Plan Review Details - Permit 07060708
Plan Review Stops For Permit 07060708
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-25 Cont ID  
Sent By mjacobs Date 2007-08-25 Time 14:00 Rev Time 0.00
Received By mjacobs Date 2007-08-25 Time 13:29 Sent To  
Notes
2007-08-25 14:01:32NEED FIRE REVIEW.
 GAVE PLANS TO'DP'

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 18:56 Rev Time 0.00
Received By mjacobs Date 2007-06-29 Time 18:03 Sent To  
Notes
2007-06-29 18:56:24BUILDING PLAN REVIEW
 PERMIT: 07060708
 ADD: 1475 CENTREPARK BLVD
 CONT: ANDERSON MOORE CONST.
 TEL: (561)753-7400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)FBC 108.3*THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By dpalmer Date 2007-09-25 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2007-09-25 Time 08:50 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 14:37 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 14:37 Sent To  
Notes
2007-08-23 14:38:03*** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
  
 1) NOTE:PLEASE SEE A NEUTRAL CONDUCTOR IS BEING SHOWN
 TO THE TRANSFORMER WHICH IS NOT POSSIBLE WHEN THIS IS A
 TRANSFORMER CREATING A SEPARATELY DERIVED SYSTEM.
 PLEASE VERIFY AND REVISED AS NEEDED.
 250.20, 250.30
  
 2) NOT: PLEASE SEE NO MAXIMUM TIMES ARE STATED FOR THE
 OC TYPE DEVICES AS SHOWN ON LEGEND. THIS WAS REQUESTED
 ON THE PREVIOUS REVIEW.
 13-415.1.ABC.1.1
  
 3) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES SHOWN
 ON TABLE ARE INDICATING AT LEAST FOUR LOCATIONS WHERE
 THE MAXIMUM PERMITTED WATTS PER SQ FT IS EXCEEDED BASED
 ON THE TABLES IN 13-415.2.B.
 PLEASE CLARIFY WHICH TABLE IS BEING USED.
 PLEASE SEE NO TOTAL DESIGN/ALLOWANCE IS INDICATED ON
 PLANS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-24 Cont ID  
Sent By dpalmer Date 2007-06-24 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2007-06-24 Time 15:32 Sent To  
Notes
2007-06-24 15:44:31*** UNSAT ***
  
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.SOME OF THESE ARE
 STATED ON PLANS HOWEVER NOT ALL OR NOT ALL CURRENT PER
 STATE ADOPTED CODES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND
 ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE SOME OF THE CODES REFLECTED ON PLANS ARE
 NOT CURRENT.
 ** PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH MAY
 REQUESTED OTHER CODES TO BE STATED.
  
 2) NOTE: PLEASE PROVIDE LIGHTING CONTROLS IN SEPARATE
 SPACES AND AREAS PER 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE ONLY ONE OS DEVICE WAS LOCATED IN MAIN
 AREA.
 PLEASE PROVIDE LIGHTING PERFORMANCE INFORMATION PER
 13-415.2.
 AS NOT ENERGY CALCULATIONS WERE SUBMITTED (REQUIRED?),
 LIGHTING INFORMATION IS STILL NEEDED.
 PLEASE COORDINATE LPD'S WITH A FIXTURE LEGEND TO BE
 PROVIDED.
 PLEASE BE SURE ALL TIMES ARE INDICATED FOR DEVICES
 CHOSEN.(ALREADY NOTED FOR OS DEVICE SHOW).
  
 3) NOTE: PLEASE INDICATE THE LOCATION OF ALL
 SERVICE/TRANSFORMER EQUIPMENT. PLANS MENTIONS THE
 TRANSFORMER IS BEING MOVED TO ABOVE CEILING. PLEASE
 PROVIDE DETAIL FOR STRUCTURAL MOUNTING OF WHAT IS BEING
 SHOWN AS EXISTING TRANSFORMER.
 110.26, 450.13
 PLEASE PROVIDE GROUNDING ATTACHMENT LOCATION FOR THE
 GROUNDING ELECTRODE CONDUCTOR OF TRANSFORMER.
 250.50, 250.20, 250.30.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-25 Cont ID  
Sent By mawillia Date 2007-08-25 Time 15:05 Rev Time 0.00
Received By mawillia Date 2007-08-25 Time 14:59 Sent To  
Notes
2007-08-25 15:05:03*****APPROVED*****
  
  
 RESTAMP OF PLAN SHEET A-1 WHICH WAS PREVIOUSLY STAMPED
 (06/28/07) BY M.R. WENNERGREN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-06-28 Cont ID  
Sent By mwennerg Date 2007-06-28 Time 11:05 Rev Time 0.00
Received By mwennerg Date 2007-06-28 Time 11:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 14:49 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 14:49 Sent To E
Notes
2007-09-24 14:49:44TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 09:21 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 09:21 Sent To  
Notes
2007-08-23 13:27:35TO "BOB"#12
2007-08-10 09:21:22WAITING FOR BOB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-02 Cont ID  
Sent By jleech Date 2007-07-02 Time 08:19 Rev Time 0.00
Received By jleech Date 2007-06-24 Time 13:27 Sent To  
Notes
2007-06-24 13:27:37TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-24 Cont ID  
Sent By tgordon Date 2007-08-24 Time 09:09 Rev Time 0.20
Received By tgordon Date 2007-08-24 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-06-25 Cont ID  
Sent By tgordon Date 2007-06-25 Time 13:30 Rev Time 0.25
Received By tgordon Date 2007-06-25 Time 13:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-07-02 Cont ID  
Sent By jleech Date 2007-07-02 Time 08:19 Rev Time 0.00
Received By jleech Date 2007-07-02 Time 08:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-24 Cont ID  
Sent By choops Date 2007-08-24 Time 16:35 Rev Time 0.00
Received By choops Date 2007-08-24 Time 16:35 Sent To  
Notes
2007-08-24 16:35:54*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.