Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-06-28 Cont ID  
Sent By mwennerg Date 2007-06-28 Time 09:02 Rev Time 0.00
Received By mwennerg Date 2007-06-28 Time 09:02 Sent To  
Notes
2007-06-28 09:04:15IF BUILDING IS EQUIPPED WITH A FIRE ALARM SYSTEM, THE
 HOOD/SUPPRESSION SHALL BE TIED IN AND INITIATE A
 GENERAL ALARM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-28 Cont ID  
Sent By mwennerg Date 2007-06-28 Time 09:13 Rev Time 0.00
Received By mwennerg Date 2007-06-27 Time 09:24 Sent To  
Notes
2007-06-27 09:24:20TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-06-27 Time 15:54 Rev Time 0.30
Received By tgordon Date 2007-06-27 Time 15:54 Sent To FIRE
Notes
2007-06-27 15:58:04*** PROVISO ***
 1) FUSIBLE LINKS ARE REQUIRED OVER COOKING APPLIANCES
 AND IN THE DUCTS, SEE INSTRUCTION MANUAL 3-27.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.