Plan Review Details - Permit 07060850
Plan Review Stops For Permit 07060850
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-12 Cont ID  
Sent By rmcdouga Date 2008-02-12 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2008-02-12 Time 11:48 Sent To  
Notes
2008-02-12 13:39:032004 FBC W/2006 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE NOTICE OF COMMENCEMENT WILL NEED TO BE RECORDED
 AND A COPY SUBMITTED.
  
 2) PLEASE CLARIFY IF THE ROOF-CEILING CONSTRUCTION IS
 CONVENTIONAL FRAMING OR SITE BUILT TRUSSES. IF THE ROOF
 IS CONVENTIONAL FRAMING, SUBMIT DETAILS SHOWING THE
 RAFTER, CEILING JOIST AND RIDGE SIZES AND CONNECTORS.
 THE CONVENTIONAL ROOF FRAMING IS REQUIRED TO COMPLY
 WITH THE IBHS GUIDELINE FOR HURRICANE RESISTANT
 CONSTRUCTION OR ASCE7-02.
 IF SITE BUILT-UP TRUSSES ARE USED, SUBMIT DETAILS FOR
 THE SITE BUILT UP-TRUSSES. PROVIDE DETAILS FOR EACH
 DIFFERENT TYPE OF TRUSS, SPECIFY THE LUMBER TYPE AND
 SIZES FOR THE TOP AND BOTTOM CORDS AND WEBS. SPECIFY
 HOW THE CORDS AND WEBS WILL BE CONNECTED TOGETHER.
 PROVIDE ENGINEERING OR CALCULATIONS INDICATING THAT THE
 TRUSSES ARE CAPABLE OFWITHSTANDING 140 MPH WINDLOADS.
 FBC R 802.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-02 Cont ID  
Sent By rmcdouga Date 2008-01-02 Time 10:15 Rev Time 0.00
Received By rmcdouga Date 2008-01-02 Time 10:15 Sent To  
Notes
2008-01-02 10:17:292004 FBC W/2007 REVISIONS
 ADDITION (AS BUILT)
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT PRODUCT APPROVALS FOR LINTELS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE ADDITION. FAC RULE 9B-72.
  
 4) SHOW COMPLIANCE WITH FBC R320 FOR PROTECTION AGAINST
 TERMITES. TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL APPLIED
 PESTICIDES, BAITING SYSTEMS, AND PESTICIDES APPLIED TO
 WOOD, OR OTHER APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION (SEE SECTION 202 , REGISTERED
 TERMITICIDE). UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: "THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES."
  
 5) SUBMIT 2 COPIES OF SIGNED AND SEALED ROOF TRUSS
 DRAWINGS AND LAYOUT THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 ADDITION.
  
 6)WPB ADMIN CODE FBC 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE INSWING AND
 OUTSWING EXTERIOR DOORS. FAC RULE 9B-72.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG
 WINDOWS. FAC RULE 9B-72.
  
 9) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK. FAC
 RULE 9B-72.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE ROOF SHINGLES. FAC
 RULE 9B-72.
  
 11) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS.
 SPECIFY THE FASTENER/ANCHOR TYPE AND FASTENER SPACING
 FOR THE STORM PANELS. CIRCLE THE ONES THAT WILL BE USED
 ON THE PRODUCT APPROVAL.
  
 NOTE: 2 COPIES OF PRODUCT APPROVALS ARE REQUIRED.
  
 12) SUBMIT 2 COPIES OF SURVEY/SITE PLAN SHOWING THE
 LOCATION OF THE ADDITION AND THE DISTANCE TO PROPERTY
 LINES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By rmcdouga Date 2007-07-13 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2007-07-13 Time 10:36 Sent To  
Notes
2007-07-13 10:41:11DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SPECIFY THE THE TIE BEAM SIZE AND REINFORCEMENT.
  
 4) SPECIFY THE STEEL REINFORCEMENT IN THE FOOTING.
  
 5) R 403.1.4 MINIMUM DEPTH.
 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 6) SHOW COMPLIANCE WITH FBC R404.1.6 HEIGHT ABOVE
 FINISHED GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 7)PROVIDE A LINTEL SCHEDULE OR DROP BEAM DETAIL AT
 WINDOW AND DOOR OPENINGS. IF LINTELS WERE USED, SUBMIT
 PRODUCT APPROVALS.
  
 8) SHOW COMPLIANCE WITH FBC R806.1 VENTILATION
 REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1/8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
 R806.2 MINIMUM AREA.
 THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS
 THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED
 EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED
 TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE
 THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS
 PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF
 THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM)
 ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE
 REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
 AS AN ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA
 MAY BE REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING
 A TRANSMISSION RATE NOT EXCEEDING 1 PERM (57.4 MG/S ? M
 2 ? PA) IS INSTALLED ON THE WARM SIDE OF THE CEILING.
 SPECIFY THE SIZE AND SPACING OF ATTIC VENTS REQUIRED TO
 COMPLY.
  
 9) R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 10) SHOW COMPLIANCE WITH FBC R320 FOR PROTECTION
 AGAINST TERMITES. TERMITE PROTECTION SHALL BE PROVIDED
 BY REGISTERED TERMITICIDES, INCLUDING SOIL APPLIED
 PESTICIDES, BAITING SYSTEMS, AND PESTICIDES APPLIED TO
 WOOD, OR OTHER APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION (SEE SECTION 202 , REGISTERED
 TERMITICIDE). UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 11) SHOW COMPLIANCE WITH FBC R506 FOR CONCRETE FLOORS
 ON THE GROUND. VAPOR BARIER, REINFORCEMENT, ETC.
  
 12) SHOW COMPLIANCE WITH R322.1.1
 ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, TRIPLEXES,
 CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT LEAST ONE
 BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE
 BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH
 A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING.
 HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE
 LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF
 NOT LESS THAN 29 INCHES (737 MM).
  
 13)ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE
 WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS
 SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130
 MPH OR GREATER DESIGNWIND SPEEDS IN ACCORDANCE WITH
 FIGURE R803.2.3.1. PLEASE REVISE NOTES ON A2.
  
 14) SPECIFY THE ROOF TRUSS SPACING ON THE PLANS.
  
 15) SPECIFY THE OVERHANG DISTANCE AT THE GABLE END.
  
 16) PROVIDE SIGNED AND SEALED ROOF TRUSS ENGINEERING
 FOR THE BUILDING INSPECTOR IN THE FIELD AT TIME OF ROOF
 FRAMING INSPECTION.
  
 17)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 18) SUBMIT PRODUCT APPROVALS FOR THE INSWING EXTERIOR
 DOOR.
  
 19) SPECIFY THE FASTENER/ANCHOR TYPE AND FASTENER
 SPACING FOR THE STORM PANELS. CIRCLE THE ONES THAT WILL
 BE USED ON THE PRODUCT APPROVAL.
  
 20) THE VALUE OF THE PROJECT HAS BEEN INCREASE BASED ON
 ICC VALUATION DATA TO $44,814.00. ADDITIONAL PERMIT
 FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-02-05 Cont ID  
Sent By btrobaug Date 2008-02-05 Time 08:19 Rev Time 0.00
Received By btrobaug Date 2008-02-05 Time 07:01 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-20 Cont ID  
Sent By btrobaug Date 2007-12-20 Time 08:08 Rev Time 0.00
Received By btrobaug Date 2007-12-20 Time 07:36 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By btrobaug Date 2007-06-29 Time 16:24 Rev Time 0.00
Received By btrobaug Date 2007-06-29 Time 15:31 Sent To M
Notes
2007-06-29 16:24:23 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THERE IS NO INDICATION HOW THE "SUB-PANEL" IS FED.
 PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE
 AND TYPE, GROUNDING DETAILS PER 215.5, 250.52 AND
 250.66.
  
 2} THERE IS A CONDENSING UNIT ON THE PLAN, INDICATE IF
 NEW OR RELOCATED. A RECEPTACLE IS REQUIRED PER 210.63.
  
 3} THE 240 VOLT OUTLET AT THE CONDENSER NEEDS TO BE A
 DISCONNECT PER 440.14.
  
 4} A RECEPTACLE MUST BE ADDED IN THE BEDROOM PER
 210.52(A) SPACING REQUIREMENTS.
  
 5} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
 SHOW LOCATIONS FOR COMPLIANCE ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-04 Cont ID  
Sent By adarroug Date 2008-02-04 Time 08:24 Rev Time 0.00
Received By adarroug Date 2008-02-04 Time 08:24 Sent To Z
Notes
2008-02-04 08:25:16TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 19:40 Rev Time 0.00
Received By shill Date 2007-12-13 Time 19:40 Sent To Z
Notes
2007-12-13 19:40:49TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-13 Cont ID  
Sent By rmcdouga Date 2007-07-13 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2007-06-27 Time 10:53 Sent To  
Notes
2007-06-27 10:53:12TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-05 Cont ID  
Sent By tgordon Date 2008-02-05 Time 08:51 Rev Time 0.30
Received By tgordon Date 2008-02-05 Time 08:51 Sent To P
Notes
2008-02-05 08:56:33*** PROVISO ***
 1) CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE A/C
 CONDENSER UNIT, SEE 2004 FBC/R M303.4.2.
  
 2) ATTIC INSULATION NEEDS TO BE R-30, PER 2004 FBC
 13-604.1.C.1 (1).
  
 3) BATHROOM TO HAVE AN EXHAUST FAN, SEE 2004 FBC/R
 R303.3 EXCEPTION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-31 Cont ID  
Sent By tgordon Date 2007-12-31 Time 09:11 Rev Time 0.30
Received By tgordon Date 2007-12-31 Time 09:11 Sent To B
Notes
2007-12-31 09:15:49*** PROVISO ***
 1) CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE A/C
 CONDENSER UNIT, SEE 2004 FBC/R M303.4.2.
  
 2) ATTIC INSULATION NEEDS TO BE R-30, PER 2004 FBC
 13-604.1.C.1 (1).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By tgordon Date 2007-07-05 Time 08:37 Rev Time 0.30
Received By tgordon Date 2007-07-05 Time 08:37 Sent To P
Notes
2007-07-05 08:48:36*** DENIED ***
 1) PROVIDE RETURN AIR FOR BEDROOM TO GET BACK TO AIR
 HANDLER.
  
 2) SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS.
  
 3) SHOW CLOTHES DRYER VENT ON MECHANICAL PLAN.
  
 4) BE ADVISED MECHANICAL PLAN SHOWS NO SUPPLY AIR TO
 THE COMPUTER AREA.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-07 Cont ID  
Sent By jleech Date 2008-02-07 Time 09:26 Rev Time 0.00
Received By jleech Date 2008-02-07 Time 09:23 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-31 Cont ID  
Sent By jleech Date 2007-12-31 Time 08:36 Rev Time 0.00
Received By jleech Date 2007-12-31 Time 08:36 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By jleech Date 2007-07-11 Time 09:52 Rev Time 0.00
Received By jleech Date 2007-07-11 Time 09:45 Sent To B
Notes
2007-07-11 10:03:49DENIED;
 RISER DIAGRAM DOES NOT MEET CODE.
 A) THE TUB IS NOT VENTED, THE LAV. VENT SHOULD BE
 UP STREAM OF THE TUB. SEE FBC-2004 PLUMBING SECTION
 909.1.
 B) THE AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO
 BE 3". FBC-2004 PLUMBING SECTION 406.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-04 Cont ID  
Sent By choops Date 2008-02-04 Time 12:02 Rev Time 0.00
Received By choops Date 2008-02-04 Time 12:02 Sent To E
Notes
2008-02-04 11:54:33***APPROVED - RESUB #2***
  
 NOTE:NO SEPARATE DWELLING UNIT IS PERMITTED WITHIN
 THE SINGLE FAMILY LOW-DENSITY (SF7) RESIDENTIAL ZONING
 DESIGNATION.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-18 Cont ID  
Sent By choops Date 2007-12-18 Time 14:38 Rev Time 0.00
Received By choops Date 2007-12-18 Time 14:38 Sent To E
Notes
2007-12-18 14:54:28***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 NEW COMMENTS:
  
 1)AS THE VALUE OF WORK AS NOW BEEN CORRECTED,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS): WHEN THE VALUE OF THE
 PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
 2)NO SURVEYS WERE PROVIDED WITH THIS SUBMITTAL.
 PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING THE
 LOCATION OF THE ADDITION WITH DIMENSIONS AND SETBACK
 DIMENSIONS TO ALL PROPERTY LINES.
  
 3)THE EAST AND WEST ELEVATIONS (SHEET A-1) LABEL THE
 DOORS AS WINDOWS.CLARIFY.
  
 NOTE:NO SEPARATE DWELLING UNIT IS PERMITTED WITHIN
 THE SINGLE FAMILY LOW-DENSITY (SF7) RESIDENTIAL ZONING
 DESIGNATION.
  
 NOTE:ALL ROOMS IN THE DWELLING UNIT MUST BE
 ACCESSIBLE FROM THE INTERIOR OF THE UNIT.
  
 NOTE:NO KITCHEN FACILITIES PERMITTED WITHIN THE
 ADDITION, NO STOVE/RANGE, NO FULL SIZE REFRIGERATOR.
  
 NOTE:NOT MORE THAN TWO (2) UNRELATED INDIVIDUALS
 (INCLUDING THE OWNER) SHALL BE PERMITTED TO RESIDE
 WITHIN THE SINGLE-FAMILY DWELLING.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By choops Date 2007-06-28 Time 08:21 Rev Time 0.00
Received By choops Date 2007-06-28 Time 08:21 Sent To E
Notes
2007-06-28 08:24:26***FAILED***
  
  
 1)SEPERATE DWELLING UNIT NOT PERMITTED.ADDITION
 MUST HAVE INTERIOR ACCESS.
  
 2)SURVEY TO INDICATE PROPOSED A/C UNIT WITH SETBACK
 DIMENSIONS TO PROPERTY LINES.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720