| 2007-06-27 14:40:55 | |
| | |
| | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE PLANS ARE MISSING THE FOLLOWING |
| | REQUIRED CODES TO BE STATED ON PLANS AND FOR DESIGN. |
| | PLEASE SEE THE FOLLOWING WHICH WAS ADOPTED AS OF |
| | DECEMBER 8TH, 2006. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE KNOW THE PLANS WILL BE ROUTED TO THE |
| | ADDRESSING REVIEWER AS THE PALM BEACH COUNTY PROPERTY |
| | APPRAISER'S OFFICE DOES NOT INDICATE AND ADDRESS, OUR |
| | SYSTEM SHOWS 1571 6TH ST AND THE PLANS DO NOT INDICATE |
| | ANY ADDRESS. |
| | PLEASE KNOW ONCE THE ADDRESS HAS BEEN DECIDED AND |
| | CORRECTED, PLEASE REVISED TITLE BLOCKS OF PLANS |
| | ACCORDINGLY. |
| | FAC61G1-16.004 |
| | |
| | 3) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK SHALL BE BASED ON THE FBC AND THE ADOPTED |
| | SUPPORTING DOCUMENTS. PLEASE SEE THE VALUE SHALL |
| | INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST |
| | ETC AS STATED IN THE FBC 108.3 |
| | PLEASE SEE THIS INCLUDES EQUIPMENT, MATERIALS ETC EVEN |
| | IF OWNER SUPPLIED. PLEASE SEE THE VALUE WILL BE |
| | ADJUSTED. |
| | |
| | 4) NOTE: PLEASE SEE THE PERMIT IS BEING APPLIED AS |
| | OWNER/ BUILDER WHERE THE PALM BEACH COUNTY PROPERTY |
| | APPRAISER'S OFFICE ALREADY LIST THIS OWNER NOT ONLY ON |
| | SEVERAL OTHER PROPERTIES BUT ALSO WITH HOMESTEAD |
| | EXEMPTION LISTED ON MORE THEN ONE PROPERTY WHICH IS NOT |
| | PERMITTED UNDER FLORIDA LAW. PLEASE SEE THIS |
| | INFORMATION FOR MULTIPLE HOMESTEADS WILL BE FORWARDED |
| | TO THE PBCPA OFFICE. |
| | PLEASE SEE THAT IN ORDER TO PULL AN OWNER/BUILDER |
| | PERMIT YOU MUST MEET THE EXCEPTION UNDER FS 489. PLEASE |
| | KNOW THIS MAY AFFECT THE PERMIT AS APPLIED AND A |
| | CONTRACTOR MAY BE REQUIRED. INFORMATION MAY ALSO BE |
| | FORWARDED TO THE COUNTY AND STATE LICENSING BOARD FOR |
| | REVIEW. |
| | |
| | 5) NOTE: PLEASE CLARIFY THE MAIN DISCONNECT AS REQUIRED |
| | PER 230.70,230.71. |
| | PLEASE SEE THE RISER MENTIONS A MAIN @ PANEL HOWEVER AS |
| | THE LOCATION OF THE PANEL IS NOT SHOWN, IT CAN NOT BE |
| | DETERMINED AT THIS TIME IF CODE COMPLIANCE IS MET. |
| | PLEASE ALSO SEE NEXT COMMENT. |
| | |
| | 6) NOTE: PLEASE SHOW THE LOCATION(S) OF ALL SERVICE |
| | EQUIPMENT AND PANEL(S). |
| | 110.26,240.24,408.7 ETC |
| | FBC 106.3.5.4 |
| | |
| | 7) NOTE: PLEASE INDICATE THE AIC RATINGS ON NEW RISER |
| | AS THE NOTED RATING ABOVE PANEL SCHEDULE MAY CHANGE |
| | ONCE THE RISER IS REVISED. 110.9 |
| | |
| | 8) NOTE: PLEASE SEE MISSING THE RECEPTACLE FOR THE |
| | DISHWASHER AS THE PLANS ONLY APPEAR TO SHOW A COUNTER |
| | SPACE RECEPTACLE AND THE PANEL SCHEDULE DOES SHOW AS |
| | DISHWASHER CIRCUIT. |
| | |
| | 9) NOTE: PLEASE SEE THE MISSING RECEPTACLE FOR THE |
| | MICROWAVE WHICH IS LISTED ON LOAD CALCULATIONS BUT NOT |
| | SHOWN ON PLANS. |
| | 408.4, FBC 106.1.2, 106.3.5.4 |
| | |
| | 10) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS |
| | THE LOADS FOR ALL SMALL APPLIANCE AND DINING ROOM |
| | CIRCUITS SHALL BE FIGURED INTO THE LOAD CALCULATIONS. |
| | PLEASE CLARIFY THE DINING ROOM/AREA. |
| | |
| | 11) NOTE: PLEASE SEE THE PLANS NEEDS TO SHOW ALL |
| | LOCATION AND IDENTIFY THE LOCATIONS OF THE AHU AND |
| | WATER HEATER. |
| | PLANS INDICATE A 220 RECEPTACLE FOR THE WATER HEATER |
| | WHICH IS NOT PERMITTED.422.30 |
| | PLEASE SEE MISSING DISCONNECTS PER 440.11 AND 422.31 |
| | |
| | 12) NOTE: PLEASE SEE 422.13 UNDER THE 2005 NEC AS THE |
| | WATER HEATER NEEDS TO BE SHOWN AT 125%. |
| | |
| | 13) NOTE: PLEASE SHOW DISCONNECT REQUIRED FOR THE CU. |
| | 440.11 |
| | FBC 106.3.5.4 |
| | |
| | 14) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL BE |
| | SPECIFIC FOR ALL CIRCUIT NUMBERS AND DESIGNATIONS ON |
| | EACH CIRCUIT SHALL BE SPECIFIC TO ALL ROOMS AND AREAS |
| | IN WHICH THEY FEED. |
| | PLEASE PLACE THE ROOM AND AREA DESIGNATIONS ON PLANS |
| | FOR COORDINATION OF CIRCUITS REQUIRED. |
| | LISTING THE NUMERICAL DESIGNATIONS AS SHOWN IS NOT |
| | ACCEPTABLE AND LISTING THE GENERAL LTS AND RECEPTS MAY |
| | NOT BE USED. PLEASE SEE THE FOLLOWING TEXT WHICH HAS |
| | BEEN EXTRACTED DIRECTLY FROM THE NEC IN 408.4. *SECTION |
| | 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE |
| | IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 15) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| | CIRCUITS ON PANEL SCHEDULE. PLEASE SEE THE PANEL |
| | SCHEDULE ONLY INDICATES ONE ARC FAULT CIRCUIT WHICH IS |
| | NOT POSSIBLE. |
| | 210.12, 408.4 |
| | |
| | 16) NOTE: PLEASE INDICATE THE TYPE OF RECESSED LIGHTS |
| | PER FBC 13-606.1.ABC.1.2.4 |
| | |
| | 17) NOTE: PLEASE SEE MISSING SOME TYPE OF LIGHT FIXTURE |
| | OR SWITCHED RECEPTACLE IN ROOMS. THE USE OF A FAN J-BOX |
| | IS NOT ACCEPTABLE. IF A FAN/ LT IS GOING TO BE CHOSEN, |
| | THESE MUST BE SHOWN ON PLANS AT THIS TIME AND THEY WILL |
| | BE REQUIRED TO BE INSTALLED BEFORE FINAL. |
| | THE SWITCHING OF A HALF SWITCHED RECEPTACLE IS ALSO |
| | PERMITTED. |
| | PLEASE SEE 210.70 , HOWEVER ALSO LS 101 7.8 . |
| | |
| | 18) NOTE: PLEASE SEE MISSING REQUIRE DEDICATED BATH(S) |
| | CIRCUIT(S) PER 210.11C3. MUST BE 20A AND #12. |
| | |
| | 19) NOTE: NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE |
| | INDICATE SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS |
| | THESE AS SMOKE DETECTORS. |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE ALL WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | AS SHOWN ON PLANS AND NOTED THESE SHOULD INDEED BY SA |
| | FOR SMOKE ALARMS. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 20) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND |
| | SEALED BY ANY DESIGNER OF RECORD OR DESIGN |
| | PROFESSIONAL. FS 481.229, 471.003 ETC |
| | PLEASE SEE THE TITLE BLOCK INDICATES HOMES DESIGNED BY |
| | ETC HOWEVER NO LICENSE INFORMATION WAS STATED ON TILE |
| | BLOCKS FOR SAID FIRM. FAC 61G1-16.004, 61G15-23.002, FS |
| | 481.219 AND 471.023. |
| | PLEASE SEE THE PLANS EVEN STATE * NOT VALID WITHOUT |
| | SEAL*. |
| | |
| | 21) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52. SEE |
| | REDLINED PLANS. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN OR |
| | SUBMITTED FOR REVIEW, THE REVIEW FOR CODE COMPLIANCE |
| | CAN ONLY BE BASED ON THE PLANS SUBMITTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |