Plan Review Details - Permit 07061019
Plan Review Stops For Permit 07061019
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 11:42 Rev Time 0.00
Received By shill Date 2007-10-29 Time 11:42 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By shill Date 2007-09-25 Time 17:05 Rev Time 0.00
Received By shill Date 2007-09-25 Time 17:05 Sent To  
Notes
2007-09-25 17:06:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS (HILLMAN ENGINEERING).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By shill Date 2007-08-09 Time 11:35 Rev Time 0.00
Received By shill Date 2007-08-09 Time 11:35 Sent To  
Notes
2007-08-09 11:35:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.
  
 2.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 3.)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL
 DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB
 SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By btrobaug Date 2007-09-11 Time 09:14 Rev Time 0.00
Received By btrobaug Date 2007-09-11 Time 08:26 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By btrobaug Date 2007-07-16 Time 08:07 Rev Time 0.00
Received By btrobaug Date 2007-07-16 Time 07:45 Sent To G
Notes
2007-07-16 08:07:25 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING,
 AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 3} PROVIDE A RISER DIAGRAM PER 215.5
 INCLUDING GENERATOR AND RELATED
 EQUIPMENT. THE METER IS NOT SHOWN ON THE PLAN
  
 4} PLEASE NOTE A DISCONNECT IS REQUIRED
 PER 225.31 AND 32. INDICATE LOCATION ON
 THE RISER AND SITE PLAN. THE TRANSFER
 SWITCH MAY NOT MEET THIS REQUIREMENT,
 SEE SPECS BEFORE SUBMITTING.
  
 5} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5.PER ARTICLE 220 PART
 III, STANDARD OR PART IV OPTIONAL, INDICATE METHOD
 USED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-11-13 Cont ID  
Sent By mperson Date 2007-11-13 Time 10:18 Rev Time 0.00
Received By mperson Date 2007-11-13 Time 10:18 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-10-29 Cont ID  
Sent By mperson Date 2007-10-29 Time 10:32 Rev Time 0.00
Received By mperson Date 2007-10-29 Time 10:32 Sent To B
Notes
2007-10-29 10:55:14DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED DRAWINGS:
  
 1. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE
 RESUBMITTED PLANS NEED THE EXISTING BTU LOAD OF GAS
 SYSTEM, AND THE PROPOSED BTU LOAD OF THE GENERATOR. PER
 106.1.2, ADDITIONAL INFORMATION REQUIRED.
  
 2. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE
 RESUBMITTED PLANS NEED THE LONGESTS LENGTH OF THE GAS
 SYSTEM. (THIS INCLUDES THE EXISTING GAS SYSTEM) PER
 106.1.2, ADDITIONAL INFORMATION REQUIRED.
  
 3. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE
 MANUFACTURER SPECIFICATION SHEETS FOR THE GENERATORS
 2ND STAGE REGULATOR NEED THE MANUFACTURER'S NAME (THIS
 IS NOT INDICATED ON THE SUBMITTED DATA SHEETS), AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 (THIS IS NOT INDICATED ON THE SUBMITTED DATA SHEETS)
 PER 106.1.2, ADDITIONAL INFORMATION REQUIRED.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By mperson Date 2007-09-25 Time 09:44 Rev Time 0.00
Received By mperson Date 2007-09-25 Time 09:44 Sent To M
Notes
2007-09-25 10:08:48DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 2006 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT SHOW ALL CUT SECTIONSAND CORRESPONDING
 LENGTHS TO THE PROPOSED GENERATOR. THE ONLY PIPING
 INDICATED IS THE UNDERGROUND PE PIPE, THERE ARE NO
 INDICATIONS OF THE ABOVE GROUND PIPING, 1ST AND 2ND
 STAGE REGULATORS, SHUT OFF VALVES AND SEDIMENT TRAPS.
 PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. **NO/OK** SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: REFERENCE COMMENT 1, WHERE ONLY THE UNDERGROUND
 PIPING IS BEING INDICATED.
  
 3. **OK**
  
 4. **OK**
  
 5. **OK**
  
 6. **OK**
  
 7. **NO** INDICATE THE DELIVERY PRESSURE ON THE
 RESUBMITTAL, IF ITS LP GAS INDICATE 10 PSI.
  
 8. **OK**
  
 9. **NO** SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: NEED MANUFACTURER SHEETS ON THE PROPOSED
 GENERATOR VERIFYING THE BTU LOAD AND MANUFACTURER
 SHEETS OF THE 2ND STAGE REGULATOR TO THE PROPOSED
 GENERATOR INDICATING THE MAKE, MODEL NUMBER, LOAD
 CAPACITY AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY.
  
 10. **OK**
  
 11. **OK**
  
 12. **OK**
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-18 Cont ID  
Sent By btrobaug Date 2007-07-16 Time 08:09 Rev Time 0.33
Received By mperson Date 2007-07-18 Time 13:53 Sent To B
Notes
2007-07-18 14:11:17DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 PLEASE SUBMIT THE FOLLOWING INFORMATION FOR THE GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 6.1.1.
  
 12. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 11:58 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 11:58 Sent To Z
Notes
2007-11-06 11:59:09TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-12 Cont ID  
Sent By shill Date 2007-10-12 Time 14:57 Rev Time 0.00
Received By shill Date 2007-10-12 Time 14:57 Sent To G
Notes
2007-10-12 14:57:57TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 15:04 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 15:04 Sent To Z
Notes
2007-09-05 15:04:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-05 Cont ID  
Sent By btrobaug Date 2007-08-09 Time 15:02 Rev Time  
Received By adarroug Date 2007-07-02 Time 11:23 Sent To Z
Notes
2007-07-16 08:06:08 
  
  
  
  
2007-07-02 11:23:41TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-25 Cont ID  
Sent By tgordon Date 2007-09-25 Time 10:56 Rev Time 0.20
Received By tgordon Date 2007-09-25 Time 10:56 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By tgordon Date 2007-07-05 Time 11:20 Rev Time 0.20
Received By tgordon Date 2007-07-05 Time 11:20 Sent To E
Notes
2007-07-05 11:30:04*** DENIED ***
 1) SHOW THE LOCATION OF THE PURPOSED GENERATOR ON THE
 SURVEY. DOES THE SUBMITTED SITE PLAN SHOWS THE
 GENERATOR ON TOP OF THE POOL EQUIPMENT?
 2) INFORMATIONAL: PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-09 Cont ID  
Sent By choops Date 2007-11-09 Time 15:56 Rev Time 0.00
Received By choops Date 2007-11-09 Time 15:56 Sent To G
Notes
2007-11-09 15:58:03***FAILED - RESUB #2***
  
  
 SENT TO "G" - MP

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-06 Cont ID  
Sent By choops Date 2007-09-06 Time 17:36 Rev Time 0.00
Received By choops Date 2007-09-06 Time 17:36 Sent To E
Notes
2007-09-06 17:36:25***APPROVED - RESUB #1***
  
 SENT TO BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-09-05 Time 15:02 Rev Time 0.00
Received By choops Date 2007-07-02 Time 14:42 Sent To E
Notes
2007-07-02 14:48:52***FAILED***
  
  
 1)PLEASE SHOW PROPOSED GENERATOR ON SURVEYS,
 INDICATE SETBACK DIMENSION ON BOTH SURVEYS FROM
 PROPERTY LINES TO PROPOSED GENERATOR.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720