| 2007-07-11 09:47:20 | 1. ENTIRE BUILDING IS TO BE COMPLETELY FIRE SPRINKLER |
| | PROTECTED. THIS PROTECTION SHALL INCLUDE ALL |
| | MECHANICAL, ELECTRICAL, PLUMBING, ELEVATOR AND JANITOR |
| | EQUIPMENT ROOMS. |
| | |
| | 2. NO ARCHITECTURAL FEATURES OF THE BUILDING SHALL NOT |
| | INTERFERE WITH THE OPERATION OF ANY FIRE SPRINKLER |
| | HEADS. |
| | |
| | 3. EACH FIRE DEPARTMENT CONNECTION DISPLAYED SHALL BE |
| | EQUIPPED WITH KNOX-BOX LOCKING CAPS. |
| | |
| | 4. ON SEVERAL SHEETS, KEY NOTE # 6 "FS WATER CURTAIN 6" |
| | ON CENTER" ARE DISPLAYED. IT APPEARS IN SOME AREAS THAT |
| | THIS WATER CURTAIN IS PROTECTING DOOR OPENINGS. |
| | TYPICALLY WATER CURTAINS ARE USED TO PROTECT WINDOW |
| | WALLS BUT NOT OPERABLE DOORS. PLEASE PROVIDE RATIONALE |
| | FOR THIS DESIGN AT DOOR OPENINGS AND BE AVAILABLE TO |
| | DEMONSTRATE CODE ALLOWANCES FOR THIS ACTIVITY. |
| | |
| | 5. ALL CONTROL VALVES AND TAMPER SWITCHES SHALL BE |
| | PROVIDED WITH APPROPRIATE SIGNAGE. |
| | |
| | 6. NO FIRE SPRINKLER PROTECTION DISPLAYED IN DIMMER |
| | CLOSET DISPLAYED ON PAGE FP1-1.1. |
| | |
| | 7. PUMP ROOM DOORS SHALL NOT INTERFERE WITH CONNECTION |
| | TO THE FDC SHOWN ON PAGE FP1-1.1. |
| | |
| | 8. THE ENTIRE FIRE SPRINKLER SYSTEM AND FIRE PUMP |
| | ASSEMBLY SHALL BE INSTALLED TO CODE AND IN AN APPROVED |
| | WORKMANLIKE MANNER. |
| | |
| | 9. THE FIRE SPRINKLER HEAD IN MECHANICAL ROOM AND |
| | JANITOR CLOSET NEAR STAIR # 12 DISPLAYED ON PAGE |
| | FP1-1.2 DOES NOT APPEAR TO BE CONNECTED TO ANY FIRE |
| | SPRINKLER PIPING. |
| | |
| | 10. TWO SMALL AREAS EQUIPPED WITH DOORS ARE ABSENT OF |
| | FIRE SPRINKLER HEADS (BOTTOM CENTER) ON PAGE FP1-3.1. |
| | |
| | 11. PLEASE CONTACT THIS OFFICE TO DISCUSS STANDPIPE |
| | SYSTEM LOCATED BEHIND DOOR ON PAGE FP1-3.2. |
| | |
| | 12. FIRE SPRINKLER PROTECTION SHALL BE PROVIDED |
| | UNDERNEATH AIR CONDITIONING DUCTS OVER FOUR FEET WIDE. |
| | |
| | 13. AREAS PLANNED FOR STORAGE LOCATED UNDERNEATH ANY |
| | STAIRS SHALL BE PROVIDED WITH FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 14. ALL FIRE SPRINKLER BULK MAINS AND BRANCH LINES |
| | SHALL BE PROPERLY SUPPORTED WITH THE APPROPRIATE |
| | DEVICES. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION |