Plan Review Details - Permit 07060774
Plan Review Stops For Permit 07060774
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-29 Cont ID  
Sent By rmcdouga Date 2007-10-29 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2007-10-29 Time 07:05 Sent To  
Notes
2007-10-29 09:55:32BUILDING PROVISO
  
 1) SUBMIT SIGNED AND SEALED ENGINEERING FOR THE HELICAL
 PILES.
  
 2) EXISTING WINDOWS AND DOORS NOT TO BE RELOCATED IN
 EXTERIOR WALLS WITHOUT CURRENT PRODUCT APPROVALS FOR
 THEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-02 Cont ID  
Sent By rmcdouga Date 2007-10-02 Time 14:02 Rev Time 0.00
Received By rmcdouga Date 2007-10-02 Time 14:02 Sent To  
Notes
2007-10-02 14:44:502004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT REVISED ENERGY CALCULATIONS. PER THE GENERAL
 DEFINITIONS AT THE END OF THE ENERGY FORM, ALL R-VALUES
 AND EFFICIENCIES INSTALLED MUST MEET OR EXCEED THE
 MINIMUM VALUES LISTED ON THE FORM. COMPONENTS AND
 EQUIPMENT NOT BEING INSTALLED OR RENOVATED MAY BE LEFT
 BLANK. THE R-VALUE OF 4.2 SPECIFIED ON SHEETS 3 AND 4
 OF THE PLANS DOES NOT MEET THE MINIMUM OF R-5 REQUIRED
 BY THE ENERGY FORM. IF THE CENTRAL A/C IS NOT BEING
 ADDED OR RENOVATED AS INDICATED IN THE LETTER THAT WAS
 SUBMITTED LEAVE THOSE LINES BLANK. THE OWNER/AGENT IS
 REQUIRED TO SIGN THE FORM. SEE FBC CHAPTER 13.
  
 2) THE NOTES ON SHEET 1 SPECIFY A NEW 4" SLAB POURED
 OVER THE EXISTING SLAB. ON SHEET 2 A NEW 6" SLAB IS
 SPECIFIED OVER THE EXISTING SLAB. ON SHEET 1 THE
 EXISTING SLAB IS SHOWN AT 4" BELOW THE FINISH FLOOR
 ELEVATION OF THE LIVING AREA. IT APPEARS THAT THE
 EXISTING SLAB WILL NEED TO BE REMOVED IN ORDER TO
 INSTALL THE 6" STRUCTURAL SLAB REQUIRED DUE TO THE POOR
 SOIL CONDITIONS. PLEASE REVIEW AND MAKE
 CORRECTIONS.CITY AMENDMENTS TO FBC 106.1.2.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE MULLIONS FOR THE
 TWO WINDOWS THAT ARE MULLED TOGETHER. FAC RULE 9B-72.
  
  
 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 EXTERIOR DOOR IS EXPIRED AND IS FOR A NON-IMPACT GLAZED
 OUTSWING DOOR. THE PLANS INDICATE A SIX PANEL METAL
 DOOR WITH NO GLASS AND THE STORM PANEL SCHEDULE DOES
 NOT LIST THIS DOOR. CHANGE THE PRODUCT APPROVAL OR THE
 PLANS FOR THIS DOOR. IF THIS IS A GLAZED DOOR, SPECIFY
 THE STORM PANELS OR OTHER IMPACT PROTECTION REQUIRED BY
 R301.2.1.2.
  
 5) ON THE PRODUCT APPROVAL FOR THE ROOF COVERING
 SPECIFY THE APPROVED ASSEMBLY AND FASTENING ASSEMBLY
 THAT WILL BE INSTALLED. PROVIDE RAS 117 CALCULATIONS
 FOR ENHANCED FASTENING IF PRESSURES ARE TOO LOW. CITY
 AMENDMENTS TO FBC 106.1.2.
  
 6) THE STORM PANEL SCHEDULE THAT WAS SUBMITTED DOES NOT
 CORRESPOND WITH THE PRODUCT APPROVAL THAT WAS
 SUBMITTED. THE 40" SPAN FOR OPENING #2 IS LESS THAN THE
 OPENING SIZE. THE ANCHOR IN THE TABLE SHOULD BE
 PANELMATE PLUS NOT TAPCON. CITY AMENDMENTS TO FBC
 106.1.2.
  
 NOTE: IN ORDER TO REUSE EXISTING DOORS AND WINDOWS,
 THEY MUST HAVE CURRENT PRODUCT APPROVALS. IF THE
 PRODUCT APPROVALS THAT ARE SUBMITTED AND REVIEWED DO
 NOT MATCH THE PRODUCTS THAT ARE BEING REINSTALLED THEY
 CAN NOT BE USED. THEY WILL BE VERIFIED BY THE INSPECTOR
 IN THE FIELD AND WILL HAVE TO BE REPLACED IF THEY DON'T
 HAVE CORRESPONDING PRODUCT APPROVALS. FAC RULE 9B-72
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By rmcdouga Date 2007-07-12 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2007-07-12 Time 17:52 Sent To  
Notes
2007-07-12 19:00:50DENIED BY BUILDING
  
 1)) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 2) SPECIFY THE REQUIRED SOIL BEARING CAPACITY FOR THE
 DESIGN. FBC* 106.1.2
  
 3) WINDOWS W1,W2 AND W3 IN THE SCHEDULE ON 3.0 ARE NOT
 EGRESS WINDOWS AS SPECIFIED. THEY DO NOT HAVE THE
 REQUIRED MINIMUM CLEAR OPENING HEIGHT OF 24". FBC
 R310.1
  
 4) SUBMIT ENERGY CALCULATIONS FOR THE ADDITION AS
 REQUIRED BY FBC CHAPTER 13.
  
 5) REVISE ROOF SHEATHING NAILING NOTES ON 4.0 AND 6.0.
 THE ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH
 SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER IN
 THE FIELD FOR ROOF ZONES 1 AND 2. SPACING OF RING-SHANK
 FASTENERS SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3
 FOR 130 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE
 WITH FIGURE R803.2.3.1.
  
 6) THE TITLE BLOCK OF THE DRAWINGS SPECIFY 1/4" SCALE
 FOR THE DRAWINGS. SEVERAL OF THE DRAWINGS ARE NOT THIS
 SCALE AND SOME SHEETS HAVE TWO OR MORE DIFFERENT SCALE
 DRAWINGS ON THEM. PLEASE CORRECT.
  
 7) SECTION B ON 4.0 SHOWS AN UNSUPPORTED OVERHANG OF
 5". PLEASE REVISE SO THAT ROOF FRAMING WILL SUPPORT THE
 OVERHANG.
  
 8) THERE IS A VOID SHOWN BETWEEN THE TOP OF THE CONC.
 TIE BEAM AND THE BOTTOM OF THE RAFTERS ON SECTION B ON
 4.0. PLEASE CLARIFY.
  
 9) THE INTERNAL WALL DETAIL ON 6.0 SPECIFIES A 4"
 CONCRETE SLAB AND SECTION A ON 4.0 HAS A 6" SLAB.
 PLEASE CORRECT.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE WINDOWS,
 STRUCTURAL MULLIONS AND ROOFING MATERIAL. THE EXISTING
 WINDOWS AND DOORS CAN ONLY BE RE-INSTALLED IF THEY HAVE
 PRODUCT APPROVALS.
  
 11) THE PRODUCT APPROVAL NOA SUBMITTED FOR THE POMA
 STORM PANELS IS EXPIRED. SUBMIT FL COVERSHEET AND
 CURRENT NOA.
  
 12) SOME OF THE INFORMATION ON THE STORM PANEL SCHEDULE
 IS INCORRECT. THE FL# AND NOA# DO NOT CORRESPOND TO THE
 PRODUCT APPROVAL THAT WAS SUBMITTED. THE SHUTTER
 MOUNTING REFERS TO THE TYPE OF MOUNT OR CONNECTION
 TYPE, FOR EXAMPLE DIRECT MOUNT, ETC. THE ANCHOR TYPE
 MUST BE ONE OF THE ONES LISTED IN THE PRODUCT
 APPROVAL.
  
 13) THE NOA SUBMITTED FOR THE JELD-WEN DOOR HAS PARTS
 THAT ARE ILLEGIBLE. SUBMIT CLEAN AND CLEAR COPIES.
  
 14) THE DOOR NOA IS FOR A GLAZED DOOR WITH NO IMPACT
 RATING AND WILL REQUIRE STORM PANELS FOR IMPACT
 PROTECTION. THE DOOR WAS NOT SHOWN ON THE STORM PANEL
 SCHEDULE. THE DOOR IS NOT SPECIFIED AS HAVING GLAZING
 ON THE PLANS. PLEASE CLARIFY.
  
 15) THE VALUE OF THE PROJECT HAS BEEN ADJUSTED TO $
 37,426.00 BASED ON ICC COST DATA. ADDITIONAL PERMIT
 FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-17 Cont ID  
Sent By btrobaug Date 2007-09-17 Time 17:14 Rev Time 0.00
Received By btrobaug Date 2007-09-17 Time 17:03 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-06-27 Cont ID  
Sent By btrobaug Date 2007-06-27 Time 07:40 Rev Time 0.00
Received By btrobaug Date 2007-06-27 Time 06:51 Sent To M
Notes
2007-06-27 07:39:42 
  
  
  
  
 .PROVISO
  
 R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED IN
 NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 09:03 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 09:03 Sent To B
Notes
2007-10-25 09:03:59TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 08:16 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 08:16 Sent To Z
Notes
2007-09-13 08:17:08TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-12 Cont ID  
Sent By rmcdouga Date 2007-07-12 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2007-06-25 Time 16:27 Sent To  
Notes
2007-06-25 16:28:03TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-09-18 Cont ID  
Sent By tgordon Date 2007-09-18 Time 08:15 Rev Time 0.20
Received By tgordon Date 2007-09-18 Time 08:15 Sent To B
Notes
2007-09-18 08:19:0212,000 BTU. A/C WALL UNIT BEING INSTALLED NO MECHANICAL
 PERMIT REQUIRED (NO DUCT WORK OR CENTRAL A/C).

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-06-27 Time 10:50 Rev Time 0.25
Received By tgordon Date 2007-06-27 Time 10:50 Sent To P
Notes
2007-06-27 10:58:14*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2. HAVE ENERGY CALCULATIONS SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLANS PAGE 5.0 ELECTRICAL PLAN SHOWS THREE A/C
 VENTS, PLEASE SHOW GRILL SIZE, CFM'S, AND DUCT SIZE.
 ALSO STATE THAT DUCTS ARE GOING TO AN EXISTING A/C
 SYSTEM.
  
 3) PLEASE PROVIDE RETURN AIR FOR FAMILY ROOM, SEE 2004
 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-07-10 Cont ID  
Sent By jleech Date 2007-07-10 Time 08:43 Rev Time 0.00
Received By jleech Date 2007-07-10 Time 08:41 Sent To B
Notes
2007-07-10 08:44:13NO PLUMBING SHOWN ON THIS PLAN.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-17 Cont ID  
Sent By choops Date 2007-09-17 Time 16:22 Rev Time 0.00
Received By choops Date 2007-09-17 Time 16:22 Sent To E
Notes
2007-09-17 16:23:02***APPROVED - RESUB #1 - ADDITION AT REAR OF HOUSE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By choops Date 2007-06-26 Time 12:58 Rev Time 0.00
Received By choops Date 2007-06-26 Time 12:58 Sent To E
Notes
2007-06-26 13:00:03***FAILED***
  
  
 1)PROVIDE 2 COPIES OF A CURRENT SURVEY SHOWING THE
 SCOPE OF WORK WITH DIMENSIONS AND SETBACK DIMENSIONS TO
 PROPERTY LINES.
  
  
 CHRIS HOOPS