Plan Review Details - Permit 07060881
Plan Review Stops For Permit 07060881
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-11-05 Cont ID  
Sent By shill Date 2009-11-05 Time 11:28 Rev Time 0.00
Received By shill Date 2009-11-05 Time 11:28 Sent To  
Notes
2009-11-05 11:28:33KITCHEN WINDOW NOA AND SHUTTER NOA/INSTALLATION
 SCHEDULE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-10-28 Cont ID  
Sent By shill Date 2009-10-28 Time 09:29 Rev Time 0.00
Received By shill Date 2009-10-28 Time 09:29 Sent To  
Notes
2009-10-28 09:29:53REVISION A4, A5
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-10-28 Cont ID  
Sent By shill Date 2009-10-28 Time 09:27 Rev Time 0.00
Received By shill Date 2009-10-28 Time 09:27 Sent To  
Notes
2009-10-28 09:29:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IMPACT PROTECTION REQUIRED, FBC R301. SUBMIT SHUTTER
 PRODUCT APPROVAL AND INSTALLATION SCHEDULE HTTP://WWW.C
 ITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION
 .PDF
  
 2. THIS PERMIT WAS ISSUED WITH PROVISO,
 LANDSCAPE/IRRIGATION PLAN REQUIRED PRIOR TO C.O. PLEASE
 ADVISE AS TO STATUS OF THAT REVISION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-06-25 Cont ID  
Sent By shill Date 2009-06-25 Time 18:24 Rev Time 0.00
Received By shill Date 2009-06-24 Time 17:56 Sent To Z
Notes
2009-06-25 18:24:50REVISION DATED 4/25/9
 COMMENT LIST REVISED 7/8/9
  
 ****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1. M2.01, DETAIL FOR SECURING CONDENSING IS NOT CLEAR.
 TWO BRACKETS ARE GRAPHICALLY SHOWN ON ONE SIDE OF THE
 UNIT, BUT THE TEXT SPECIFIES 4. IF FOUR ARE INSTALLED,
 TWO PER SIDE, THIS LEAVES TWO SIDES WITHOUT BRACKETS,
 NOT CLEAR HOW THOSE TWO SIDES WILL RESIST WIND
 PRESSURES.
  
 PLEASE DO NOT RESUBMIT THE MECHANICAL SHEETS. EITHER
 PROVIDE A NEW DETAIL OR THIS WILL BE PROVISO ITEM,
 INSTALL IN ACCORDANCE WITH FBC R301, SUBJECT TO
 INSPECTOR'S DISCRETION.
  
 2. R703.6.3, DETAIL 4 A5 DOES NOT SHOW REQUIRED BOND
 BREAK. ***IF PLANS DO NOT NEED TO BE REVISED FOR OTHER
 REASONS, THIS WILL BE A REDLINE ITEM***
  
 3. A NEW WINDOW OPENING IS SHOWN, PLEASE PROVIDE
 FRAMING DETAIL FBC R301. ***IF PLANS DO NOT REQUIRE
 REVISION FOR OTHER REASONS, THIS WILL BE A PROVISO
 ITEM.**
  
 4. A4 STATES TO REPLACE EXIST NON ORIGINAL ALUMINUM
 CASEMENT WINDOW WITH AN ALUMINUM AWNING WINDOW, REUSED.
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE INSTALLED WINDOW, FAC9B72.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-04-17 Cont ID  
Sent By shill Date 2009-04-17 Time 14:05 Rev Time 0.00
Received By shill Date 2009-04-17 Time 14:05 Sent To  
Notes
2009-04-17 14:06:14REVISION DATED 3/9/9 OK (FOOTING)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-11 Cont ID  
Sent By amorse Date 2007-12-11 Time 17:45 Rev Time 0.00
Received By amorse Date 2007-12-11 Time 17:45 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-02 Cont ID  
Sent By amorse Date 2007-10-02 Time 18:38 Rev Time 0.00
Received By amorse Date 2007-10-02 Time 18:38 Sent To PC
Notes
2007-10-02 18:57:59 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM 1ST
 REVIEW ON 7/14/07:
  
 5)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR TO SUBMITTAL
 ****NOTE MAKE THE FOLLWING CORRECTIONS TO ENERGY
 CALC'S, WALLS ARE WOOD FRAME NOT CONCRETE, THEY ARE NOT
 SIGNED BY OWNER AGENT, AND UNLESS COMPLETE HOUSE IS
 BEING BROUGHT UP TO NEW ENERGY STANDARDS FORM 600C-04R
 SHOULD BE USED FOR ADDITIONS OR RENOVATIONS 600 SQ. FT.
 OR LESS****
  
 7)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
 ****NOTE THIS SHALL BE INCUDED ON THE PERMIT SET OF
 DRAWINGS****
  
 8)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
 ****NOTE ALTERATION LEVEL FITS THE DEFINITION OF A
 LEVEL 2, PLEASE SEE ATTACHED COPY OF CHAPTER 3
 CLASSIFICATION OF WORK****
  
 NEW COMMENTS
  
 1)PROVIDE PRODUCT APPROVALS FOR THE NEW FRONT ENTRY
 DOOR
  
 2)NEW NOTE UNDER WINDOW SCHEDULE ON A-3 IS INCORRECT
 PLEASE REMOVE, ALL OPENINGS WITHIN 30 FEET OF GRADE
 SHALL MEET LARGE MISSILE IMPACT REQUIREMENTS PER
 1609.1.4 (1) FBC
  
 3)PROVIDE PRODUCT APPROVALS FOR SHUTTERS FOR WINDOWS
 IN NEW LOCATIONS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-14 Cont ID  
Sent By amorse Date 2007-07-14 Time 07:38 Rev Time 0.00
Received By amorse Date 2007-07-14 Time 07:38 Sent To PC
Notes
2007-07-14 08:49:33 
  
 DENIED
  
 1)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER
 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY
 THE RESPONSIBLE ARCHITECT AND MUST,
 AT A MINIMUM CONTAIN
 ****1)FIRM/LICENSEE NAME,ADDRESS, AND TELEPHONE #
 ****2)FIRM/LICENSEE LICENSE #
 3)NAME OF PROJECT
 4)DATE PREPARED
 5)A SPACE FOR SIGNATURE & DATED SEAL
 6)A SPACE FOR PRINTED NAME OF PERSON
 SEALING THE DOCUMENT.
  
 2)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES. ALL
 CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 *****PROVIDE PRODUCT APPROVALS FOR ALL NEW DOORS AND
 WINDOWS AS WELL AS ROOFING PRODUCTS*****
  
 3)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 4)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 5)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 *****NOTE PLEASE CORRECT INFORMATION ON THE ENERGY
 CALC'S FLOOR TYPE IS NOT SLAB ON GRADE AS EXISTING
 BUILDING HAS CRAWL SPACE, WALLS ARE NOT CONCRETE, MORE
 THAN ONE TYPE OF CEILING IS PRESENT ON DRAWINGS.*****
  
 6)PROVIDE DETAILS OF ALL STRUCTURAL WORK, NEW COLUMNS
 AND BEAM, FRAMED WALL INFILL, ETC.
  
 7)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS
  
 8)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 9)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 10)PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4
 FBC
  
 11)PROVIDE DESIGN PRESSURES FOR ALL NEW DOOR AND
 WINDOW OPENINGS
  
 12)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 13)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
 14)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 15)ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICAL AND MECHANICAL AND ROOFING
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-04 Cont ID  
Sent By btrobaug Date 2008-12-04 Time 10:03 Rev Time 0.00
Received By btrobaug Date 2008-12-04 Time 09:56 Sent To PC
Notes
2008-12-04 10:03:12 
  
  
 REVISION DENIED
  
 THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED TO
 REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO THE
 DESIGNER TO BE REDRAWN.FS 471.025
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-26 Cont ID  
Sent By btrobaug Date 2007-09-26 Time 13:18 Rev Time 0.00
Received By btrobaug Date 2007-09-25 Time 06:35 Sent To P
Notes
2007-09-26 13:18:17 
  
  
 PROVISO
  
 THE SMOKE DETECTOR THAT WAS ADDED TO THE DEN BATHROOM
 IS IN VIOLATION OF NFPA-72, 11.8.3.5 (5) SMOKE ALARMS
 AND SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN A
 914-MM (36-IN.) HORIZONTAL PATH FROM A DOOR TO A
 KITCHEN OR A BATHROOM CONTAINING A SHOWER OR TUB. MUST
 NOT BE INSTALLED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By btrobaug Date 2007-06-29 Time 08:59 Rev Time 0.00
Received By btrobaug Date 2007-06-29 Time 06:58 Sent To M
Notes
2007-06-29 08:59:10 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE LOAD CALCULATIONS, INCLUDE ADDED LOADS, PER
 ARTICLE 220 PART III, STANDARD OR PART IV OPTIONAL,
 INDICATE METHOD USED, INDICATE THE SIZE OF THE EXISTING
 SERVICE. INDICATE THE SIZE AND TYPE OF THE SERVICE
 ENTRANCE CONDUCTORS ON THE RISER DIAGRAM, SHEET E2.01.
 PER 215.5.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.THE ONE SUBMITTED DOESNT CORRELATE THE
 LOADS WITH THE EQUIPMENT. SHEET E2.01.
  
 3} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.LOCATE SAME
 ON THE PLAN.
  
 4} THE SCUTTLE FOR AHU 1 MUST COMPLY WITH 210.63
 (RECEPTACLE).
  
 5} THE LOCATION OF THE NEW A/C SERVICE PANEL MUST
 COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. IT WOULD
 APPEAR IT IS LOCATED OVER THE CONDENSER PAD , WHICH
 WOULD BE A VIOLATION. PLEASE VERIFY AND RELOCATE NOW IF
 NECESSARY TO PREVENT AN INSPECTION ISSUE AFTER THE
 EQUIPMENT IS INSTALLED.
  
 NOTE: PLEASE VERIFY THAT THE NEW PANEL WILL BE FED FROM
 THE METER AND NOT SUBFED FROM THE EXISTING PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-10-27 Cont ID  
Sent By kstevens Date 2009-10-27 Time 15:04 Rev Time 0.00
Received By kstevens Date 2009-10-27 Time 15:04 Sent To  
Notes
2009-10-27 15:05:14PASSED -- REVISION REQUIRED THE GAS RISER PIPING SHALL
 REFLECT THE INSTALLATION.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-06-22 Cont ID  
Sent By lmartine Date 2009-06-22 Time 15:06 Rev Time 0.00
Received By lmartine Date 2009-06-22 Time 15:06 Sent To  
Notes
2009-06-22 15:07:45SEE APPROVAL ON PLANS BY JULIAN 6/22/09 LM
2007-06-27 09:14:35OK PER G JUDGE 6-27-07 NO FEE

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-11-02 Cont ID  
Sent By lmartine Date 2009-10-29 Time 13:48 Rev Time 0.00
Received By lmartine Date 2009-10-29 Time 13:48 Sent To  
Notes
2009-11-02 13:49:03GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-10-22 Cont ID  
Sent By kstevens Date 2009-10-22 Time 11:06 Rev Time 0.00
Received By kstevens Date 2009-10-22 Time 11:06 Sent To  
Notes
2009-10-22 11:08:38SENT TO KSTEVENS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-06-22 Cont ID  
Sent By lmartine Date 2009-06-22 Time 10:49 Rev Time 0.00
Received By shill Date 2009-06-03 Time 15:33 Sent To  
Notes
2009-07-02 11:45:08PLANS GIVEN TO AMY STELLY TO REVIEW IN MAGGIE'S
 ABSENCE. CONTRACTOR BRING SURVEY DRAWING (REQUESTED BY
 MAGGIE) TO AMY STELLY. 7/2/09. RB
  
  
2009-06-24 14:23:48TAKEN OF RESIDENTIAL BOARD, TO SMH DESK
  
2009-06-04 15:39:46TO R2

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 11:49 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 11:49 Sent To B
Notes
2009-04-17 11:50:07TO "SHILL"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-02 Cont ID  
Sent By adarroug Date 2008-12-02 Time 16:31 Rev Time 0.00
Received By adarroug Date 2008-12-02 Time 16:31 Sent To E
Notes
2008-12-02 16:31:45TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-26 Cont ID  
Sent By adarroug Date 2007-11-26 Time 16:38 Rev Time 0.00
Received By adarroug Date 2007-11-26 Time 16:38 Sent To Z
Notes
2007-11-26 16:38:48TO "Z" BOX/RESUB--NEW SHEET FOR "Z"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 09:08 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 09:08 Sent To Z
Notes
2007-09-17 09:08:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-14 Time   Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 13:54 Sent To  
Notes
2007-06-27 13:54:35TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-06-15 Cont ID  
Sent By rregueir Date 2009-06-15 Time 16:02 Rev Time 0.00
Received By rregueir Date 2009-06-15 Time 16:01 Sent To P
Notes
2009-06-15 16:02:30**PROVISO**
  
 AHU SERVICE PANEL SHALL BE WITHIN 6' OF ATTIC ACCESS
 PER FBC-R SECTION N1110.AB.3.5.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-06-29 Cont ID  
Sent By btrobaug Date 2007-09-25 Time 06:45 Rev Time 0.30
Received By tgordon Date 2007-06-29 Time 15:24 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-06-29 Cont ID  
Sent By kstevens Date 2009-06-29 Time 11:17 Rev Time 0.00
Received By kstevens Date 2009-06-29 Time 11:17 Sent To  
Notes
2009-06-29 11:18:01REVISION OK -- SANITARY ISOMETRIC RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-06-15 Cont ID  
Sent By kstevens Date 2009-06-15 Time 16:41 Rev Time 0.00
Received By kstevens Date 2009-06-15 Time 16:41 Sent To  
Notes
2009-06-15 16:50:44REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL
 DRAWING AND SPECIFICATION SHEETS. A TITLE BLOCK MUST,
 AT A MINIMUM, CONTAIN THE FOLLWOING INFORMATION:
 (1) FIRM NAME, ADDRESS AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER
 (3) NAME OR IDENTIFICATION OF PROJECT
 (4) DATE PREPARED
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL - (OK)
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 FAC 61G1-16.004 & FS 481.2055. -- THIS INFORMATION IS
 MISSING FROM THE 8-1/2 X 11 INCH SHEET WITH THE
 SANITARY RISER DIAGRAM.
  
 2. THE SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET THE CODE REQUIRMENTS.
 (A) THE DOUBLE LAV IS ON THE WALL OPPOSITE OF THE W/C
 AND SHOWER. THE RISER SHOWS IT AT THE WALL TO THE LEFT
 SIDE OF THE FIXTURES.
 (B) FIXTURES SHALL NOT BE DOUBLE TRAPPED. THE WATER
 CLOSET HAS AN INTEGRAL TRAP IN THE FIXTURE SO NO TRAP
 IS REQUIRED ON THE FIXTURE ROUGH.
 SECTIONS 106.1.1 & 1002.1/P3201.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-01 Cont ID  
Sent By jleech Date 2007-10-01 Time 09:11 Rev Time 0.00
Received By jleech Date 2007-10-01 Time 09:11 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By jleech Date 2007-07-11 Time 09:18 Rev Time 0.00
Received By jleech Date 2007-07-11 Time 07:51 Sent To B
Notes
2007-07-11 09:29:23SANITARY RISER DIAGRAM REQUIRED FOR 2ND FLOOR BATHROOM
 AND ADDED SINK. SEE FBC BUILDING CHAPTER 1
 ADMINISTRATION CODE SECTION 106.3.5.4(9).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2009-07-05 Cont ID  
Sent By mcruz Date 2009-07-05 Time 11:48 Rev Time 0.00
Received By mcruz Date 2009-07-05 Time 11:48 Sent To  
Notes
2009-07-05 11:48:32PASSED WITH PROVISO:
 THE LANDSCAPE/IRRIGATION PLANS SHALL BE APPROVED PRIOR
 TO FINAL C.O.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 15:26 Rev Time 0.00
Received By choops Date 2007-11-28 Time 15:26 Sent To B
Notes
2007-11-28 15:27:08***APPROVED - RESUB #2 - RESTAMPED PLANS***
  
 PROVISO:
  
 1)AS THE STRUCTURE IS NONCONFORMING WITH RESPECT TO
 THE REQUIRED SETBACK DIMENSIONS, AS PER SECTION
 94-513(A)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS:NONCONFORMING STRUCTURES OR BUILDINGS
 SHALL NOT BE IMPROVED, CONSTRUCTED, ENLARGED, OR
 ALTERED IN ANY MANNER TO CREATE A NEW NONCONFORMITY OR
 TO INCREASE AN EXISTING NONCONFORMITY, BUT MAY BE
 IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED AS LONG AS
 NO NEW NONCONFORMITY IS CREATED OR AN EXISTING
 NONCONFORMITY INCREASED.
 2)AS THE VALUE OF PROPOSED WORK EXCEEDS 50% OF THE
 VALUE OF THE HOME, LANDSCAPING SHALL BE BROUGHT TO
 CURRENT REGULATIONS, IF NOT ALREADY:FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By choops Date 2007-09-18 Time 15:05 Rev Time 0.00
Received By choops Date 2007-09-18 Time 15:05 Sent To E
Notes
2007-09-18 15:13:46***APPROVED - RESUB #1***
  
 PROVISO:
  
 1)AS THE STRUCTURE IS NONCONFORMING WITH RESPECT TO
 THE REQUIRED SETBACK DIMENSIONS, AS PER SECTION
 94-513(A)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS:NONCONFORMING STRUCTURES OR BUILDINGS
 SHALL NOT BE IMPROVED, CONSTRUCTED, ENLARGED, OR
 ALTERED IN ANY MANNER TO CREATE A NEW NONCONFORMITY OR
 TO INCREASE AN EXISTING NONCONFORMITY, BUT MAY BE
 IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED AS LONG AS
 NO NEW NONCONFORMITY IS CREATED OR AN EXISTING
 NONCONFORMITY INCREASED.
 2)AS THE VALUE OF PROPOSED WORK EXCEEDS 50% OF THE
 VALUE OF THE HOME, LANDSCAPING SHALL BE BROUGHT TO
 CURRENT REGULATIONS, IF NOT ALREADY:FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By choops Date 2007-06-27 Time 14:17 Rev Time 0.00
Received By choops Date 2007-06-27 Time 14:17 Sent To E
Notes
2007-06-27 14:20:44***FAILED***
  
  
 1)PROVIDE 2 COPIES OF A CURRENT SURVEY SHOWING THE
 SCOPE OF WORK WITH DIMENSIONS AND SETBACK DIMENSTIONS
 TO THE PROPERTY LINES.(NOTE:SHOW ANY EXTERIOR WORK
 BEING DONE: SHOW ANY PROPOSED A/C EQUIPMENT WITH
 SETBACKS, SHOW ANY OVERHANGS/PORCHES...ETC.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN