Plan Review Details - Permit 07061010
Plan Review Stops For Permit 07061010
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-15 Cont ID  
Sent By rmcdouga Date 2008-10-15 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2008-10-15 Time 11:49 Sent To  
Notes
2008-10-15 11:50:21REVISIONS TO SHEET 4.1 ARE OK FOR BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-12 Cont ID  
Sent By rmcdouga Date 2008-02-12 Time 07:23 Rev Time 0.00
Received By rmcdouga Date 2008-02-12 Time 07:01 Sent To  
Notes
2008-02-12 07:55:19REVISED ROOF FRAMING PLAN IS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-21 Cont ID  
Sent By rmcdouga Date 2007-09-21 Time 10:17 Rev Time 0.00
Received By rmcdouga Date 2007-09-21 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By rmcdouga Date 2007-07-17 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2007-07-16 Time 18:54 Sent To  
Notes
2007-07-17 08:50:06DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SHOW COMPLIANCE WITH R302 LOCATION ON LOT.R302.1
 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT. INDICATE THE
 DISTANCE TO STRUCTURES ON ADJACENT LOTS ON THE SITE
 PLAN WHERE THE DISTANCE FROM THE PROPOSED ADDITION TO
 THE PROPERTY LINES IS LESS THAN6 FEET.
  
 4) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 5) THE SECTION TAG FOR 3 ON 7.1 STEP DOWNFOOTING AT
 GARAGE IS SHOWN IN THE WRONG LOCATION ON SHEET 3.1.
  
 6) PORTIONS OF THE NEW ADDITION MASONRY WALLS ON SHEETS
 3.1 AND 4.1 ARE MISTAKENLY INDICATED AS EXISTING.
  
 7) REVISE THE ROOF SHEATHING FASTENING SCHEDULE ON 5.1
 TO COMPLY WITH THE 2006 REVISIONS TO THE 2004 FBC.
 FASTENER SPACING IN ROOF ZONE 3 IS REQUIRED TO BE 4" OC
 AT STRUCTURAL PANEL EDGES AND FIELD. ALL ROOF ZONES ARE
 REQUIRED TO BE FASTENED WITH 8D RING SHANK NAILS. SEE
 FBC R803.2.3.1
  
 8) SPECIFY THE INSULATION IN THE 2 X 8 KNEE WALL SHOWN
 IN SECTION 2 ON 5.1.
  
 9) IN THE CONNECTOR SCHEDULE ON 5.1 NUMBER 22 SHOULD BE
 AN LUS 210. PLEASE CORRECT.
  
 10) SPECIFY THE UPLIFT FOR THE LTA 1 STRAP THAT IS
 LISTED IN THE SCHEDULE AS AN ALTERNATE TO THE HETAL
 CONNECTORS.
  
 11) SPECIFY THE CONNECTORS THAT WILL BE REQUIRED AT THE
 HIP GIRDERS.
  
 12) TYPICAL WALL SECTION 1 ON 7.1 SHOWS AN 18" X 18"
 FOOTING AND IN THE SCHEDULE ON 3.1 FOOTING F2 IS
 SPECIFIED AS 18" X 16". PLEASE CORRECT.
  
 13) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORMS PER FBC CHAPTER 13.
  
 14)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 15) SUBMIT COMPLETE NOAS FOR THE CAST-CRETE LINTELS.
 THE ONES SUBMITTED ARE MISSING PAGES.
  
 16) SPECIFY THE FASTENING METHOD THAT WILL BE USED TO
 ATTACH THE CONCRETE ROOF TILES. CIRCLE THE APPROPRIATE
 ITEM FROM ONES LISTED ON THE NOA.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-10 Cont ID  
Sent By dpalmer Date 2009-03-10 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2009-03-10 Time 17:14 Sent To PC
Notes
2009-03-10 17:14:23** REDLINED PLANS
  
 1) NOTE: RISER IS EXISTING PER CONTRACTOR AND OWNER.
 THE GENERATOR AS SHOWN IS ALSO EXISTING AND PERMITTED
 UNDER 06040588.
 SD WAS REDLINED TO SA AND CONFIRMED WITH CONTRACTOR THE
 DEVICES ARE INDEED SMOKE ALARMS AND NOT SMOKE
 DETECTORS.
 A FULL AND COMPLETE DETAILED PANEL SCHEDULE IS REQUIRED
 PER 408.4. THIS WAS ALSO CONFIRMED WITH CONTRACTOR.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 19:02 Sent To M
Notes
2007-09-04 19:02:42*** PROVISO/REVISION NEEDED**
  
 ** PLEASE SEE SOME EXACT SAME COMMENTS FROM PREVIOUS
 REVIEW ALONG WITH NEW COMMENT(S) AS RISER DIAGRAM HAS
 CHANGED.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #12 WHICH
 SPECIFICALLY MENTIONED THE LIVING ROOM RECEPTACLES ARE
 NOT PERMITTED TO BE ON THE DINING ROOM RECEPTACLE
 CIRCUIT. PLANS STILL SHOW BOTH ON THE SAME CIRCUIT??
 PLEASE SEE THIS SAME PREVIOUS NOTE ALSO GAVE THE
 INFORMATION AS ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS ARE REQUIRED TO BE FIGURED AT 1500VA MINIMUM.
 PLEASE SEE THE LOAD CALCULATIONS ONLY INDICATE 2 AT
 1500VA.
  
 2) NOTE: PLEASE SEE THE RISER HAS NOW BEEN REVISED
 REMOVING THE MAIN DISCONNECT WHICH WAS PREVIOUSLY SHOWN
 AND IS NOW SHOWING AN EXISTING *MAIN CIRCUIT BREAKER*
 PANEL INSIDE THE GARAGE.THE RISER STILLS SHOWS AN
 *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE MAIN NOW
 THAT THE MAIN HAS MOVED INSIDE WHICH IS NOT PERMITTED.
 THIS PARALLELS THE NEUTRAL AND CREATES OBJECTIONABLE
 CURRENTS.
 250.24B AND 250.6.
 ** PER HOMEOWNER, THERE IS A METER/MAIN COMBINATION
 PANEL AT THE DWELLING WHICH EXISTS. THIS SHALL BE
 VERIFIED AND REVISED ACCORDINGLY.
  
 3) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS THE DISPOSAL
 AND DISHWASHER ARE FED TO THE SAME UNDER COUNTER
 RECEPTACLE HOWEVER THE PLANS AT THIS SAME LOCATION
 INDICATE SEPARATE RECEPTACLES ON EITHER SIDE OF THE
 SINK.
 THIS NEEDS TO BE VERIFIED. IF THESE ARE BOTH FED TO THE
 SAME RECEPTACLE DEVICE THAN THE 1-POLEBREAKERS ON
 PANEL SCHEDULE FOR CIRCUITS 10 AND 12 WILL BE REQUIRED
 TO BE CHANGED TO A 2-POL BREAKER PER 210.4B.
  
 ** NEED TO REVISE THE PLANS ALONG WITH ANY OTHER
 REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION. A HOLD
 WILL BE PLACED ON THE INSPECTIONS.
 ** IF PLANS COME BACK WITH CORRECTIONS FOR ANY OTHER
 TRADES BEFORE PERMIT IS ISSUED PLEASE REVISE PLANS AT
 THAT TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2007-07-03 Time 17:11 Sent To M
Notes
2007-07-03 18:50:39* UNSAT **
  
 1) NOTE: 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS
 REQUIRE THE CODES TO BE STATED ON PLANS. PLEASE SEE THE
 FOLLOWING ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL
 BE REQUIRED FOR OTHER TRADES. PLEASE KNOW AS OF
 DECEMBER 8TH, 2006 THE STATE ADOPTED THE 2006 REVISIONS
 TO THE 2004 FBC.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (ALREADY SHOWN)
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE CLARIFY SERVICE AS RISER APPEARS TO
 SHOW AND INDICATE SOME AS NEW AND THE LOAD CALCULATIONS
 INDICATE SERVICE AS EXISTING?
 PLEASE SEE RISER SHOWS A MAIN DISCONNECT, HOWEVER PLANS
 DO NOT INDICATE THIS MAIN OUTSIDE?
 110.26, 230.70 ETC
 PLEASE SEE NOTE #7 ALSO.
  
 3) NOTE: PLEASE SEE PANEL SCHEDULE CONTAINS NOTE WHICH
 MENTIONS PANEL IS IN GARAGE HOWEVER PLEASE SEE THE
 PLANS AS THEY DO NOT INDICATE ANY PANEL IN GARAGE.
 PLEASE INDICATE ALL SERVICE EQUIPMENT AND PANEL(S) ON
 PLANS.
 110.26,240.24,408.7, ETC
 FBC 106.1.2, 106.3.5.4
  
 4) NOTE: PLEASE SEE PLANS ARE MISSING CIRCUITING ON
 SEVERAL ITEMS. PLEASE SEE GFI RECEPTACLES REAR WALLS,
 FLOOD LTS (NOT ALL), SMOKE ALARMS, INSTA-GAS WH, ETC.
 PLEASE SEE THERE ARE DEVICES INSIDE DWELLING AS WELL.
 PLEASE COMPLETE AND COORDINATE WITH THE PANEL
 SCHEDULE.
 408.4, 310.16, 24.4
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SEE MISSING ARC FAULT FOR SMOKE ALARMS
 ONCE CIRCUITED. 210.12
  
 6) NOTE: PLEASE SEE NFPA-72 11-5.1.1.1 AND 11.8.3 AS
 THE LOCATION OF THE SA IN THE MASTER BEDROOM NEEDS TO
 BE RELOCATED INTO THE BEDROOM AREA OR ADD AN ADDITIONAL
 UNIT.
  
 7) NOTE: PLEASE SEE BASED ON THE RISER AND THE SERVICE
 ENTRANCE CONDUCTORS THE GROUNDING ELECTRODE CONDUCTOR
 IS NOT OF SUFFICIENT SIZE BASED ON 250.66
 PLEASE INCREASE/ADJUST.
  
 8) NOTE: PLEASE SEE SOME MISSING RECEPTACLES FOR 2FT OR
 MORE OF WALL SPACE AND RECEPTACLES WITHIN 12FT OF EACH
 OTHER. PLEASE SEE LIVING AND DINING WALLS.
 210.52
  
 9) NOTE: PLEASE SEE ALL RECESSED LIGHTING LUMINARIES
 ARE REQUIRED TO MEET FBC 2004 13-606.1.ABC.1.2.4.
 PLEASE PLACE NOTE/INFORMATION FOR THIS.
  
 10) NOTE: PLEASE SEE 410.8 FOR RECESSED LIGHTING SHOWN
 OVER JACUZZI TUB. PLEASE SPECIFY THE TYPE OF FIXTURE AS
 THERE ARE SOME FIXTURES WHICH ARE LISTED TO BE OVER TUB
 W/OUT BEING A CLOSED IN TYPE VAPOR PROOF. IF USING VP,
 THEN INDICATE. PLEASE KNOW IN ANY CASE NO FIXTURES MAY
 BE WITHIN 7FT OF THE HIGHEST WATER LEVEL.
 PLEASE ADJUST TYPE FIXTURE.
  
 11) NOTE: PLEASE SEE NO GFI PROTECTION IS INDICATED ON
 PLANS OR PANEL SCHEDULE FOR THE JACUZZI TUB.
 PLEASE SEE 680.71
  
 12) NOTE: PLEASE SEE 210.52B1, AND 220.52 AS THE DINING
 ROOM/AREA RECEPTACLES ARE NOT PERMITTED TO BE ON WITH
 THE LIVING ROOM AS SHOWN. PLEASE SEE THE CODE SECTIONS
 GIVEN AS ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS
 SHALL BE A MINIMUM OF 1500VA.
 PLEASE SEE THE DINING/BREAKFAST AREAS AND THE LIKE
 SHALL BE INCLUDED.
  
 13) NOTE: PLEASE CORRELATE ALL LOAD CALCULATIONS INTO
 ONE LOAD CALCULATION OF EXISTING AND NEW. PLEASE SEE
 SOME ITEMS ON PLANS WHICH ARE DEDICATED CIRCUITS ARE
 NOT IN LOAD CALCULATIONS OR LOADS DO NOT COORDINATE.
 PLEASE SEE RANGE (LOAD), SEE MISSING GDO LOAD/CIRCUIT
 ON PANEL SCHEDULE, SEE MISSING MULTIPLE SMALL APPLIANCE
 CIRCUITS ABOVE ETC.
 PLEASE ALSO SEE 220.83 ETC.
  
 14) NOTE: PLEASE KNOW THE LOW VOLTAGE AS SHOWN ON PLANS
 WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT. THE
 SEPARATE PERMIT APPLICATION MAY REFERENCE THESE PLANS
 FOR CATV, PHONE AS SHOWN ON PLANS.
 PLEASE KNOW THAT ANY LV FOR SECURITY/ALARM WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT, HOWEVER NOT PLANS
 ARE NEEDED.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-03-04 Cont ID  
Sent By adarroug Date 2009-03-04 Time 11:36 Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 11:36 Sent To E
Notes
2009-03-04 11:36:31TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-10-10 Cont ID  
Sent By adarroug Date 2008-10-10 Time 09:24 Rev Time 0.00
Received By adarroug Date 2008-10-10 Time 09:24 Sent To P
Notes
2008-10-10 09:25:14TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 11:31 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 11:31 Sent To Z
Notes
2008-04-08 11:31:47TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 14:23 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 14:23 Sent To M
Notes
2008-04-02 14:23:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-07 Cont ID  
Sent By adarroug Date 2008-02-07 Time 09:00 Rev Time 0.00
Received By adarroug Date 2008-02-07 Time 09:00 Sent To B
Notes
2008-02-07 09:00:21TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 14:49 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 14:49 Sent To Z
Notes
2007-08-30 14:49:54TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-17 Cont ID  
Sent By rmcdouga Date 2007-07-17 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2007-07-02 Time 16:01 Sent To  
Notes
2007-07-02 16:02:08TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-04-09 Cont ID  
Sent By tgordon Date 2008-04-09 Time 14:16 Rev Time 0.30
Received By tgordon Date 2008-04-09 Time 14:16 Sent To  
Notes
2008-04-09 14:17:22REVISION TO MECH. PLANS AND COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-04-03 Cont ID  
Sent By tgordon Date 2008-04-03 Time 11:39 Rev Time 0.30
Received By tgordon Date 2008-04-03 Time 11:39 Sent To Z
Notes
2008-04-03 11:48:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLANS ON FILE ARE SIGNED AND SEALED BY AN
 ENGINEER GORDON F. BUCK, AND ONLY HE CAN MAKE REVISIONS
 TO THEM. PLEASE HAVE THE ENGINEER OF RECORD DO THE
 REVISION OR HAVE HIM SUBMIT A LETTER REMOVING HIMSELF
 FROM THE PROJECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-13 Cont ID  
Sent By tgordon Date 2007-09-05 Time 13:39 Rev Time 0.30
Received By tgordon Date 2007-09-05 Time 13:38 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By tgordon Date 2007-07-05 Time 09:23 Rev Time 0.30
Received By tgordon Date 2007-07-05 Time 09:23 Sent To P
Notes
2007-07-05 09:33:01*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) THE ENERGY CALCULATIONS ARE CALLING FOR A 16.5 SEER
 A/C SYSTEM, THE MECHANICAL PLANS ARE CALLING FOR A 13
 SEER A/C SYSTEM, THE TWO MUST COINCIDE PLEASE CORRECT.
  
 3) SHOW ON MECHANICAL PLANS THE HEATER SIZE (KW).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status N Date 2008-10-15 Cont ID  
Sent By mperson Date 2008-10-15 Time 10:08 Rev Time 0.30
Received By mperson Date 2008-10-15 Time 10:07 Sent To B
Notes
2008-10-15 10:17:49****************PROVISO****************
  
 REVISION SHEET 4.1: "N" CHANGES IN FLOOR PLAN LAYOUT. A
 REVISION OF SHEET 8.1, PLUMBING RISER WILL BE REQUIRED
 CLEARLY INDICATING THE CHANGES OF THE FOLLOWING.
  
 A} RELOCATED KITCHEN SINK.
  
 B} RELOCATED LAUNDRY ROOM AND HALF/BATH (ROOMS WERE
 FLIPPED).
  
 END OF COMMENTS:
  
 *IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 14:29 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 14:21 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By jleech Date 2007-07-12 Time 11:19 Rev Time 0.00
Received By jleech Date 2007-07-12 Time 11:11 Sent To B
Notes
2007-07-12 11:29:09DENIED;
 1. 1/2 BATHROOM; CHECK FOR CLEAR FLOOR SPACE IN FRONT
 OF TOILET, MUST BE 21", SEE FBC PLUMBING SECTION
 405.3.1.
 2. SANITARY RISER DIAGRAM;
 A) HORIZONTAL DRY VENT FOR MASTER TOILET NOT
 PERMITED SECTION 905.3.
 B) AUTOMATIC CLOTHES WASHER TO DISCHARGE
 DOWN STREAM OF THE 1/2 BATH GROUP, SECTION 909.1
 C) THE TUB WASTE CANNOT RUN THRU THE SHOWER
 TRAP AS DRAWN. SECTION 1002.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2008-04-08 Cont ID  
Sent By choops Date 2008-04-08 Time 16:42 Rev Time 0.00
Received By choops Date 2008-04-08 Time 16:42 Sent To M
Notes
2008-04-08 16:43:13***APPROVED - REVISION - CHANGING A/C SYSTEM (ADDING
 ADDITION C.U.)***
  
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 3 Status F Date 2008-04-03 Cont ID  
Sent By choops Date 2008-04-03 Time 16:35 Rev Time 0.00
Received By choops Date 2008-04-03 Time 16:35 Sent To  
Notes
2008-04-03 16:37:13***FAILED - REVISION - CHANGING A/C SYSTEM (ADDING
 ADDITION C.U.)***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 INDICATING SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-04 Cont ID  
Sent By choops Date 2007-09-04 Time 12:57 Rev Time 0.00
Received By choops Date 2007-09-04 Time 12:57 Sent To E
Notes
2007-09-04 12:57:30***APPROVED******RESUB #1***
  
 SENT TO DP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By choops Date 2007-07-03 Time 16:35 Rev Time 0.00
Received By choops Date 2007-07-03 Time 16:35 Sent To E
Notes
2007-07-03 16:44:37***FAILED***
  
  
 1)PLEASE INDICATE SCOPE OF WORK ON APPLICATION MORE
 CLEARLY.INCLUDE ALL WORK BEING DONE (WALKWAY, DECK,
 ETC...)
  
 2)PROPOSED ADDITION DOES NOT MEET SETBACK
 REQUIREMENTS.ENCROACHES INTO REQUIRED WEST SIDE
 SETBACK OF 7' .
  
 3)PROVIDE OVERHANG DIMENSION FROM WALL TO OUTERMOST
 POINT OF ROOF.
  
 4)SHOW ELEVATION DIMENSION OF PROPOSED ADDITION FROM
 GRADE TO THE MIDPOINT OF THE ROOF'S PITCH.
  
 5)SHOW NEW A/C UNIT WITH SETBACK DIMENSIONS TO THE
 PROPERTY LINES.
  
 6)PROVIDE AN UPDATED SURVEY THAT ACCURATELY REFLECTS
 WHAT IS ON THE SITE.
  
 7)PROVIDE DIMENSIONS OF PROPOSED WALKWAY.INDICATE
 WHETHER DRIVEWAY IS INCLUDED IN SCOPE OF WORK OR NOT,
 IF SO INCLUDE DIMENSIONS OF NEW DRIVEWAY, IF NOT
 INCLUDE ALL DIMENSIONS OF EXISTING DRIVEWAY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720