| 2007-07-11 17:01:16 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE INDICATEDLONGEST LENGTH OF THE EXISTING GAS |
| | SYSTEM IS BEING INDICATED AS FIFTY FEET (50'). THE |
| | PROPOSED PIPING DISTANCE TO THE GRILL IS BEING |
| | INDICATED AS ANOTHER FIVE FEET (5'). THATS A LONGEST |
| | LENGTH TOTAL OF FIFTY FIVE FEET (55'). THE EXISTING |
| | PIPING TO THE GRILL IS BEING INDICATED AS 1/2" |
| | GALVANIZED. PER FBC-2004 FUEL GAS TABLE 402.4(2) THE |
| | 1/2" GALVANIZED PIPING IS ONLY GOOD FOR 66,000 BTU'S. |
| | THE PROPOSED GRILL IS 90,000 BTU'S. THIS WILL NOT WORK |
| | AS 0.5 PSI DELIVERY PRESSURE. THE OPTIONS ARE (A) |
| | INCREASE THE EXISTING 1/2" GALVANIZED PIPE SIZE TO |
| | 3/4". (B) RESUBMIT WITH A 2 PSI DELIVERY PRESSURE. |
| | PLEASE INCLUDE MANUFACTURER SPECIFICATIONS FOR THE |
| | PROPOSED MP REGULATORS WITH THE MAKE, MODEL NUMBER, |
| | LOAD CAPACITY AND A LISTING FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY [NRTL]. PLEASE CLEARLY |
| | INDICATE THE LOCATION OF THE MP REGULATORS ON THE |
| | RESUBMITTED DRAWING. (C) CHANGE THE GRILL TO ACCOMODATE |
| | THE BTU LOAD OF THE EXISTING 1/2" GALVANIZED GAS |
| | PIPING. |
| | NOTE: PLEASE CLEARLY INDICATE THE LONGEST LENGTH OF THE |
| | EXISTING SYSTEM FROM THE METER TO THE FARTHEST |
| | APPLIANCE ON THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |