Plan Review Details - Permit 07070020
Plan Review Stops For Permit 07070020
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-11-11 Cont ID  
Sent By shill Date 2007-11-11 Time 15:44 Rev Time 0.00
Received By shill Date 2007-11-11 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-19 Cont ID  
Sent By shill Date 2007-10-19 Time 15:15 Rev Time 0.00
Received By shill Date 2007-10-19 Time 15:15 Sent To  
Notes
2007-10-19 15:33:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLANS ARE TO SHOW CODE COMPLIANCE.THE RESPONSE
 LETTER CAN BE HELPFUL IN EXPLAINING HOW A COMMENT WAS
 ADDRESSED. BUT THE PLANS SHOULD CLEARLY SHOW SCOPE OF
 WORK.
  
 2.THE RESPONSE LETTER GIVES INFORMATION WHICH IS
 DESIGN RELATED.ONLY CODE COMPLIANCE IS ADDRESSED IN
 THE PLAN REVIEW.IT APPEARS THAT YOU ARE CLOSING AN
 EXISTING OPENING AND CREATING A NEW ONE.THIS NEEDS TO
 BE SHOWN ON THE PLAN, USING THE FLOOR PLAN, DETAILS,
 AND DETAIL MARKERS.
  
 3.PROVIDE A DETAIL FOR THE INFILL AND A DETAIL FOR
 THE FRAMING OF THE NEW OPENING.STATING THAT YOU ARE
 INSTALLING 4 STUDS IS NOT SUFFICIENT NOR CODE
 COMPLIANT.
  
 4.ON THE INSTALLATION SCHEDULE, STATE WHICH
 CONNECTION TYPE YOU ARE USING.YOU'VE CIRCLED ALL OF
 THEM ON THE PRODUCT APPROVAL.THE 6" SPACING WHICH YOU
 SPECIFY IS NOT COMPLIANT FOR ALL CONNECTION MOUNTING
 TYPES.THIS SHOULD BE A THROUGH L, SEE SHEETS 13-15.
  
 5.A 2" EDGE DISTANCE REQUIRES A FACTOR OF .5, SEE
 SHEET 14 OF THE PRODUCT APPROVAL.INFORMATIONAL;
 AFFECTS ANCHOR SPACING, CANNOT BE REVIEWED AS
 CONNECTION MOUNTING TYPE HAS NOT BEEN SPECIFIED.
  
 6.SPANS SHOULD EQUAL BLADE LENGTH, SO SHOULD
 CORRELATE WITH THE OPENING HEIGHT.REVISE INSTALLATION
 SCHEDULE.
  
 7.THE FIRST COMMENT LISTS REQUESTED THAT THE PLANS
 SHOW HOW EMERGENCY EGRESS FOR BEDROOMS WILL BE
 ADDRESSED.IT IS NOT CLEAR HOW THIS HAS BEEN
 ADDRESSED, FBC 310, FBC EB505.1.
  
 8.ANOTHER COMMENT LIST HAD REQUESTED THAT THE
 APPLICATION BE REVISED TO REFLECT SCOPE OF WORK (AFTER
 CONTRACTOR STATED THAT ONLY S/H WINDOWS WERE BEING
 INSTALLED).IT STILL STATES "DUAL ACTION AND SINGLE
 HUNG".PLANS ARE TO SHOW WHICH WINDOW TYPE WILL BE
 INSTALLED IN EACH LOCATION.REVISE APPLICATION IF ONLY
 ONE WINDOW TYPE IS BEING INSTALLED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-27 Cont ID  
Sent By shill Date 2007-08-27 Time 17:39 Rev Time 0.00
Received By shill Date 2007-08-27 Time 17:39 Sent To  
Notes
2007-08-27 17:41:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
  
 2.)THE LETTER STATES THAT YOU ARE CLOSING IN ONE
 OPENING AND THIS CLOSET WILL OPEN INTO THE HALL.IS
 THE HALL CLOSET DOOR A NEW OPENING?PROVIDE A DETAIL.
 WHAT ARE ALL OF THE DARK LINES ON THE PLAN?THE PLAN
 STATES "REPLACE FOUR STUDS", STILL NOT CLEAR WHAT THE
 SCOPE OF WORK IS.
  
 NEW COMMENT:
  
 3.)2 SETS REQUIRED (ONLY ONE INSTALLATION SCHEDULE
 SUBMITTED).
  
 4.)INSTALLATION SCHEDULE IS INCOMPLETE.SHUTTER
 MOUNTING TYPE SHOULD CORRELATE WITH THE ANCHOR
 SCHEDULE, A THROUGH L ON THE PRODUCT APPROVAL.EDGE
 DISTANCE OF 2" REQUIRES A FACTOR OF.5 AND NOT ALLOWED
 FOR SOLD SET, SEE SHEET 14.PROVIDE ALL INFORAMTION ON
 THE INSTALLATION SCHEDULE; MANY COLUMNS WERE LEFT
 BLANK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-03 Cont ID  
Sent By shill Date 2007-08-03 Time 17:39 Rev Time 0.00
Received By shill Date 2007-08-03 Time 17:39 Sent To  
Notes
2007-08-03 17:43:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)IF YOU ARE NOT USING THE DUAL ACTION WINDOW AS
 STATED (SINGLE HUNG IN ALL OPENINGS), YOU MUST SHOW HOW
 YOU ARE COMPLYING WITH THE REQUIREMENTS OF FBC R310,
 FBC EB 505.1, EMERGENCY EGRESS.THE APPLICATION STATES
 "SINGLE HUNG AND DUAL ACTION".PLEASE REVISE
 APPLICATION TO BE CONSISTENT WITH THE SCOPE OF WORK.
  
 2.)THE LETTER STATES THAT YOU ARE CLOSING IN ONE
 OPENING AND THIS CLOSET WILL OPEN INTO THE HALL.IS
 THE HALL CLOSET DOOR A NEW OPENING?PROVIDE A DETAIL.
 WHAT ARE ALL OF THE DARK LINES ON THE PLAN?THE PLAN
 STATES "REPLACE FOUR STUDS", STILL NOT CLEAR WHAT THE
 SCOPE OF WORK IS.
  
 3.)THE RESPONSE LETTER STATES THAT THE INSTALLATION
 SCHEDULE WILL BE SUBMITTED BY THE SHUTTER COMPANY. THIS
 IS REQUIRED AT THIS TIME.THEY MAY APPLY FOR PERMIT AT
 THIS TIME AND REFERENCE THIS PERMIT NUMBER. OR, SUBMIT
 THE INSTALLATION SCHEDULE AS A PART OF THIS PERMIT
 PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 09:07 Rev Time 0.00
Received By shill Date 2007-07-26 Time 09:07 Sent To  
Notes
2007-07-26 09:12:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE PLAN SHOWS WORK IN RED.ONE IS A PHOTOCOPY,
 SO IS NO LONGER IN RED.CODE COMPLIANCE, SCOPE OF WORK
 MUST BE SUBMITTED IN A FORMAT WHICH CAN BE DIGITIZED IN
 BLACK AND WHITE.PLEASE REVISE DRAWING.
  
 2.)PLAN STATES "REPLACE FOUR STUDS", PROVIDE A DETAIL
 AND STATE WHETHER THIS IS A BEARING OR NON LOAD BEARING
 WALL.
  
 3.)SHOW ALL BEDROOMS ON THE FLOOR PLAN AND INDICATE
 WHERE THE DUAL ACTION WINDOW WILL BE USED.
  
 4.)COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION IN ANOTHER FORMAT.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 15:11 Sent To B
Notes
2007-11-06 15:11:31TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 16:48 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 16:48 Sent To B
Notes
2007-10-09 16:48:39TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-14 Cont ID  
Sent By adarroug Date 2007-08-14 Time 09:57 Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 09:57 Sent To B
Notes
2007-08-14 09:57:42TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 13:40 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 13:40 Sent To B
Notes
2007-08-02 13:41:05TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 09:13 Rev Time 0.00
Received By shill Date 2007-07-03 Time 10:50 Sent To  
Notes
2007-07-03 10:50:23TO "MISC" BOX#1