Plan Review Details - Permit 07070042
Plan Review Stops For Permit 07070042
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-17 Cont ID  
Sent By amorse Date 2008-01-17 Time 16:16 Rev Time 0.00
Received By amorse Date 2008-01-17 Time 16:16 Sent To PC
Notes
2008-01-17 16:19:19 
  
 PASSED
  
 REVISION FOR HELICAL PILES AND FOUNDATION
 MODIFICATIONS, THREE PAGES SHEET #'S 7, 7A AND 8
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-27 Cont ID  
Sent By amorse Date 2007-10-27 Time 08:56 Rev Time 0.00
Received By amorse Date 2007-10-27 Time 08:56 Sent To PC
Notes
2007-10-27 09:03:38 
  
 PASSED
  
 1)RAS 117 CALCULATIONS ARE INCORRECTLY BASED ON A -45
 PSF, ALL NON INSULATED ROOFING ASSEMBLIES THAT ARE -45
 PSF ARE LIMITATION #9 WHICH DO NOT ALLOW FOR ENHANCED
 FASTENING TO BE CALCULATED SEE PAGE 34 OF NOA THE
 ASSEMBLY THAT YOU ARE USING, BASED ON SHEET 6 OF THE
 DRAWING IS ON PAGE 33 OF THE NOA AND HAS A DESIGN
 PRESSURE OF -52.5 WITH THE 6" O/C PATTERN THAT YOU USED
 IN YOUR CALCULATIONS
  
 *****PLEASE SUBMIT NEW CALCULATIONS TO THE INSPECTOR AT
 TIME OF INSPECTION*****
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-06 Cont ID  
Sent By amorse Date 2007-10-06 Time 08:54 Rev Time 0.00
Received By amorse Date 2007-10-06 Time 08:54 Sent To PC
Notes
2007-10-06 09:46:23 
  
 DENIED
  
 1)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR TO SUBMITTAL
 ****NOTE THAT OWNER/AGENT MUST SIGN AND DATE AS WELLAS
 PREPARER, ALSO CONFIRM THAT R-VALUE FOR CEILING/DECK
 AREA IS INCLUDED IN CALCULATIONS EITHER AS RAISED WOOD
 FLOOR OR ADDED TO ATTIC AREA SQUARE FOOTAGE****
  
 2)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 ****NOTE THIS IS A REQUIREMENT OF THIS
 JURISDICTION****
  
 3)PROVIDE CORRECT FLORIDA PRODUCT APPROVAL
 INFORMATION FOR THE SIMPSON CONNECTORS, PLEASE SEE THE
 2 COPIES OF THE FLORIDA INDEXTHAT ARE ATTACHED AND
 HIGHLITE THE APPROPRIATE CONNECTORS
  
 4)PROVIDE CORRECT FLORIDA PRODUCT APPROVAL
 INFORMATION FOR THE PEACHTREE SGD, PLEASE USE THE
 FLORIDA STATE LINK ON THE PAGE FOR THE SGD (FL 9141) TO
 DOWNLOAD THE CORRECT COMPLIANCE REPORT
  
 5)PROVIDE PRODUCT APPROVALS FOR MULLIONS THAT WILL BE
 USED TO TIE DOUBLE AND TRIPLE SET WINDOWS
  
 6)PROVIDE PRODUCT APPROVALS FOR ALL ENTRY DOORS
 INCLUDING FRONT DOOR WITH SIDELITE
  
 7)PROVIDE DETAIL THAT SHOWS THE ATTACHMENT OF
 GUARDRAIL TO PROVIDE FOR THE CONCENTRATED LOADS
 REQUIRED BY 1607.7.1.1 FBC AND HOW THE WATERTIGHT
 CONSTRUCTION WHERE PENETRATING ROOFING MATERIALS
  
 8)STATE THE PERIMETER AND CORNER DESIGN PRESSURE FOR
 THE FLAT DECK AREA THAT IS TO USE ROOFING PRODUCT IF
 THEY EXCEED THE DESIGN PRESSURE LIMIT OF THE PRODUCT
 APPROVAL PROVIDE CALCULATIONS PER RAS 117 (SEE
 LIMITATION #7 ON LAST PAGE OF THE PRODUCT APPROVAL) FOR
 ENHANCED FASTENING
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By amorse Date 2007-07-19 Time 16:15 Rev Time 0.00
Received By amorse Date 2007-07-19 Time 16:15 Sent To PC
Notes
2007-07-17 18:47:40 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 29.62FOR STATE
 RADON FEES THIS AMOUNT IS REQUIRED TO BE PAID PRIOR TO
 FURTHER PLAN REVIEW
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 5)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 7)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 NOTE: PRODUCT APPROVALS ARE REQUIRED FOR CASTCRETE
 LINTELS, GARAGE SECTIONAL DOOR, ALL STRUCTURAL
 STRAPS/TIES THAT WILL BE USED
 ( PROVIDE EITHER A COMPLETE CONNECTOR SCHEDULE WITH THE
 FLORIDA STATEWIDE PRODUCT APPROVAL NUMBER LISTED OR THE
 MANUFACTURERS FLORIDA INDEX WITH THE APPROPRIATE
 CONNECTORS MARKED.)
  
 8)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 10)SUBMIT ENGINEERED TRUSS DRAWINGS FOR FLOOR AND
 ROOF TRUSSES THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 11)SUBMIT SPIRAL STAIRCASEDRAWINGS THAT
 COMPLY WITH R311.5 AND R311.5.8.1 FBC RES. WITH PERMIT
 APPLICATION THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE
 DESIGNER OF RECORD
  
 12)PROVIDE SIZE OF ATTIC VENTILATION AND IT'S SPACING
 TO SHOW COMPLIANCE WITH R806.2 FBC RES. (IF 20 SQ. FT.
 IS REQUIRED THIS WILL REQUIRE APPROX. 60 VENTS OF
 4"X12")
  
 13)NO SECTIONS WERE GIVEN OF THROUGH FRONT LIVING
 ROOM/TERRACE/VERANDA AREAS PLEASE SHOW CONSTRUCTION OF
 DECKS, AS UNCOVERED DECK IS SITUATED OVER LIVING SPACE
 AND SHOW SOFFIT MATERIAL AT THESE LOCATIONS AND BACK
 COVERED PATIO AREA
  
 14)PROVIDE COMPLETED APPLICATION FOR LOCAL PRODUCT
 APPROVAL FOR THE SLIDING GLASS DOORS. SEE ATTACHED
 APPLICATION AND BE SURE ALL REQUIRED INFORMATION IS
 PROVIDED PER CHECK LIST ON BACK.
  
 15)STAIR HANDRAILS AND GUARDS SHALL REJECT A 4"
 SPHERE PER R312.2 FBC RES.
  
 16 )PROVIDE INFORMATION ON PLANS THAT STAIRS MEET ALL
 THE REQUIREMENTS OF R315.1 - 315.5.5 FBC RES.
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-05-26 Cont ID  
Sent By btrobaug Date 2009-05-26 Time 12:29 Rev Time 0.00
Received By btrobaug Date 2009-05-26 Time 12:00 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-26 Cont ID  
Sent By btrobaug Date 2007-10-26 Time 12:59 Rev Time 0.00
Received By btrobaug Date 2007-10-26 Time 07:55 Sent To M
Notes
2007-10-26 13:05:55 
  
 REDLINED RECEPTALE IN BEDROOM AND STUDIO, UPPER, AND
 BATH CIRCUIT ON SCHEDULE./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By btrobaug Date 2007-09-24 Time 10:57 Rev Time 0.00
Received By btrobaug Date 2007-09-24 Time 08:51 Sent To M
Notes
2007-09-24 10:50:13 
  
 THESE ARE REPEAT COMMENTS FROM 7/10/07 REVIEW.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THIS COMMENT WAS NOT ADDRESSED..
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. THE
 CALCULATION GIVEN WAS ONLY AT THE TRANSFORMER, NOT AT
 THE SERVICE EQUIPMENT, WHICH IS THE INFORMATION THE
 CONTRACTOR NEEDS TO PURCHASE THE CORRECT EQUIPMENT.
  
 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE
 CENTRAL HEAT, AND POOL HEATER TOOK A DEMAND AND WAS
 THEN FIGURED INTO THE TOTAL LOAD AND ANOTHER DEMAND OF
 40% WAS TAKEN.
 THE LOAD CALCULATION IS STILL INCORRECT. THE
 CALCULATION APPEARS TO BE PARTLY FROM ARTICLE 220.83.
 THE 65% DEMAND ON THE AHU'S, SHOULD BE 100%, SEE
 220.83(B). ALSO ONLY THE LARGEST OF THE A/C OR AHU LOAD
 SHOULD BE IN THE CALCULATION, AGAIN SEE 220.83(B). THE
 40 PERCENT DEMAND TAKEN ON THAT LOAD IS IS NEVER
 ALLOWED. IN THE CASE OF THE AHU'S A DOUBLE DEMAND WAS
 TAKEN, 1ST THE 65% THEN 40% OF THAT.
  
 THIS IS A NEW COMMENT FOR THIS REVIEWDUE TO THE CHANGE
 IN THE RISER DIAGRAM
  
 1} LOCATE THE GUTTER SHOWN ON THE RISER, AT THE
 PHYSICAL LOCATION ON THE PLAN
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By btrobaug Date 2007-07-10 Time 14:59 Rev Time 0.00
Received By btrobaug Date 2007-07-10 Time 12:05 Sent To M
Notes
2007-07-10 12:27:30 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} 230.31 SIZE AND RATING
 (A) GENERAL SERVICE-LATERAL CONDUCTORS SHALL HAVE
 SUFFICIENT AMPACITY TO CARRY THE CURRENT FOR THE LOAD
 AS CALCULATED IN ACCORDANCE WITH ARTICLE 220 AND SHALL
 HAVE ADEQUATE MECHANICAL STRENGTH. THE LOAD CALCULATION
 @ 244 AMPS, EXCEEDS THE SERVICE SIZE OF 200 AMPS. THE
 SERVICE MUST BE INCREASED.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS." ALL PANELS.
  
 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE
 CENTRAL HEAT, AND POOL HEATER TOOK A DEMAND AND WAS
 THEN FIGURED INTO THE TOTAL LOAD AND ANOTHER DEMAND OF
 40% WAS TAKEN.
  
 6} THE POOL HEATER WAS CALCULATED @ 40%, INDICATE THE
 ARTICLE FROM WHICH THAT DEMAND WAS ALLOWED.
  
 7} PROVIDE A LEGEND FOR THE SYMBOLS USED FOR THE
 ELECTRICAL PLANS.
  
 8} THE CONDENSING UNITS ARE REQUIRED TO HAVE
 DISCONNECTS PER 440.14, THE PLAN INDICATES JUNCTION
 BOXES. PLEASE CLARIFY.
  
 9} THE SPA MUST BE GFCI PROTECTED PER 680.43(A)(3).
 INDICATE SAME ON PLAN.
  
 10} THE WATER HEATER IN THE GARAGE IS SHOWN NEXT TO A
 RECEPTACLE, AND THERE DOES NOT APPEAR TO BE A
 DISCONNECT FOR THAT UNIT. SEE 422.16 REGARDING
 "APPLIANCE IS INTENDED OR IDENTIFIED FOR FLEXIBLE CORD
 CONNECTION".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
 .

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-11-12 Time 11:07 Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 11:07 Sent To M
Notes
2008-11-12 11:08:11TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:07 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:07 Sent To B
Notes
2008-01-11 17:07:51TO ADRIAN MORSES DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 12:17 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 12:17 Sent To E
Notes
2007-10-24 12:18:26TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 10:45 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 10:45 Sent To Z
Notes
2007-09-17 10:45:34TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-19 Time   Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 09:02 Sent To  
Notes
2007-07-06 09:02:34TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-11-13 Cont ID  
Sent By tgordon Date 2008-11-13 Time 14:23 Rev Time 0.40
Received By tgordon Date 2008-11-13 Time 14:23 Sent To  
Notes
2008-11-13 14:24:06REVISION TO MECH. PLANS 18 AND 19.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-11-12 Cont ID  
Sent By tgordon Date 2008-11-12 Time 15:36 Rev Time 1.30
Received By tgordon Date 2008-11-12 Time 15:36 Sent To  
Notes
2008-11-12 16:11:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS.
 *** DENIED ***
  
 1) THE FOLLOWING RETURN AIR DUCTS APPEAR TO BE UNDER
 SIZED. 8" RETURN FLEX TO MASTER BEDROOM (AHU #2), 10"
 RETURN FLEX TO THE LOFT (AHU #3), AND THE 7"X24" CHASE
 FOR AHU #1.
  
 2) SHOW THE SIZE OF THE DUCT (RIGID FIBROUS GLASS) FROM
 AHU #1 TO THE 7"X24" CHASE, PER 2004 FBC/R M1601.1.
  
 3) PLEASE SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL
 DUCT DESIGN (3 SYSTEMS), PER 2004 FBC/R M1601.1 AND FBC
 13-610.1.ABC.1. SEE ATTACHED COPY OF MANUAL D
 RECOMMENDED VELOCITY.
  
 4) PLEASE SUBMIT A BLOWER PERFORMANCE TABLE OR GRAPH
 FOR EACH AHU, PER MANUAL D 5-1.
  
 5) PLEASE SUBMIT THE PRODUCT AND PERFORMANCE DATA
 SHEETS FOR THE FLEXIBLE DUCT BEING USED, PER 2004 FBC/R
 M1601.4.
  
 NOTICE: 2004 FBC/R M1602.4 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN
 RESIDENTIAL BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND
 PRESSURE DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR.
 PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS WHERE
 RETURNS ARE CENTRALLY LOCATED SHALL BE LIMITED TO 0.01
 INCH WC (2.5 PASCALS) OR LESS. PRESSURE DIFFERENTIALS
 ACROSS FIRE WALLS IN CEILING SPACE PLENUMS SHALL BE
 LIMITED TO 0.01 INCH WC (2.5 PASCALS) BY PROVIDING AIR
 DUCT PATHWAYS OR AIR TRANSFER PATHWAYS FROM THE HIGH
 PRESSURE ZONE TO THE LOW ZONE.
 BALANCED RETURN AIR MAY ALSO BE ACHIEVED BY.
 (A) TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B) TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C) HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-26 Cont ID  
Sent By tgordon Date 2007-10-26 Time 14:53 Rev Time 0.40
Received By tgordon Date 2007-10-26 Time 14:53 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By tgordon Date 2007-09-25 Time 08:40 Rev Time 0.45
Received By tgordon Date 2007-09-25 Time 08:40 Sent To P
Notes
2007-09-25 08:52:01PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW, ENERGY CALCULATIONS NEED TO
 BE SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 2) THE MECHANICAL PLANS PAGES 18 & 19 NEED THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN, AND CONTRACTOR INFORMATION IF APPLICABLE ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 3) SHOW ON MECHANICAL PLANS THE ATTIC ACCESS FOR AHU
 #2, SEE FBC/R M1305.1.3.2.
  
