| 2007-06-26 12:06:40 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW THE PLANS ARE INCOMPLETE AT THIS TIME |
| | AND THERE ARE SEVERAL CODE RELATED ISSUES WHICH WILL BE |
| | REQUIRED SUBSTANTIAL CHANGES TO PLANS. |
| | ** PLEASE KNOW THERE ARE ITEMS WHICH CAN NOT YET BE |
| | REVIEWED FOR COMPLIANCE. |
| | |
| | 1) NOTE: PLEASE SEE PLANS ARE MISSING THE FOLLOWING |
| | REQUIRED CODES TO BE STATED ON PLANS AND FOR DESIGN. |
| | PLEASE SEE THE FOLLOWING WHICH WAS ADOPTED AS OF |
| | DECEMBER 8TH, 2006. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE KNOW THE PLANS WILL BE ROUTED TO THE |
| | ADDRESSING REVIEWER AS THE PALM BEACH COUNTY PROPERTY |
| | APPRAISER OFFICE DOES NOT INDICATE AND ADDRESS, OUT |
| | SYSTEM SHOWS 715 59TH AND THE PLANS INDICATE 714 59TH. |
| | |
| | PLEASE KNOW ONCE THE ADDRESS HAS BEEN DECIDED AND |
| | CORRECTED, PLEASE REVISED TITLE BLOCKS OF PLANS |
| | ACCORDINGLY. |
| | FAC61G1-16.004 |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS ARE INCOMPLETE AS NO |
| | ELECTRICAL RISER DIAGRAM WAS SUBMITTED. |
| | A) PLEASE SEE NO SERVICE ENTRANCE |
| | CONDUCTORS.215.5,240.4,310.16 ETC |
| | B) PLEASE SEE NO GROUNDING ELECTRODE SYSTEM WAS |
| | SUBMITTED. 250.50 |
| | C) PLEASE SEE NO MAIN DISCONNECT WAS SHOWN FOR SERVICE. |
| | 230.70, 230.71 ETC |
| | D) PLEASE INDICATE THE AIC RATINGS ON NEW RISER AS THE |
| | NOTED RATING ABOVE PANEL SCHEDULE MAY CHANGE ONCE THE |
| | RISER IS REVISED. 110.9 |
| | E) PLEASE SEE LOCATIONS OF ALL SERVICE EQUIPMENT WERE |
| | SHOWN ON PLANS. 110.26, 240.24 ETC |
| | |
| | 4) NOTE: PLEASE SEE THE RECEPTACLES ON KITCHEN COUNTER |
| | SPACE NEED TO MEET 210.52C1-5 AND 210.8A6. |
| | |
| | 5) NOTE: PLEASE SEE MISSING GFI RECEPTACLE PER 210.52E, |
| | 210.8A |
| | |
| | 6) NOTE: PLEASE SEE MISSING THE RECEPTACLE FOR THE |
| | DISHWASHER AS THE PLANS ONLY APPEAR TO SHOW A COUNTER |
| | SPACE RECEPTACLE AND THE PANEL SCHEDULE DOES SHOW AS |
| | DISHWASHER CIRCUIT. |
| | |
| | 7) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS |
| | THE LOADS FOR ALL SMALL APPLIANCE AND DINING ROOM |
| | CIRCUITS SHALL BE FIGURED INTO THE LOAD CALCULATIONS. |
| | PLEASE SEE THE FOLLOWING COMMENT. |
| | |
| | 8) NOTE: PLEASE SEE THERE ARE NUMEROUS DEDICATED |
| | CIRCUITS ON PANEL SCHEDULE WHICH ARE NOT IN LOAD |
| | CALCULATIONS. PLEASE SEE THERE ARE OTHER ITEMS WHICH DO |
| | NOT MATCH. |
| | A) PLEASE SEE THE PANEL SCHEDULE SHOWS ONE WATER |
| | HEATER, YET THE LOAD CALCULATIONS INDICATES 2@450WATTS, |
| | YET THE TOTAL LOAD IS 9KW? |
| | B) PLEASE SEE THE PANEL SCHEDULE SHOW 2-AHU SYSTEMS AND |
| | ONLY ONE CU. IN EITHER CASE PLEASE SEE THE PANEL |
| | SCHEDULE SHOWS TWO 10KW UNITS AND LOAD CALCULATIONS |
| | ONLY INDICATE ONE 7.5KW AND 1-10KW? |
| | PLEASE SEE COMMENT WITH RESPECT TO PLANS. |
| | C) PLEASE SEE FRIG, APPLIANCES, DISHWASHER ETC. PLEASE |
| | SEE ALL OF NEC 220 AS THERE ARE TOO MANY MISSING AND |
| | COORDINATION NEEDS TO BE ADDRESSED. |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 9) NOTE: PLEASE SEE 210.11C2, 220.53 AS THE LOADS FOR |
| | WASHER AND LAUNDRY SHALL BE BASED ON THE MINIMUM PER |
| | CODE AT 1500VA. |
| | |
| | 10) NOTE: PLEASE SEE THE CLOSET LIGHT NEEDS TO MEET |
| | 410.8 |
| | |
| | 11) NOTE: PLEASE SEE A PLAN INDICATES THE ELECTRICAL |
| | PANEL LOCATED WHERE IS DOES NOT MEET 110.26, 240.24, |
| | 408.7. |
| | THIS LOCATION ON PLANS IS NOT PERMITTED. |
| | |
| | 12) NOTE: PLEASE SEE THE REFRIGERATOR RECEPTACLE IS |
| | BEING SHOWN AS A 220V RECEPTACLE?? |
| | FBC 106.1.2, 210.4? |
| | |
| | 13) NOTE: PLEASE SEE THE PLANS NEEDS TO SHOW ALL |
| | LOCATION AND IDENTIFY THE LOCATIONS OF THE AHU AND |
| | WATER HEATER. |
| | PLEASE SEE MISSING DISCONNECTS PER 440.11 AND 422.31 |
| | |
| | 14) NOTE: PLEASE SEE 422.13 UNDER THE 2005 NEC AS THE |
| | WATER HEATER NEEDS TO BE SHOWN AT 125%. |
| | |
| | 15) NOTE: PLEASE SEE THE PLAN INDICATES BOTH A 220V |
| | RECEPTACLE AND A DISCONNECT FOR THE CU?? |
| | THE HARDWIRED DISCONNECT IS REQUIRED. |
| | |
| | 16) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL BE |
| | SPECIFIC FOR ALL CIRCUIT NUMBERS AND DESIGNATIONS ON |
| | EACH CIRCUIT SHALL BE SPECIFIC TO ALL ROOMS AND AREAS |
| | IN WHICH THEY FEED. |
| | LISTING THE NUMERICAL DESIGNATIONS AS SHOWN IS NOT |
| | ACCEPTABLE AND LISTING THE GENERAL LTS AND RECEPTS MAY |
| | NOT BE USED. PLEASE SEE THE FOLLOWING TEXT WHICH HAS |
| | BEEN EXTRACTED DIRECTLY FROM THE NEC IN 408.4. *SECTION |
| | 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE |
| | IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 17) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| | CIRCUITS ON PANEL SCHEDULE. THE GENERAL NOTE IS NOT |
| | ACCEPTABLE. SEE NOTE ABOVE.#16. IDENTIFY EACH. |
| | |
| | 18) NOTE: PLEASE INDICATE THE TYPE OF RECESSED LIGHTS |
| | PER FBC 13-606.1.ABC.1.2.4 |
| | |
| | 19) NOTE: PLEASE SEE THE KITCHEN LIGHTING NEED SOT BE |
| | ON A 3-WAY SWITCH PER 210.70 AND LS 101 7.8 FOR EGRESS |
| | INTO THE KITCHEN AREA. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |