| 2007-07-13 10:41:11 | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SPECIFY THE THE TIE BEAM SIZE AND REINFORCEMENT. |
| | |
| | 4) SPECIFY THE STEEL REINFORCEMENT IN THE FOOTING. |
| | |
| | 5) R 403.1.4 MINIMUM DEPTH. |
| | ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 |
| | INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R404.1.6 HEIGHT ABOVE |
| | FINISHED GRADE. |
| | CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| | ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| | ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| | VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| | ELSEWHERE. |
| | |
| | 7)PROVIDE A LINTEL SCHEDULE OR DROP BEAM DETAIL AT |
| | WINDOW AND DOOR OPENINGS. IF LINTELS WERE USED, SUBMIT |
| | PRODUCT APPROVALS. |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R806.1 VENTILATION |
| | REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1/8 |
| | INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | R806.2 MINIMUM AREA. |
| | THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS |
| | THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED |
| | EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED |
| | TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE |
| | THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS |
| | PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF |
| | THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) |
| | ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE |
| | REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| | AS AN ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA |
| | MAY BE REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING |
| | A TRANSMISSION RATE NOT EXCEEDING 1 PERM (57.4 MG/S ? M |
| | 2 ? PA) IS INSTALLED ON THE WARM SIDE OF THE CEILING. |
| | SPECIFY THE SIZE AND SPACING OF ATTIC VENTS REQUIRED TO |
| | COMPLY. |
| | |
| | 9) R807.1 ATTIC ACCESS. |
| | IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED |
| | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) |
| | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR |
| | GREATER. |
| | THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22 |
| | INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE |
| | LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE |
| | LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED |
| | HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME |
| | POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3 |
| | FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| | LOCATED IN ATTICS. |
| | |
| | 10) SHOW COMPLIANCE WITH FBC R320 FOR PROTECTION |
| | AGAINST TERMITES. TERMITE PROTECTION SHALL BE PROVIDED |
| | BY REGISTERED TERMITICIDES, INCLUDING SOIL APPLIED |
| | PESTICIDES, BAITING SYSTEMS, AND PESTICIDES APPLIED TO |
| | WOOD, OR OTHER APPROVED METHODS OF TERMITE PROTECTION |
| | LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| | CONSTRUCTION (SEE SECTION 202 , REGISTERED |
| | TERMITICIDE). UPON COMPLETION OF THE APPLICATION OF THE |
| | TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF |
| | COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT |
| | BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE |
| | FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A |
| | COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN |
| | TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND |
| | LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF |
| | AGRICULTURE AND CONSUMER SERVICES.? |
| | |
| | 11) SHOW COMPLIANCE WITH FBC R506 FOR CONCRETE FLOORS |
| | ON THE GROUND. VAPOR BARIER, REINFORCEMENT, ETC. |
| | |
| | 12) SHOW COMPLIANCE WITH R322.1.1 |
| | ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, TRIPLEXES, |
| | CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT LEAST ONE |
| | BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE |
| | BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH |
| | A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING. |
| | HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE |
| | LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF |
| | NOT LESS THAN 29 INCHES (737 MM). |
| | |
| | 13)ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE |
| | WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC |
| | RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL |
| | BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT |
| | 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT |
| | INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS |
| | SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 |
| | MPH OR GREATER DESIGNWIND SPEEDS IN ACCORDANCE WITH |
| | FIGURE R803.2.3.1. PLEASE REVISE NOTES ON A2. |
| | |
| | 14) SPECIFY THE ROOF TRUSS SPACING ON THE PLANS. |
| | |
| | 15) SPECIFY THE OVERHANG DISTANCE AT THE GABLE END. |
| | |
| | 16) PROVIDE SIGNED AND SEALED ROOF TRUSS ENGINEERING |
| | FOR THE BUILDING INSPECTOR IN THE FIELD AT TIME OF ROOF |
| | FRAMING INSPECTION. |
| | |
| | 17)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 18) SUBMIT PRODUCT APPROVALS FOR THE INSWING EXTERIOR |
| | DOOR. |
| | |
| | 19) SPECIFY THE FASTENER/ANCHOR TYPE AND FASTENER |
| | SPACING FOR THE STORM PANELS. CIRCLE THE ONES THAT WILL |
| | BE USED ON THE PRODUCT APPROVAL. |
| | |
| | 20) THE VALUE OF THE PROJECT HAS BEEN INCREASE BASED ON |
| | ICC VALUATION DATA TO $44,814.00. ADDITIONAL PERMIT |
| | FEES ARE DUE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |