Plan Review Details - Permit 07060821
Plan Review Stops For Permit 07060821
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-22 Cont ID  
Sent By btrobaug Date 2007-08-22 Time 17:58 Rev Time 0.00
Received By btrobaug Date 2007-08-22 Time 17:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By btrobaug Date 2007-07-03 Time 13:22 Rev Time 0.00
Received By btrobaug Date 2007-07-03 Time 12:49 Sent To P
Notes
2007-07-03 13:22:20 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2).
  
 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE THE
 ALARMS ON THE PLAN TO SHOW COMPLIANCE.
  
 5} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE
 FOR RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3
 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 13:56 Sent To E
Notes
2007-08-09 13:57:15TO BT'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-12 Cont ID  
Sent By mperson Date 2007-07-12 Time 10:33 Rev Time 0.00
Received By mperson Date 2007-06-26 Time 08:40 Sent To  
Notes
2007-06-26 08:41:19TO "E" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By mperson Date 2007-08-28 Time 15:36 Rev Time 0.00
Received By mperson Date 2007-08-28 Time 15:36 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By mperson Date 2007-07-12 Time 09:52 Rev Time 0.33
Received By mperson Date 2007-07-12 Time 09:52 Sent To PC
Notes
2007-07-12 10:11:22DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.1.3 DRAWINGS IN
 PENCIL ARE UNACCEPTABLE, PLEASE RESUBMIT ALL DRAWINGS
 IN INK.
  
 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC. PLEASE
 REFERENCE AN EXAMPLE OF AN ISOMETRIC DRAWING THAT
 REFLECTS THE PROPOSED PLUMBING WORK AND IS CODE
 COMPLIANT ATTACHED TO THE PLUMBING COMMENTS FOR THE
 RESUBMITTAL.
  
 4. THE FOLLOWING IS REQUIRED FOR THE PROPOSE WASHING
 MACHINE PER FBC-2004 PLUMBING.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE WASHING MACHINE
 STANDPIPES ON THE RESUBMITTAL.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3").
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  