| 2007-08-15 18:20:47 | PROJECT: 1700 PARKER AVENUE |
| | |
| | PROJECT DETAIL: REWORK EXISTING WEST CENTRAL ELEVATION |
| | |
| | CONCRETE RAMP FROM MONTGOMERY HALL |
| | TO MEET THE ACCESSIBILITY REQUIREMENTS. |
| | |
| | PLAN REVIEW: 2004 FLORIDA EXISTING BUILDING CODE/2006 |
| | REVS. |
| | 2004 FLORIDA BUILDING CODE/2006 |
| | REVS. |
| | |
| | STATUS: DENIED |
| | |
| | COMMENTS: |
| | |
| | |
| | 1) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE |
| | FOLLOWING: |
| | |
| | FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2) PLEASE PROVIDE A RAISED SEAL WITHIN THE TITLE BLOCK |
| | ON ALL SHEETS AS PER THE FOLLOWING: |
| | |
| | 61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED |
| | 481.203(6), 481.203(8), 481.2131(1), |
| | 481.219(3),(4),(5), 481.221, |
| | 481.225(1)(E),(G), 481.2251(1)(H) FS. HISTORY? |
| | NEW 9-7-00. |
| | |
| | 3)PLEASE PROVIDE DETAILS FOR THE ACTUAL SCOPE OF |
| | WORK. THE DETAILS ON THE PLAN, SHEET A0-0 DENOTES NEW |
| | CONSTRUCTION AND ARE FOR THE RAMP LOCATED AT THE |
| | SOUTHWEST CORNER OF THE BUILDING: |
| | |
| | A) SHOW EXISTING CONCRETE RAMP SLOPE AND |
| | PROPOSED SLOPE. |
| | B) SUBMIT GUARD/HAND RAIL SHOP DRAWINGS. |
| | C) SHOW ELEVATION OF EXISTING RAMP. |
| | D) SHOW THE PROPOSED EXTERIOR ACCESSIBLE ROUTE |
| | FROM PARKING TO RAMP. |
| | E) DETECTABLE WARNINGS IF APPLICABLE: |
| | |
| | 11-4.29.5 DETECTABLE WARNINGS AT HAZARDOUS VEHICULAR |
| | AREAS. |
| | IF A WALK CROSSES OR ADJOINS A VEHICULAR WAY, AND THE |
| | WALKING SURFACES ARE NOT SEPARATED BY CURBS, RAILINGS, |
| | OR OTHER ELEMENTS BETWEEN THE PEDESTRIAN AREAS AND |
| | VEHICULAR AREAS, THE BOUNDARY BETWEEN THE AREAS SHALL |
| | BE DEFINED BY A CONTINUOUS DETECTABLE WARNING WHICH IS |
| | 36 INCHES (915 MM) WIDE, COMPLYING WITH SECTION |
| | 11-4.29.2. |
| | |
| | 4) THE ARCHITECT SHALL LOCATE THE AREA OF WORK ON SHEET |
| | A0-0. |
| | |
| | 5) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE |
| | MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS |
| | NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE. |
| | FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE |
| | PERMIT ISSUANCE. |
| | |
| | |
| | REVIEW: KEN CONRAD |
| | PHONE: 561.805.6666 |
| | |
| | |
| | |