| 2007-07-13 15:22:38 | **** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING |
| | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED |
| | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 |
| | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE STATING THE |
| | SOUTH FLORIDA BUILDING CODE WHICH HAS NOT BEEN IN |
| | EFFECT FOR SEVERAL YEARS. PLEASE SEE COMMENT ABOVE AND |
| | ADJUST TITLE BLOCKS. |
| | THIS COMMENT IS FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | FBC 106.1.2 |
| | ** COMMENT PREVIOUSLY MADE ON OTHER PROJECTS |
| | |
| | 3) NOTE: PLEASE SEE THE MISSING LICENSE INFORMATION FOR |
| | THE FIRM. PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | FAC 61G15-23.002 AND FS 471.023. |
| | ** COMMENT PREVIOUSLY MADE ON OTHER PROJECTS. |
| | |
| | 4) NOTE: PLEASE IDENTIFY WHICH PANEL IS THE NEW ONE |
| | BEING FED. THE BASE BUILDING REFERENCED PLANS ARE |
| | INDICATING NUMEROUS PANELS HOWEVER THE NEW SHEETS |
| | SHOULD INDICATE THE PANEL FEED ETC. |
| | 215.5, 230, 240, 310.16 ETC |
| | FBC 106.1.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |