Plan Review Details - Permit 07060876
Plan Review Stops For Permit 07060876
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-03 Cont ID  
Sent By lmartine Date 2007-08-03 Time 12:05 Rev Time 0.00
Received By lmartine Date 2007-08-03 Time 12:05 Sent To  
Notes
2007-08-03 12:06:12INTERIOR DEMO ONLY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By mjacobs Date 2007-07-11 Time 11:35 Rev Time 0.00
Received By mjacobs Date 2007-07-11 Time 09:35 Sent To PC
Notes
2007-07-11 10:07:16BUILDING PLAN REVIEW
 PERMIT: 07060876
 ADD: 801 NORTHPOINT PKWY
 CONT: ALRALI CONST. CORP.
 TEL: (305)866-4700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE ADDRESS ON THE APPLICATION AND DRAWINGS SHALL
 INDICATE THE SUITE/BAY AND FLOOR NUMBER.
  
 3) 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)THE DESCRIPTION ON THE APPLICATION IS FOR A
 DEMOLITION PERMIT. HOWEVER THE DRAWINGS SUBMITTED
 INDICATE NEW WALL TO BE CONSTRUCTED. IF THIS
 APPLICATION IS FOR THE DEMOLITION PERMIT, ONLY THE
 DEMOLITION PAGES SHALL BE SUBMITTED.
  
 5)THE AA #0001897 SHOWS NO RELATION TOGAMBACH
 ARCHITECTS INC. THE NUMBER FOR THE BUSINESS ON THE DBPR
 WEB-SITE IS 13001005. CLARIFY AND STATE THE CORRECT
 BUSINESS NUMBER ON THE DRAWINGS. NOTE: CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. SEC.106.
  
 6)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-03 Cont ID  
Sent By lmartine Date 2007-08-03 Time 12:06 Rev Time 0.00
Received By lmartine Date 2007-08-03 Time 12:06 Sent To  
Notes
2007-08-03 12:07:15INTERIOR DEMO ONLY , OK PER DEWEY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By dpalmer Date 2007-06-29 Time 18:43 Rev Time 0.00
Received By dpalmer Date 2007-06-29 Time 17:52 Sent To  
Notes
2007-06-29 18:43:50 
  
 *** UNSAT ***
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004
 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE KNOW THAT PERMIT APPLICATION WAS
 SUBMITTED WITHOUT ANY SUITE/UNIT/SPACE #. PLEASE KNOW
 THAT A COPY OF THE PERMIT APPLICATION HAS BEEN
 FORWARDED TO THE ADDRESSING REVIEWER. ONCE THE
 SUITE/UNIT/SPACE NUMBER HAS BEEN DETERMINED PLEASE BE
 SURE THIS INFORMATION IS PLACED ON PLANS/TITLE BLOCKS.
 FAC 61G15-23.002, 61G1-16.004
  
 3) NOTE:PLEASE SEE THERE ARE DISCREPANCIES WITH THE
 PERMIT APPLICATION AND THE PLANS AS SUBMITTED. PLEASE
 SEE PERMIT APPLICATION MENTIONS *DEMOLISH SOME
 PARTITIONS* HOWEVER THE PLANS ALSO INCLUDE SOME SHEETS
 FOR NEW WORK?
 PLEASE CLARIFY.
 FBC 106.1, 106.3.5.1.2
  
  
 4) NOTE: PLEASE SEE THE INFORMATION AS STATED ON TITLE
 BLOCKS FOR THE ARCHITECTURAL FIRM DOES NOT CORRELATE
 WITH THE STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION. PLEASE SEE I HAVE ATTACHED THE PRINT OUT AS
 OF THIS REVIEWFROM DBPR WHICH SHOWS DIFFERENT LICENSE
 INFORMATION THAN THAT ONE PLANS.
 ** PLEASE KNOW THIS IS REQUIRED OF ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
 FAC 61G1-16.004, FS 481.219
  
 5) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR NEW WORK.
 PLEASE SEE THE 2004 FBC ESPECIALLY CHAPTER 13. PLEASE
 SEE THE 2005 NEC FOR OTHER ITEMS RELATED TO DESIGN AS
 WELL AS NFPA-101 AND NFPA-72
  
 6) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR
 MINIMUM LEVELS FOR FIRE ALARMS DEVICES TO BE STATED FOR
 ANY CHANGES. PLEASE SHOW ANY NEW EXISTING WHICH MEETS
 THIS SECTION WHERE WORK IS BEING AND CHANGES ARE BEING
 MADE.
  
 7) NOTE: PLEASE SEE THE VALUE ON PERMIT APPLICATION IS
 YET TO BE CONFIRMED UNTIL CLARIFICATION OF THE SCOPE OF
 WORK.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-07 Cont ID  
Sent By mwennerg Date 2007-09-07 Time 09:55 Rev Time 0.00
Received By mwennerg Date 2007-09-07 Time 09:55 Sent To  
Notes
2007-09-07 09:56:19APPROVED FOR DEMO ONLY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-07-06 Cont ID  
Sent By mwennerg Date 2007-07-06 Time 13:44 Rev Time 0.00
Received By mwennerg Date 2007-07-06 Time 13:44 Sent To  
Notes
2007-07-06 13:49:22***PROVISO***
  
 DEMOLITION ONLY
  
 1) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241.
  
 2) SITE SHALL BE KEPT CLEAN OF EXCESSIVE CONSTRUCTION
 DEBRIS ON A DAILY BASIS.
  
 3) PLANS ADVISE NO FIRE SPRINKLER SYSTEM. PLEASE ADVISE
 IF BUILDING HAS FIRE ALARM SYSTEM, AND IF SO WILL IT BE
 IMPACTED BY WORK.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 15:01 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 15:01 Sent To B
Notes
2008-04-14 08:17:064/14/08--TO "LMARTINEZ" DESK--REV
2008-04-08 15:01:33TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-23 Time 15:57 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 15:57 Sent To  
Notes
2007-08-01 14:31:26TO "COMM" BD#57
2007-07-27 15:57:55WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-11 Time   Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 13:09 Sent To  
Notes
2007-06-29 13:00:51TO "BOB"#4
2007-06-27 13:09:37WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 15:23 Rev Time 0.20
Received By tgordon Date 2007-07-03 Time 15:23 Sent To  
Notes
2007-07-03 15:24:38NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-08-03 Cont ID  
Sent By lmartine Date 2007-08-03 Time 12:07 Rev Time 0.00
Received By lmartine Date 2007-08-03 Time 12:07 Sent To  
Notes
2007-08-03 12:08:48NO PLUMBING INFORMATION GIVEN TO REVIEW

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-09 Cont ID  
Sent By jleech Date 2007-07-09 Time 08:49 Rev Time 0.00
Received By jleech Date 2007-07-09 Time 08:43 Sent To  
Notes
2007-07-09 08:53:23DENIED;
 1. NOT ENOUGH INFORMATION TO DO A PLUMBING REVIEW.
 A) PLUMBING DETAILS REQUIRED FOR COFFEE SHOP.
 B) WHAT IS GOING INTO THE MEDICAL AREAS?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695