Plan Review Details - Permit 07060731
Plan Review Stops For Permit 07060731
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-29 Cont ID  
Sent By jwitmer Date 2008-01-29 Time 11:13 Rev Time 2.22
Received By jwitmer Date 2008-01-29 Time 11:12 Sent To  
Notes
2008-01-29 14:07:28BUILDING PLAN REVIEW
 PERMIT: 07060731
 ADD: 226 E ALHAMBRA PLACE
 CONT: O/BOWNER- REGIONAL PROPERTIES
 TEL: (561)891-0705ALAN LIPTON
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.IFYOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE. NOTE ONLY ONE SET OF SIGNED
 AND SEALED SET OF PLANS WERE SUBMITTED.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS PLEASE REVISE THE
 BUILDING CODE STATEMENT TO REFLECT THE 2007
 SUPPLEMENTS.
  
 1F) PLANS ALSO NEED TO REFLECT 2004 EXISTING BUILDING
 CODE W/ 2007 SUPPLEMENTS UNDER CHAPTER 8 CHANGE OF
 OCCUPANCY THIS SHALL ALSO BE NOTED ON PLANS.
  
 1G)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2)THE PERMIT APPLICATION INDICATES WORK TO BE
 COMPLETED UNDER THIS PERMIT BY A OWNER/ BUILDER. OWNER
 / BUILDERS CAN ONLY WORK ON A R-3 RESIDENCE, SINGLE
 FAMILY
 RESIDENCE. THE SECOND ISSUE WITH THE OWNER/ BUILDER
 PERMIT IS A COMPANY OWNS THE RESIDENCE NOT AN
 INDIVIDUAL PLEASE SEE FL S S 489.103 EXEMPTIONS(7).
 A CGC, CBC OR RESIDENTIAL CONTRACTOR MAY APPLY FOR
 PERMIT, A NOTIRIZED LETTER FROM THE OWNER TRANSFERRING
 THE PERMIT, FEES AND PLANS TO THE NEW CONTRACTOR WILL
 BE REQUIED. THERE IS A $100.00 FEE FOR THE TRANSFER OF
 OWNERSHIP OF THE PERMIT. THE NEW CONTRACTOR WILL NEED
 TO FILL OUT A NEW PERMIT APPLICATION, IF THE QUALIFIER
 FOR THE SUB-CONTRACTORS SIGNS ON MEP THESE WILL BE NO
 FEE PERMITS.
  
 3)EXISTING BUILDING CODE, :
 A) TABLE 812.4.1 HAZARD CATEGORIES GOES TO A HIGHER
 HAZARD WHICH ENVOKES CHAPTER 10 FBC.
 B) 806.1ACCESSIBILITY IN ALL PORTIONS OFBUILDINGS
 UNDERGOING A CHANGE IN OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FBC, BUILDING
 ACCESSIBLE BATHROOMS 11-4.16, 11-4.19, 11-4.20,
 11-4.21,& 11-4.23.
 ACCESSIBLE KITHCEN-SINK 11-4.24
 ACCESSIBLE KITHEN - MICROWAVE SIDE APPROACH REACH
 RANGES11-4.27.3.
 11-9.5(1) ALL PUBLIC AND COMMON USE AREAS SHALL
 COMPLY WITH SECTION 11-4 NEW CONSTRUCTION. AT LEAST ONE
 OF EACH TYPE AMENITY( SUCH AS WASHER, DRYERS AND
 SIMILAR EQUIPMENT INSTALLED FOR THE USE OF OCCUPANTS)
 IN EACH COMMON AREA SHALL BE ACCESSIBLE AND SHALL
 LOCATE ON AN ACCESSIBLE ROUTE TO ANY ACCESSIBLE UNIT OR
 SLEEPING ACCOMMODATION.
  
 4) SHEET 1 DEMO NOTE 4 INDICATES THE REMOVAL OF DOORS,
 SEE EXISTING BUILDING CODE SECTION 812.3.2 -R-4THE
 FOLLOWING REQUIREMENTS ARE TO BE MET.
 A) CORRIDOR DOORS SHALL COMPLY WITH 605.5.1 AND
 605.5.2 EXISTING BUILDING CODE
 B) FIRE ALARMS AND DETECTION SYSTEMS SHALL COMPLY
 WITH 604.4.
  
 5)THE PRODUCT APPROVALS SUBMITTED ARE NOT TESTED FOR
 LARGE MISSLE IMPACT RESISTANCE. 1609.1.4 PROTECTION OF
 OPENINGS IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING
 THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET
 (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS
 AND THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE
 BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 ANDASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND
 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS
 LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST. 2.GLAZED
 OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE
 SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST.
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING FBC
 1609.1.4.
 STORM SHUTTES WILL BE REQUIRED, INDICATE AREA WHERE THE
 STORM SHUTTERS WILL BE STORED AND SECURED WHEN NOT IN
 USE.FL BLD CODE 2001 SECTION 103.6, 1609.1.4, 1714.5
 & 3401.7.2.4. PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE
 ZONES, SLAT TYPES, ETC., SHALL BESUBMITTED AT TIME OF
 PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) CASEMENTPGT WINDOWS***
 B) SINGLE HUNG PGT WINDOWS ***
 C) NEW FRONT DOOR- NO REPORT SUBMITTED
 D) STORM SHUTTERS- NO REPORT
  
 **** NOTE THE NOA'S SUBMITTED DO NOT HAVE THE REQUIRED
 FLORIDA COVERSHEET, NOTE THESE OLDER NOA'S WERE BEFORE
 THE 2004 FBC AND MAY HAVE TOOK THE 1 1/3RD INCREASES IN
 THE FASTENERS(STEEL).SEE CALCULATIONS WERE BEFORE THE
 2004 FBC ENACTMENT DATE OF 10-01-05. 1605.3.1.1.
  
 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 8)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-02 Cont ID  
Sent By jjohnsto Date 2007-11-02 Time 12:02 Rev Time 12.00
Received By jjohnsto Date 2007-11-02 Time 11:53 Sent To  
Notes
2007-11-02 11:56:17CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR,
 WEST PALM BEACH, FLORIDA33401
 TEL:561-805-6713FAX:561-805-6731
  
 JAMES JOHNSTON,
 BUILDING PLAN EXAMINER II
 E-MAIL:JJOHNSTON @WPB.ORG
  
  
 PERMIT NO07060731
 PROJECT GROUP HOME
 ADDRESS226ALHAMBRA PLACE
 DATE NOVEMBER 1, 2007
  
  
 BUILDINGPLANREVIEW
  
 FLORIDA BUILDING CODES 2004 W REVISIONS
  
  
 FLORIDA STATUE713.13NOTICE OF COMMENCEMENT FILE
 NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. IF
 THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
 COMMENT-FOR YOUR INFORMATION
  
  
 1
 CORRECTION SUBMITTAL
 WHEN RE-SUBMITTINGCORRECTED PLANS FOR PERMITTING,
 PLEASEREMOVE AND REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE REVISION
 MADE.
  
 IDENTIFY THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES
 CAN BE FOUND AND INCLUDE THE OLD SHEETS IN THE
 RE-SUBMITTAL
 PACKAGE FOR THE PLAN REVIEWER?S REFERENCE.
  
 COMMENT-FOR YOUR INFORMATION
  
  
 2
 FLORIDA STATUE471.025ENGINEER SEAL
 ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR
  
 DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING
 FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED
 TO THE OWNER OR THE OWNER'S REPRESENTATIVE SHALL BE
 SIGNED
 BY THE LICENSEE, DATED, AND SEALED WITH SAID SEAL. SUCH
 SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE OF THE
 AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED.
  
 COMMENT-THE ENGINEER SHALL SEAL EACH SHEET OF THE
 DRAWINGS
 IN THE TITLE BLOCK AS REQUIRED BY THIS STATUE.
  
  
 3
 FLORIDA STATUE481.219CERTIFICATION OF PARTNERSHIPS,
 LIMITED LIABILITY COMPANIES, AND CORPORATIONS.
  
 ARCHITECTURAL SERVICES
 FOR THE PURPOSES OF THIS SECTION, A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A CORPORATION,
 LIMITED LIABILITY COMPANY, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME, OFFERING
 ARCHITECTURAL
 SERVICES TO THE PUBLIC JOINTLY OR SEPARATELY.
  
 INTERIOR DESIGN SERVICES
 FOR THE PURPOSES OF THIS SECTION, A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A CORPORATION,
 LIMITED LIABILITY COMPANY, PARTNERSHIP, OR PERSON
 OPERATING
 UNDER A FICTITIOUS NAME, OFFERING INTERIOR DESIGN
 SERVICES
 TO THE PUBLIC JOINTLY OR SEPARATELY.
  
 COMMENT-
 THE FIRM MCARCHITECTURE SHALL
 PROVIDE THEIR STATE OF FLORIDA CERTIFICATE OF
 AUTHORIZATION NUMBER IN THE TITLE BLOCK .
  
  
  
 4
 481.221SEALS; DISPLAY OF CERTIFICATE NUMBER
 ALL FINAL CONSTRUCTION DOCUMENTS AND INSTRUMENTS OF
 SERVICE WHICH INCLUDE DRAWINGS, PLANS, SPECIFICATIONS,
  
 OR REPORTS PREPARED OR ISSUED BY THE REGISTERED
 ARCHITECT
 AND BEING FILED FOR PUBLIC RECORD SHALL BEAR THE
 SIGNATURE
 AND SEAL OF THE REGISTERED ARCHITECT WHO PREPARED OR
 APPROVED THE DOCUMENT AND THE DATE ON WHICH THEY WERE
 SEALED.
 THE SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE
 OF AUTHENTICITY.
  
 COMMENT-
 THE INDIVIDUAL MAYORICHAVERRA MUST PROVIDE
 THEIR SEAL DATE AND SIGNATURE IN COMPLIANCE WITH THIS
 FLORIDA STATUE
  
  
 5
 481.221SEALS; DISPLAY OF CERTIFICATE NUMBER
 THE REGISTERED INTERIOR DESIGNER AND BEING FILED FOR
 PUBLIC
 RECORD SHALL BEAR THE SIGNATURE AND SEAL OF THE
 REGISTERED
 INTERIOR DESIGNER WHO PREPARED OR APPROVED THE
 DOCUMENT
  
 AND THE DATE ON WHICH THEY WERE SEALED. THE SIGNATURE,
  
 DATE, AND SEAL SHALL BE EVIDENCE OF AUTHENTICITY.
  
 COMMENT-
 THE INDIVIDUAL MAYORICHAVERRA MUST PROVIDE
 THEIR SEAL DATE AND SIGNATURE IN COMPLIANCE WITH THIS
 FLORIDA STATUE
  
 COMMENT-
 PLEASE NOTE THAT THE INDIVIDUAL MAYORI CHAVERRA
 ORMCARCHITECTURE IS NOT ON FILE WITH THE STATE OF
 FLORIDA
 DBPRFOR ARCHITECTURE OR INTERIOR DESIGN.
 IF THIS INDIVIDUAL IS NOT LICENSED BY THE STATE OF
 FLORIDA
 ALL REFERENCE TO THEIR NAME MUST BE REMOVED ON THE
 PLAN
  
  
  
 6
 FENCE REPAIR
  
 COMMENT
 FENCE WORK WILL REQUIRE A SEPARATE PERMIT
  
  
 7
 FBCTABLE 601BUILDING FIRE RESISTANT RATING THIS
 BUILDING HAS BEEN RATED III B BY THE DESIGN
 PROFESSIONAL AND THEREFORE SHALLREQUIRE A MORE
 STRINGENT CODE THAN THEV B RATINGWHICH IS
 APPLICABLE
 FOR THIS PROJECT
  
 COMMENT
 1EXTERIOR BEARING WALLS SHALL BE RATED FOR 2 HOURS
  
 2FIRE RETARDANT TREATED WOOD FRAMING SHALL BE
 ALLOWED
 IN EXTERIOR FRAMINGSECT2303.2
  
 3PLEASE COORDINATE THE BUILDING INFORMATION ON A-2
 REFERENCING OCCUPANCY ETC. WITH THE BUILDING
 INFORMATION ON A-1.
  
  
 8
 704.5 FIRE-RESISTANCE RATINGS.
 EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN
 ACCORDANCE
 WITH TABLES 601 AND 602 .
 THE FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A
 FIRE
 SEPARATION DISTANCE OF GREATER THAN 5 FEETSHALL BE
 RATED
 FOR EXPOSURE TO FIRE FROM THE INSIDE.
  
 COMMENT
 PLEASE NOTE EXTERIOR WALL RATING ON PLAN
  
  
  
  
 9
  
 1715.4 FIRE-PROTECTION RATED GLAZING.
 ALL WINDOWS IN EXTERIOR WALLS SHALL HAVE A 1-1/2 HR
 RATING
 THE WINDOWS SHALL BE MANUFACTURED IN ACCORDANCE WITH
 NFPA- 257.
 DOORS SHALL HAVE A RATING OF 1-1/2 HR WITHOUT GLASS
  
 2715.4.5 INSTALLATION.
 FIRE-PROTECTION-RATED GLAZING SHALL BE IN THE FIXED
 POSITION
 OR BE AUTOMATIC-CLOSING AND SHALL BE INSTALLED IN
 APPROVED
 FRAMES.
  
 3 715.4.8 EXTERIOR FIRE WINDOW ASSEMBLIES. EXTERIOR
 OPENINGS, OTHER THAN DOORS, REQUIRED TO BE PROTECTED BY
 SECTION 704.12 , WHERE LOCATED IN A WALL REQUIRED BY
 TABLE 602 TO HAVE A FIRE-RESISTANCE RATING
  
 OF GREATER THAN 1 HOUR, SHALL BE PROTECTED WITH AN
 ASSEMBLY HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 1? HOURS
  
 COMMENT
 PLEASE PROVIDE THE PRODUCT APPROVALS
 WITH THE 1-1/2 HR RATING FOR THE BUILDING COMPONENTS
 LISTED BELOW
  
  
  
 10
 717.2 FIREBLOCKING.
 IN COMBUSTIBLE CONSTRUCTION, FIREBLOCKING SHALL BE
 INSTALLED TO CUT OFF CONCEALED DRAFT OPENINGS (BOTH
 VERTICAL AND HORIZONTAL) AND SHALL FORM AN EFFECTIVE
 BARRIER BETWEEN FLOORS, BETWEEN A TOP STORY AND A ROOF
  
 OR ATTIC SPACE
  
 COMMENT
 PLEASE NOTE ON PLAN FRAMING
  
  
  
 11
 719.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 COMMENT
 PLEASE PROVIDE THE INSULATION APPLICATION FOR
 TYPE III-B CONSTRUCTION
  
  
  
 12
 SECTION 720
 PRESCRIPTIVE FIRE RESISTANCE
 TABLE720.1(1)
 MINIMUM PROTECTION OF STRUCTURAL PARTS BASED
 ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING
 MATERIALS
  
 COMMENT
 PLEASE PROVIDE THE CORRECT INSULATING
 MATERIALS FOR THE TWO HOUR WALLS
  
  
  
 13
 803.4 APPLICATION.
 WHERE THESE MATERIALS ARE APPLIED ON WALLS, CEILINGS OR
 STRUCTURAL ELEMENTS REQUIRED TO HAVE A FIRE-RESISTANCE
 RATING OR TO BE OF NONCOMBUSTIBLE CONSTRUCTION, THEY
 SHALL COMPLY WITH THE PROVISIONS OF THIS SECTION.
  
  
 COMMENT
 PLEASE SEE SECTION 803 FOR APPLICATION OF THE INTERIOR
 ELEMENTS
  
  
  
 14
 PRODUCT APPROVALS REQUIRED
 FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3
 REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS
 SUBMIT TWO COPIES OF EACH APPROVAL WITH THE FLORIDA
 PRODUCT APPROVAL COVER SHEET THE ARCHITECT?S /
 ENGINEER?S SIGNATURE AS APPLICABLE, STATING ?TO THE
 BEST
 OF THEIR KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH
 THE PLANS AND SPECIFICATIONS.
  
 COMMENT
 PLEASE SUBMIT THE 1-1/2 HR FIRE RATED WINDOW
 AND DOOR PRODUCT APPROVAL.
  
  
  
 15
 11-4.22.3 CLEAR FLOOR SPACE.
 AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH SECTION
 11-4.2.3 SHALL BE PROVIDED WITHIN AN ACCESSIBLE TOILET
 ROOM.
 THE CLEAR FLOOR SPACE AT FIXTURES AND CONTROLS, THE
 ACCESSIBLE ROUTE, AND THE TURNING SPACE MAY OVERLAP.
  
 COMMENT
 THE BATHROOM DOOR CANNOT SWING INTO THE TURNING SPACE.
  
  
  
 16
 11-4.19 LAVATORIES AND MIRRORS.
 11-4.19.2 HEIGHT AND CLEARANCES.
 LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER
 SURFACE NO HIGHER THAN 34 INCHES ABOVE THE FINISH
 FLOOR.
  
 COMMENT
 KNEE CLEARANCE THAT IS AT LEAST 27 INCHES HIGH,
 30 INCHES WIDE, AND 19 INCHES DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS.
 PROVIDE A CLEARANCE OF AT LEAST 29 INCHES ABOVE THE
 FINISH FLOOR TO THE BOTTOM OF THE APRON.
 KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE 31 .
  
  
  
 17
 11-4.20.6 SHOWER UNIT.
 A SHOWER SPRAY UNIT WITH A HOSE AT LEAST 60 INCHES LONG
 THAT CAN BE USED BOTH AS A FIXED SHOWER HEAD AND AS A
 HAND-HELD SHOWER SHALL BE PROVIDED.
  
 COMMENT
 PLEASE COMPLY
  
  
  
 18
 11-4.21.3 SEAT.
 A SEAT SHALL BE PROVIDED IN SHOWER STALLS 36 INCHES BY
 36
 INCHES THE SEAT SHALL BE MOUNTED 17 INCHES TO 19
 INCHES
  
 FROM THE BATHROOM FLOOR AND SHALL EXTEND THE FULL DEPTH
 OF
 THE STALL.
 IN A 36-INCH BY 36-INCH SHOWER STALL, THE SEAT SHALL BE
 ON
 THE WALL OPPOSITE THE CONTROLS.
  
 COMMENT
 PLEASE LOCATE THE SEAT OPPOSITE THE CONTROLS
  
  
  
 19
 11-4.21.7 CURBS.
 IF PROVIDED, CURBS IN SHOWER STALLS 36 INCHES BY 36
 INCHES
 SHALL BE NO HIGHER THAN ? INCH
 SHOWER STALLS THAT ARE 30 INCHES BY 60 INCHES MINIMUM
 SHALL NOT HAVE CURBS.
  
 COMMENT
 PLEASE COMPLY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-30 Cont ID  
Sent By dpalmer Date 2007-12-30 Time 13:27 Rev Time 0.00
Received By dpalmer Date 2007-12-30 Time 13:27 Sent To  
Notes
2007-12-30 13:27:31 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW MUST
 HAVE A PERMIT APPLICATION SUBMITTED BY A LICENSED
 CONTRACTOR. MAY NOT PERFORM WORK AS OWNER/BUILDER UNDER
 FS 489.
  
 2) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW PLEASE
 BE SURE THE APPLIED VALUED FOR THE SCOPE OF WORK SHOWN
 IS BASED ON ALL LABOR, MATERIALS, EQUIPMENT ETC EVEN IF
 ANY ARE OWNER SUPPLIED.
  
 3) NOTE: PLEASE SEE THE SMOKE DETECTOR SHOWN IN THE
 MIDDLE OF THE FAMILY ROOM IS ALSO NOTED AS BEING A
 SMOKE ALARMS. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS
 SHOW A LOW VOLTAGE FIRE ALARM SYSTEM BEING INSTALLED.
  
 4) NOTE: PLEASE SEE THE NEW PANELS SUBMITTED ARE
 UNCLEAR IN THE FACT THAT PANEL *A* WHICH IS SHOWN ON
 THE INSIDE OF THE HOUSE IS SHOWN FEEDING PANEL *B*
 WHICH IS OUTSIDE NEXT TO METER. IS THIS CORRECT? OR ARE
 PANELS THE OTHER WAY?
 PLEASE CLARIFY.
  
 5) NOTE: PLEASE SHOW WHICH CIRCUITS ARE NEW ON PANEL
 SCHEDULE AND WHICH ARE EXISTING. PLEASE EXAMPLE PLEASE
 SEE ROOMS WHICH NOTE NEW ARC FAULT PROTECTION ON
 CIRCUITS HOWEVER CIRCUITS IN PANEL SCHEDULE ARE NOT
 NOTED.
 PLEASE SEE FOR EXAMPLE RANGE ON PLANS APPEARS TO BE
 NEW. PLEASE SEE THE HALLWAY IN THE MAIN AREA OF HOUSE
 SHOWS A NEW RECEPTACLE AND LT IN ATTIC HOWEVER HALLWAY
 ALSO SHOWS ANOTHER NEW RECEPTACLE IN WHAT APPEARS TO BE
 THE MIDDLE OF THE CEILING.
  
 6) NOTE: PLEASE SEE KITCHEN COUNTER SPACE WITH NO GFI
 RECEPTACLE(S) MEETING 210.52C1
 PLEASE SEE TWO REDLINED AREAS.
 IF THESE ARE NOT EXISTING MEETING MINIMUM CODE SPACING
 , NEW WILL BE REQUIRED.
  
 ** PLEASE SEE THAT SOME OF THESE ITEMS ARE ITEMS WHICH
 CAN BE REDLINED HOWEVER THE PERMIT APPLICATION HAS NOT
 YET BEEN APPLIED FOR BY LICENSED CONTRACTOR.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE
 ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By dpalmer Date 2007-10-23 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2007-10-22 Time 19:02 Sent To  
Notes
2007-10-23 14:57:30 
  
 ***DENIED ***
  
 1) NOTE: PLEASE SEE NO PERMIT APPLICATION WAS SUBMITTED
 FOR SCOPE OF WORK WHICH IS REQUIRED TO BE DONE BY A
 LICENSED CONTRACTOR. THE PERMIT AS APPLIED MAY NOT BE
 DONE BY A CORPORATION, OWNER BUILDER, ETC AS STATED IN
 FS 489.113
  
 2) NOTE: PLEASE SEE A VALUATION FOR THE COMPLETE SCOPE
 OF WORK MUST BE STATED AND APPLIED.
 FBC 108.3
  
 3) NOTE: PLEASE SEE THAT ONLY ONE SET OF PLANS WAS
 SUBMITTED WHEN A MINIMUM OF TWO SETS OF ALL DOCUMENTS
 ARE REQUIRED.
 PLEASE SEE FBC 106.1
  
 4) NOTE: PLEASE SEE THE SINGLE SET OF PLANS SUBMITTED
 ARE IN FACT ARE PHOTO-COPIES OF PLANS WHICH APPEARED TO
 BE SIGNED, DATED AND SEALED BY AN ENGINEER.
 PLEASE SUBMIT ORIGINAL SIGNED, DATED AND SEALED PLANS
 BY THE DESIGNER OF RECORD AS REQUIRED PER FAC
 61G15-23.002 AND FS 471.025
  
 5) NOTE: PLEASE SEE THE PLANS CALL FOR NEW CIRCUITS IN
 BATHROOMS WHICH ARE SHOWN AS #14 AWG.
 PLEASE SEE 210.52D, 210.11C3 AS #14 IS NOT SUFFICIENT
 SIZE.
  
 6) NOTE: PLEASE SEE THE PLANS AND FIRE ALARM RISER
 CALLS FOR SA WHICH IS FOR SMOKE ALARMS. PLEASE SEE
 HOWEVER THE NOTE ON PLANS MENTIONS SMOKE DETECTORS.
 PLEASE KNOW AS THE PLAN CONTAINS HORN AND STROBE
 DEVICES FOR ALARM AND SOUNDING THESE DEVICES WOULD MOST
 LIKELY BE SD FOR SMOKE DETECTORS. SMOKE DETECTORS BY
 DEFINITION IN NFPA-72 ARE DEVICES WHICH ONLY DETECT
 SMOKE AND DO NOT SOUND AN ALARM.
 SMOKE ALARM DEVICES BY DEFINITION ACTUALLY DETECT AND
 SOUND AN ALARM.
 THESE DO NOT CORRELATE WITH PLANS.
 PLEASE REVISE AND ADJUST.
  
 7) NOTE: PLEASE PROVIDE A PANEL SCHEDULE FOR NEW
 DEDICATED CIRCUITS AS REQUIRED.
 NEC 408.4, FBC 106.3.5.1.2
  
 8) NOTE: PLEASE KNOW THE PANEL SCHEDULE IS TO INCLUDED
 NEW DEDICATED CIRCUIT REQUIRED FOR FIRE ALARM PANEL
 WHICH IS REQUIRED TO BE MARKED/LABELED/LOCKED OFF FOR
 PROTECTION.
 PLEASE SEE NFPA-72 4.4.1.4.1
  
 9) NOTE: PLEASE PROVIDE AND CLARIFY INFORMATION AND
 SCOPE OF WORK AS APPLIED.
 PLANS CALL FOR BUSINESS OCCUPANCY BUT ALSO R-4?
 PLEASE PROVIDE INFORMATION FROM STATE REGARDING WHAT
 TYPE OF GROUP HOME ETC THIS WILL BE.
 PLEASE KNOW AT THIS TIME THERE MAY BE SOME COMMENTS
 WHICH CAN NOT BE MADE DUE TO INFORMATION AND/OR
 CLARIFICATION NEEDED.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-02-01 Cont ID  
Sent By mwennerg Date 2008-02-01 Time 15:22 Rev Time 0.00
Received By mwennerg Date 2008-02-01 Time 15:22 Sent To  
Notes
2008-02-01 15:27:22***DENIED***
  
 1) A COPY OF THE FIRST FIRE REVIEW IS ATTACHED AS IT
 DOES NOT APPEAR TO HAVE BEEN ADDRESSED. PLEASE RESPOND
 TO COMMENTS TO HELP EXPEDITE THIS PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-06 Cont ID  
Sent By mawillia Date 2007-11-06 Time 13:33 Rev Time 0.00
Received By mawillia Date 2007-11-06 Time 11:27 Sent To  
Notes
2007-11-06 13:33:46*****DENIED*****
  
  
 1.ONLY ONE PLAN SET WAS SUBMITTED FOR REVIEW.PLEASE
 BE ADVISED THAT AT LEAST TWO SETS OF PLANS ARE REQUIRED
 FOR REVIEW.WHEN THE PERMIT HAS BEEN ISSUED, ONE SET
 OF THE REVIEWED AND APPROVED CONSTRUCTION
 DOCUMENTS/PLANS SHALL BE RETAINED IN THE FILES OF THE
 CONSTRUCTION SERVICES DEPARTMENT.
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.BE ADVISED THAT NFPA 101 - 2003 EDITION DOES NOT
 RECOGNIZE GROUP HOMES;THEREFORE LIST THE OCCUPANCY
 TYPE FOR THIS PROJECT (RESIDENTIAL, NEW DAY-CARE, OR
 NEW RESIDENTIAL BOARD AND CARE - SMALL FACILITY) TO
 FURTHER BASE THE FIRE REVIEW.ON SHEET A-5, OCCUPANCY
 CLASSIFICATION OF BUSINESS IS INCORRECT.
  
 4.IF THE OCCUPANCY IS OTHER THAN RESIDENTIAL, ADDRESS
 NUMBERS (AS PER WEST PALM BEACH CODE) SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN STROKE.
 DISPLAY/SHOW THE ADDRESS NUMBER ON THE APPROPIATE
 EXTERIOR ELEVATION (SHEET A-3) WHICH FRONTS ALHAMBRA
 PLACE.
  
 5.IN THE FIRE ALARM RISER SHOWN ON SHEET A-5, TEN
 (10) SMOKE ALARM (SA) DEVICES ARE LISTED HOWEVER, THE
 LIFE SAFETY/FIRE ALARM PLAN ONLY ILLUSTRATES NINE (9)
 SUCH DEVICES.
  
 6.BATHROOM DOORS SHALL BE AT LEAST 24" WIDE AND SHALL
 BE DESIGNED TO ALLOW OPENING FROM THE OUTSIDE DURING AN
 EMERGENCY WHEN LOCKED.
  
 7.EVERY CLOSET DOOR LATCH SHALL BE READILY OPENED
 FROM THE INSIDE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-28 Cont ID  
Sent By spalmer Date 2007-12-28 Time 15:17 Rev Time 0.00
Received By spalmer Date 2007-12-28 Time 15:17 Sent To  
Notes
2007-12-28 15:17:38TO COMM BOARD # 44

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 08:41 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 08:41 Sent To  
Notes
2007-10-18 12:22:39TO "COMM" BD#42
2007-10-18 08:42:12WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 11:14 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 11:14 Sent To Z
Notes
2007-10-09 11:14:42TO "Z" BOX--WAS A PRE-INSPECT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2007-07-09 Cont ID  
Sent By kconrad Date 2007-07-09 Time 13:09 Rev Time 0.00
Received By kconrad Date 2007-07-09 Time 13:09 Sent To I
Notes
2007-07-09 13:15:21PRE-INSPECT DENIED. REQUIRE APPROVED PLANS FOR CHANGE
 OF OCCUPANCY. PLANS TO MEET THE MINIMUM CODE
 REQUIREMENTS OF THE2004 FLORIDA EXISTING BUILDING
 CODE, SECTION 800. ADVISED THE OWNER TO OBTAIN A
 LICENSED DESIGN PROFESSIONAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By rregueir Date 2008-01-22 Time 08:45 Rev Time 0.00
Received By rregueir Date 2008-01-22 Time 08:41 Sent To  
Notes
2008-01-22 08:44:42REVIEW #: 2ND
 ACTION: PASSED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
  
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PREVIOUS REVIEW ERRONIOUSLY IDENTIFIED THE SPACES SHOWN
 ON SCOPE OF WORK AS BEING RECONFIGURED, THUS REQUIRING
 VENTILATION CALCULATIONS. NO SUCH WORK IS NOW SHOWN ON
 PLANS AND THEREFORE NO NEW VENTILATION REQUIREMENTS
 EXIST. ALL MECHANICAL DUCTWORK AND EQUIPMENT IS SHOWN
 AS EXISTING. NO ADDITIONAL MECHANICAL REVIEW IS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-13 Cont ID  
Sent By rregueir Date 2007-11-13 Time 10:57 Rev Time 0.00
Received By rregueir Date 2007-11-13 Time 10:57 Sent To  
Notes
2007-11-13 10:58:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ONLY ONE SET OF PLANS WERE SUBMITTED. PLEASE SUBMIT
 TWO COPIES OF ALL PLANS AND SPECIFICATIONS RELATED TO
 THIS APPLICATION IN ACCORDANCE WITH FBC 106.1.
  
 2. A NEW PERMIT APPLICATION IS REQUIRED, SIGNED BY A
 LICENSED CONTRACTOR, WITH A DESCRIPTION OF THE SCOPE OF
 WORK AS WELL AS A DECLARED VALUATION OF THE WORK.
  
 3. THESE PLANS APPEAR TO HAVE PHOTOCOPIED SIGNATURES OF
 THE DESIGNER AND NO SEAL. ALL PLANS SUBMITTED BY THE
 DESIGN PROFESSIONAL ARE TO BE SIGNED, SEALED AND DATED,
 WITH ORIGINAL SIGNATURES, IN ACCORDANCE WITH FS 471.025
 AND FAC RULE 61G15-23.002.
  
 4. PG A-4: AS A LEVEL 2 ALTERATION, THIS WORK INVOLVES
 THE RECONFIGURATION OF SPACES. AS SUCH, PLEASE SHOW THE
 MEANS AND RATE OF VENTILATION (OUTSIDE AIR) IN
 ACCORDANCE WITH FBC,M CHAPTER 4. SEE FBC, EB 609.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-25 Cont ID  
Sent By mperson Date 2008-01-25 Time 08:59 Rev Time 0.00
Received By mperson Date 2008-01-25 Time 08:59 Sent To  
Notes
2008-01-25 09:08:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PREVIOUS PLAN REVIEW COMMENTS NOT ADDRESSED**
  
 1. **COMMENT NOT ADDRESSED**
 THERE WAS NOT A PERMIT APPLICATION SUBMITTED FOR THE
 PROPOSED WORK WHICH IS REQUIRED BY A LICENSED
 CONTRACTOR. PER *FS489.113 PERMIT APPLICATION CAN NOT
 BE SUBMITTED BY A CORPORATION OR OWNER BUILDER.
  
 2. **COMMENT NOT ADDRESSED**
 THERE WAS NO VALUATION FOR THE PROPOSED WORK. PER
 *108.3 VALUATION MUST BE ON THE REQUIRED PERMIT
 APPLICATION FOR THE PROPOSED WORK.
  
 3. **COMMENT NOT ADDRESSED**
 ONLY ONE SET OF PLANS WERE SUBMITTED.
 PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 4. **COMMENT NOT ADDRESSED DUE TO ONLY ONE SET OF
 PLANS BEING SUBMITTED**
 SUBMITTED PLANS WERE NOT SEALED BY ENGINEER OF RECORD.
 PER *FAC-61G15-23.002 ANS *FS 471.025, SEAL SIGNATURE
 AND DATE SHALL BE AFFIXED.
  
 5. **COMMENT NOT ADDRESSED**
 PER FBC PLUMBING TABLE 403.1, R-4: A DRINKING FOUNTAIN
 (1 PER 100) AND 1 SERVICE SINK ARE REQUIRED FOR AN
 R-4.
  
 6. **COMMENT NOT ADDRESSED, SEE NOTE BELOW COMMENT**
 SHEET A-5 SANITARY ISOMETRIC RISER DIAGRAM: THE
 RELOCATED WASHING MACHINE MUST DISCHARGE DOWNSTREAM OF
 THE WET VENTED BATHROOM GROUP. PER * 909.1, WET VENT
 PERMITTED.
 NOTE: THE RESUBMITTED PLAN HAS DELETED THE REQUIRED
 SANITARY RISER DIAGRAM FOR THE RELOCATED WASHING
 MACHINE, ALSO THE REQUIRED DRINKING FOUNTAIN AND
 SERVICE SINK WILL NEED TO BE ON THE SANIATRY RISER
 DIAGRAM.
  
 7. **COMMENT NOT ADDRESSED**
 PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, PLUMBING:
 AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS REQUIRED
 FOR THE PROPOSED WORK (WASHING MACHINE AND THE REQUIRED
 DRINKING FOUNTAIN AND SERVICE SINK PER TABLE *403.1
 R-4) FOR BOTH THE HOT AND COLD WATER INDICATING THE
 PIPE SIZES, VALVE LOCATIONS, LOCATION OF THE WATER
 SUPPLY LINE WITH BACKFLOW PREVENTER **608, THERMAL
 EXPANSION CONTROL FOR THE WATER HEATER **607.3, AND
 LOCATION OF THE WATER-HAMMER ARRESTORS WHERE QUICK
 CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
  
 8. **COMMENT NOT ADDRESSED, ELEVATION DETAILS REQUIRED
 AND CLEAR FLOOR SPACE NEEDS TO INDICATED ON THE FLOOR
 PLAN AS WELL AS WHEELCHAIR TURNING SPACE**
 THE FOLLOWING ARE REQUIRED FOR THE ACCESSIBLE FIXTURES
 PER CHAPTER 11 FLORIDA ACCESSIBILTY CODE: **NOTE:
 BACKING SHALL BE INDICATED FOR GRAB BARS ON THE
 REQUIRED ELEVATION DETAILS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19"
 HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37)
 11-4.21.5 CONTROLS. REQUIRED (SEE FIGURE 37)
 11-4.21.7 CURBS. 36" X 36" MAXIMUM 1/2" CURB (NO CURB
 REQUIRED IN MINIMUM 30" X 60" STALLS)
  
 **THE FOLLOWING ARE NEW ITEMS THE ARE REQUIRED TO BE
 ADA COMPLIANT**
  
 ** 11-4.20 BATHTUBS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33)
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.5 CONTROLS. (SEE FIGURE 34)
 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE
 MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD
 SHALL BE PROVIDED.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.(NO CABINET DOORS)
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-03 Cont ID  
Sent By mperson Date 2007-12-03 Time 06:13 Rev Time 0.00
Received By mperson Date 2007-12-03 Time 06:13 Sent To PC
Notes
2007-12-03 07:34:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THERE WAS NOT A PERMIT APPLICATION SUBMITTED FOR
 THE PROPOSED WORK WHICH IS REQUIRED BY A LICENSED
 CONTRACTOR. PER *FS489.113 PERMIT APPLICATION CAN NOT
 BE SUBMITTED BY A CORPORATION OR OWNER BUILDER.
  
 2. THERE WAS NO VALUATION FOR THE PROPOSED WORK. PER
 *108.3 VALUATION MUST BE ON THE REQUIRED PERMIT
 APPLICATION FOR THE PROPOSED WORK.
  
 3. ONLY ONE SET OF PLANS WERE SUBMITTED.
 PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 4. SUBMITTED PLANS WERE NOT SEALED BY ENGINEER OF
 RECORD. PER* FAC-61G15-23.002 AND *FS 471.025, SEAL
 SIGNATURE AND DATE
 SHALL BE AFFIXED.
 *NOTE: IT ALSO APPEAR SIGNATURE WAS PHOTO COPIED,
 ORIGINAL SIGNATURE REQUIRED.
  
 5. PER TABLE 403.1, R-4: A DRINKING FOUNTAIN (1 PER
 100) AND 1 SERVICE SINK REQUIRED.
  
 6. SHEET A-5 SANITARY ISOMETRIC RISER DIAGRAM: THE
 RELOCATED WASHING MACHINE MUST DISCHARGE DOWNSTREAM OF
 THE WET VENTED BATHROOM GROUP. PER * 909.1, WET VENT
 PERMITTED.
  
 7. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE
 WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 8. THE FOLLOWING ARE REQUIRED FOR THE ACCESSIBLE
 FIXTURES PER CHAPTER 11 FLORIDA ACCESSIBILTY CODE:
 **NOTE: BACKING SHALL BE INDICATED FOR GRAB BARS ON THE
 REQUIRED ELEVATION DETAILS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37) 11-4.21.5
 CONTROLS. REQUIRED (SEE FIGURE 37) 11-4.21.7 CURBS. 36"
 X 36" MAXIMUM 1/2" CURB (NO CURB REQUIRED IN MINIMUM
 30" X 60" STALLS)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-31 Cont ID  
Sent By choops Date 2007-12-31 Time 09:07 Rev Time 0.00
Received By choops Date 2007-12-31 Time 09:07 Sent To  
Notes
2007-12-31 09:09:14***APPROVED - ONE (1) SET OF PLANS KEPT FOR PLANNING
 AND ZONING DEPARTMENT RETENTION***
  
 NOTE:A BUSINESS TAX RECEIPT WILL BE REQUIRED FOR THE
 OCCUPATIONAL USE.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By choops Date 2007-10-12 Time 10:54 Rev Time 0.00
Received By choops Date 2007-10-12 Time 10:54 Sent To E
Notes
2007-10-12 10:56:28***FAILED***
  
  
 1)PLEASE SUBMIT AN EXTRA COPY OF PLANS FOR PLANNING
 & ZONING DEPARTMENT RETENTION.
  
 NOTE:A BUSINESS TAX RECEIPT WILL BE REQUIRED FOR THE
 OCCUPATIONAL USE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved