| Plan Review Stops For Permit 07061019 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-29 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-29 |
Time |
11:42 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-25 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-25 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2007-09-25 17:06:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS (HILLMAN ENGINEERING). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-09 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-09 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2007-08-09 11:35:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH | | | FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS, | | | AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING, | | | UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS | | | FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF | | | THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD | | | LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE USED. | | | | | | 2.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4. | | | | | | 3.)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL | | | DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB | | | SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-11 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-11 |
Time |
08:26 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-16 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-16 |
Time |
07:45 |
Sent To |
G |
|
| Notes |
| 2007-07-16 08:07:25 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE TOTAL COST OF LABOR AND | | | MATERIAL FOR THE GENERATOR, EQUIPMENT | | | (TRANSFER SWITCHES, PANELS ETC.) | | | AND PAD PER 108.3 FBC AS AMENDED. | | | INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING, | | | AND GET A RECEIPT FROM THE | | | PERMIT CLERK. | | | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS | | | INDICATING RECOMMENDED SETBACKS AND | | | ELECTRICAL SPEC'S FOR THE GENERATOR AND | | | TRANSFER SWITCH. | | | | | | 3} PROVIDE A RISER DIAGRAM PER 215.5 | | | INCLUDING GENERATOR AND RELATED | | | EQUIPMENT. THE METER IS NOT SHOWN ON THE PLAN | | | | | | 4} PLEASE NOTE A DISCONNECT IS REQUIRED | | | PER 225.31 AND 32. INDICATE LOCATION ON | | | THE RISER AND SITE PLAN. THE TRANSFER | | | SWITCH MAY NOT MEET THIS REQUIREMENT, | | | SEE SPECS BEFORE SUBMITTING. | | | | | | 5} PROVIDE A LOAD CALCULATION FOR THE | | | LOAD INTENDED TO BE SERVED. 215.5.PER ARTICLE 220 PART | | | III, STANDARD OR PART IV OPTIONAL, INDICATE METHOD | | | USED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2007-11-13 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-11-13 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-11-13 |
Time |
10:18 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-10-29 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-10-29 |
Time |
10:32 |
Sent To |
B |
|
| Notes |
| 2007-10-29 10:55:14 | DENIED 3RD TIME | | | REFERENCE: | | | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | | ** FLORIDA STATUTES (FS). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE | | | RESUBMITTED DRAWINGS: | | | | | | 1. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE | | | RESUBMITTED PLANS NEED THE EXISTING BTU LOAD OF GAS | | | SYSTEM, AND THE PROPOSED BTU LOAD OF THE GENERATOR. PER | | | 106.1.2, ADDITIONAL INFORMATION REQUIRED. | | | | | | 2. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE | | | RESUBMITTED PLANS NEED THE LONGESTS LENGTH OF THE GAS | | | SYSTEM. (THIS INCLUDES THE EXISTING GAS SYSTEM) PER | | | 106.1.2, ADDITIONAL INFORMATION REQUIRED. | | | | | | 3. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE | | | MANUFACTURER SPECIFICATION SHEETS FOR THE GENERATORS | | | 2ND STAGE REGULATOR NEED THE MANUFACTURER'S NAME (THIS | | | IS NOT INDICATED ON THE SUBMITTED DATA SHEETS), AND A | | | LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY | | | (THIS IS NOT INDICATED ON THE SUBMITTED DATA SHEETS) | | | PER 106.1.2, ADDITIONAL INFORMATION REQUIRED. | | | | | | 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE DRAWING SHALL CLEARLY PRINT AND SIGN | | | NAME, AND ALSO DATE DRAWING. PLEASE DO | | | THIS PRIOR TO RESUBMITTING. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-09-25 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-09-25 |
Time |
09:44 |
Sent To |
M |
|
| Notes |
| 2007-09-25 10:08:48 | DENIED 2ND TIME | | | REFERENCE: | | | ** FBC-2004 WITH 2006 REVISIONS, FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | | MADE ON PREVIOUS REVIEWS. | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | | PREVIOUS REVIEW NOTES. | | | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | | | 1. **NO** SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND | | | DOES NOT SHOW ALL CUT SECTIONSAND CORRESPONDING | | | LENGTHS TO THE PROPOSED GENERATOR. THE ONLY PIPING | | | INDICATED IS THE UNDERGROUND PE PIPE, THERE ARE NO | | | INDICATIONS OF THE ABOVE GROUND PIPING, 1ST AND 2ND | | | STAGE REGULATORS, SHUT OFF VALVES AND SEDIMENT TRAPS. | | | PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON | | | CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE | | | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, | | | AS DETERMINED BY THE | | | BUILDING OFFICIAL. | | | | | | 2. **NO/OK** SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | NOTE: REFERENCE COMMENT 1, WHERE ONLY THE UNDERGROUND | | | PIPING IS BEING INDICATED. | | | | | | 3. **OK** | | | | | | 4. **OK** | | | | | | 5. **OK** | | | | | | 6. **OK** | | | | | | 7. **NO** INDICATE THE DELIVERY PRESSURE ON THE | | | RESUBMITTAL, IF ITS LP GAS INDICATE 10 PSI. | | | | | | 8. **OK** | | | | | | 9. **NO** SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | NOTE: NEED MANUFACTURER SHEETS ON THE PROPOSED | | | GENERATOR VERIFYING THE BTU LOAD AND MANUFACTURER | | | SHEETS OF THE 2ND STAGE REGULATOR TO THE PROPOSED | | | GENERATOR INDICATING THE MAKE, MODEL NUMBER, LOAD | | | CAPACITY AND A LISTING FROM A NATIONALLY RECOGNIZED | | | TESTING LABORATORY. | | | | | | 10. **OK** | | | | | | 11. **OK** | | | | | | 12. **OK** | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-16 |
Time |
08:09 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-07-18 |
Time |
13:53 |
Sent To |
B |
|
| Notes |
| 2007-07-18 14:11:17 | DENIED | | | REFERENCE: | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | ******IMPORTANT INFORMATION****** | | | AS OF 8/25/06 GENERATOR (GEN/RES AND | | | GEN/COM) PERMIT APPLICATIONS SHALL NOT | | | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- | | | MATION AND GAS (OR DIESEL) INFORMATION | | | IS ALL SUBMITTED AT THE SAME TIME. THE | | | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- | | | FORMATION WILL BE ROUTED TOGETHER. THIS | | | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY | | | THE MANUFACTURER'S SPECI- | | | FICATIONS AND INSTALLATION INSTRUCTIONS) | | | ARE AVAILABLE TO ALL PLAN REVIEWERS. | | | | | | CONTRACTOR INFORMATION | | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL GEN/RES INSPECTION. | | | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION FOR THE GAS | | | PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM. | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 6.1.1. | | | | | | 12. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE DRAWING SHALL CLEARLY PRINT AND SIGN | | | NAME, AND ALSO DATE DRAWING. PLEASE DO | | | THIS PRIOR TO RESUBMITTING. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-11-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-06 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-06 |
Time |
11:58 |
Sent To |
Z |
|
| Notes |
| 2007-11-06 11:59:09 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-12 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-12 |
Time |
14:57 |
Sent To |
G |
|
| Notes |
| 2007-10-12 14:57:57 | TO "G" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-09-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-05 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-05 |
Time |
15:04 |
Sent To |
Z |
|
| Notes |
| 2007-09-05 15:04:36 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-09-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-09 |
Time |
15:02 |
Rev Time |
|
| Received By |
adarroug |
Date |
2007-07-02 |
Time |
11:23 |
Sent To |
Z |
|
| Notes |
| 2007-07-16 08:06:08 | | | | | | | | | | | | | | | 2007-07-02 11:23:41 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-25 |
Time |
10:56 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-09-25 |
Time |
10:56 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-05 |
Time |
11:20 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-07-05 |
Time |
11:20 |
Sent To |
E |
|
| Notes |
| 2007-07-05 11:30:04 | *** DENIED *** | | | 1) SHOW THE LOCATION OF THE PURPOSED GENERATOR ON THE | | | SURVEY. DOES THE SUBMITTED SITE PLAN SHOWS THE | | | GENERATOR ON TOP OF THE POOL EQUIPMENT? | | | 2) INFORMATIONAL: PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE | | | RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS | | | CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | 2004 FMC 804.3.5 #3, WHERE THE | | | TERMINATION IS LOCATED BELOW AN ADJACENT | | | ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | | ROOF STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED | | | CLEARANCES AROUND EQUIPMENT FOR | | | SERVICING,AND PROVIDE MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-11-09 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-11-09 |
Time |
15:56 |
Sent To |
G |
|
| Notes |
| 2007-11-09 15:58:03 | ***FAILED - RESUB #2*** | | | | | | | | | SENT TO "G" - MP |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-09-06 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-09-06 |
Time |
17:36 |
Sent To |
E |
|
| Notes |
| 2007-09-06 17:36:25 | ***APPROVED - RESUB #1*** | | | | | | SENT TO BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-05 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-02 |
Time |
14:42 |
Sent To |
E |
|
| Notes |
| 2007-07-02 14:48:52 | ***FAILED*** | | | | | | | | | 1)PLEASE SHOW PROPOSED GENERATOR ON SURVEYS, | | | INDICATE SETBACK DIMENSION ON BOTH SURVEYS FROM | | | PROPERTY LINES TO PROPOSED GENERATOR. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|