 4) SHOW ON MECHANICAL PLAN ALL BATHROOM EXHAUST FANS
 AND CFM'S, SEE ELECTRICAL PLAN AND FBC/R R303.3
 EXCEPT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By tgordon Date 2007-07-11 Time 09:06 Rev Time 0.30
Received By tgordon Date 2007-07-11 Time 09:06 Sent To P
Notes
2007-07-11 09:30:48*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R,
 PLEASE CORRECT ALSO HAVE OWNER/AGENT SIGN REVISED
 E-CAL'S. SEE 2004 FBC 13-600.3.A AND 13-600.3.ABC.2.
  
 2) MECHANICAL PLANS NEED TO BE SEALED BY JOHN CRESWELL,
 P.E. AS HIS NAME AND INFORMATION IS IN THE TITLE BLOCK,
 SEE FAC 61G15-23.002.
  
 3) NEED A/C EQUIPMENT LISTING ON MECHANICAL PLANS
 SHOWING ALL PERTINENT INFORMATION (EQUIPMENT
 MANUFACTURE, MODEL NUMBERS, SEER, TOTAL AND SENSIBLE
 BTU'S, HEATER KW, ETC.).
  
 4) PLEASE SHOW CFM'S AT ALL SUPPLY AIR GRILLS.
  
 5) PLEASE SIZE THE SUPPLY AIR TRUNK LINE TO THE AIR
 HANDLER IN THE GARAGE.
  
 6) THE SECOND FLOOR NEEDS A RETURN FOR THE LOFT AND
 OPEN AREA, SEE 2004 FBC/R M1604.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-01 Cont ID  
Sent By jleech Date 2007-10-01 Time 09:27 Rev Time 0.00
Received By jleech Date 2007-10-01 Time 09:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By jleech Date 2007-07-17 Time 07:15 Rev Time 0.00
Received By jleech Date 2007-07-17 Time 07:15 Sent To B
Notes
2007-07-17 07:20:51DENIED;
 SANITARY RISER DIAGRAM NOT TO CODE;
 A) 2ND FLOOR PLUMBING FIXTURES CANNOT DUMP
 INTO THE VENT OF THE FIRST FLOOR FIXTURES.
 B) 1/2 BATH, TOILET NOT VENTED AS DRAWN.
 ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-20 Cont ID  
Sent By choops Date 2007-09-20 Time 08:50 Rev Time 0.00
Received By choops Date 2007-09-20 Time 08:50 Sent To E
Notes
2007-09-20 08:55:04***PASSED- RESUB #1***
  
 PROVISO:POOL NOT INCLUDED UNDER THIS PERMIT, TO BE
 UNDER SEPARATE PERMIT.
  
 NOTE:AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE VALUE OF THE HOME, ALL LANDSCAPING SHALL BE BROUGHT
 TO COMPLIANCE WITH SECTION 94-442 OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 NOTE:2ND FLOOR AREA ABOVE GARAGE TO MAINTAIN INTERIOR
 ACCESS.NO SEPARATE DWELLING UNIT WILL BE PERMITTED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-09 Cont ID  
Sent By choops Date 2007-07-09 Time 09:18 Rev Time 0.00
Received By choops Date 2007-07-09 Time 09:18 Sent To E
Notes
2007-07-09 09:20:51***FAILED***
  
  
 1)PLEASE CLARIFY SCOPE OF WORK ON APPLICATION.REAR
 PORCH TO BE ADDED, DRIVEWAY TO BE INCLUDED UNDER THIS
 PERMIT?IF SO, INCLUDE ALL DIMENSIONS AND TOTAL SQUARE
 FEET OF PROPOSED DRIVEWAY.
  
 2)PROVIDE CHIMNEY DIMENSION THAT EXTENDS PAST THE
 TOP OF THE ROOF.
  
 3)SHOW ANY PROPOSED A/C EQUIPMENT ON SITE PLAN WITH
 SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
 4)SHOW ALL OVERHANG DIMENSIONS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720