASS). SUBMIT MANUFACTURE AND MOTEL NUMBER OF | | | BACKFLOW. | | | 2. SANITARY RISER DIAGRAM; ( MARKED ON ONE SET OF | | | PLANS. | | | A) 2 KITCHEN SINKS SHOWN ON RISER DIAGRAM ONLY | | | ONE ON PLANS, PLEASE CORRECT. | | | B) HORIZONTALDRY VENTS NOT PERMITED SEE FBC | | | PLUMBING SECTION 905.3 | | | C) AUTOMATIC CLOTHES WASHER STAND PIPE IS NOT | | | REQUIRED TO HAVE AN AIR HAMMER DEVISE IN THE DRAINAGE | | | SYSTEM PLEASE REMOVE. | | | D)AIR ADMITTANCE VALVE IS NOT REQUIRED IF THE | | | WASTE ARE IS LESS THAN 6 FEET. SHOW ON PLANS. FBC | | | PLUMBING 906.1 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-26 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-26 |
Time |
07:13 |
Sent To |
|
|
| Notes |
| 2007-07-26 07:20:46 | DENIED; | | | 1. ADD NOTE TO PLAN; ICE MACHINE DISCHARGE THROUGH AN | | | AIR GAP FITTING. | | | 2. PLUMBING FLOOR PLAN SHOWS TWO WATER HEATERS WATER | | | RISER DIAGRAM SHOWS ONLY ONE. PLEASE EXPLAIN. | | | 3.SHOW DEMO PLAN. ITS NOT CLEAR WHAT PLUMBING IS BEING | | | ALTERED. | | | 4. SUPPLY CUT SHEET ON HEAT PUMP. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-23 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-23 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-23 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2007-07-23 08:55:15 | *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|