Plan Review Details - Permit 07060707
Plan Review Stops For Permit 07060707
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2008-05-05 Cont ID  
Sent By lursu Date 2008-05-05 Time 11:21 Rev Time 0.00
Received By lursu Date 2008-05-05 Time 11:21 Sent To  
Notes
2008-05-05 11:23:44NEW SITE ADDRESS TO USE IS 3100 N MILITARY TRL ALONG
 WITH THE EXISTING PCN FOR 3200 N MILITARY TRL .AT THE
 TIME WHEN THE NEW PARCEL CONTROL NUMBER IS ISSUED BY
 THE PROPERTY APPRAISER , THE ADDRESS BE ATTACHED TO THE
 NEW PCN.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2008-02-07 Cont ID  
Sent By lursu Date 2008-02-07 Time 08:47 Rev Time 0.00
Received By lursu Date 2008-02-07 Time 08:47 Sent To  
Notes
2008-02-07 08:48:38***FAILED***
  
 THE UOT( UNITY OF TITLE)MUST BE RECORDED AND PROPERTY
 APPRAISER'S OFFICE MUST ASSIGN A NEW PARCEL CONTROL
 NUMBER FOR ALL UNIFIED PARCELS PRIOR OF THE NEW SITE
 ADDRESS TO BE RELEASED.
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By lursu Date 2007-09-06 Time 09:43 Rev Time 0.00
Received By lursu Date 2007-08-02 Time 09:28 Sent To  
Notes
2007-09-06 09:46:25FOR THE NEW BUILDING TO BE BUILD A NEW SITE ADDRESS IS
 REQUIRED.PRIOR OF RELEASING THE SITE ADDRESS THE UNITY
 OF TITLE OR REPLAT IS NECESSARY FOR ALL PARCELS PART OF
 THIS PROJECT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-07-03 11:52:07NEEDS

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2009-09-01 Cont ID  
Sent By jwitmer Date 2009-09-01 Time 13:44 Rev Time 1.22
Received By jwitmer Date 2009-09-01 Time 11:18 Sent To  
Notes
2009-09-01 13:26:00ARCHITECUTRAL REVISION# 12, 7-20-09
  
 A-001
 A-010
 A-011
 A-012
 A-100
 A-100A
 A-400
 A-401
  
 FIRE SPRINKLER PLAN REVISION# 7
 FIRE SPRINKLER PERMIT# 08110219
 NOTE THE MAIN FIRE SPRINKLERS TO BE IN BEFORE C.O.
 FP-102
 FP-103

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2009-06-30 Cont ID  
Sent By jwitmer Date 2009-06-30 Time 09:30 Rev Time 1.00
Received By jwitmer Date 2009-06-30 Time 08:23 Sent To  
Notes
2009-06-30 09:25:30REVISION, SHEETS:
 A-010
 A-012
 A-100
 A-100A
 A-101
 A-103
 A-400
 A-900

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-02-06 Cont ID  
Sent By jwitmer Date 2009-02-06 Time 14:42 Rev Time 0.77
Received By jwitmer Date 2009-02-06 Time 14:42 Sent To  
Notes
2009-02-06 14:43:28STEEL BAR JOIST AND ENGINEERING CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-01-02 Cont ID  
Sent By jwitmer Date 2009-01-02 Time 14:29 Rev Time 0.77
Received By jwitmer Date 2009-01-02 Time 14:20 Sent To PC
Notes
2009-01-02 14:30:08SUBMITTAL: SHORING DRAWINGS FOR SMALL MEZZANINE

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-12-30 Cont ID  
Sent By jwitmer Date 2008-12-30 Time 15:56 Rev Time 4.44
Received By jwitmer Date 2008-12-30 Time 15:56 Sent To  
Notes
2008-12-30 16:02:53REVISION:# 7 REVIEWED WITH EXCEPTION TO PREVIOUS
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-12-29 Cont ID  
Sent By jwitmer Date 2008-12-29 Time 15:41 Rev Time 3.33
Received By jwitmer Date 2008-12-29 Time 10:38 Sent To  
Notes
2008-12-29 16:57:15BUILDING PLAN REVIEW
 PERMIT: 07060707
 ADD: 3100 N MILITARY TRAIL
 CONT: ANDERSON MOORE
 TEL: (561)753-7400
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW: REVISION# 7 / DATE 11-07-08
 ACTION: DENIED
 SHEETS: A-100, A-100A, A-101 & A-103.
  
 1) A-100 , A101& A-101A ALL INDICATE DOOR# 170 (D-G) AS
 A 1 1/2 HOUR FIRE RATED DOOR BUT THE DOOR SCHEDULE ON
 SHEET A900 INDICATE THESE DOORS TO BE INSTALLED WITH
 DOUBLE ACTION DOOR HINGES. TABLE 302.3.2 DOES INDICATE
 TWO HOUR WALLS ARE REQUIRED AND THE PLANS INDICATE AS
 SUCH BUT THE DOOR OPENINGS REQUIRE OPENING PROTECTION.
 TABLE 715.3 INDICATES THE DOOR OPENINGS TO HAVE A 1 1/2
 HR FIRE RATING.
  
 THERE ARE THREE ISUES WITH THE DOUBLE ACTION TYPE DOOR:
  
 1A) SECTION 715.3.3 FIRE DOOR ASSEMBLIES SHALL ALSO
 MEET THE THE REQUIREMENTS FOR A SMOKE AND DRAFT CONTROL
 DOOR ASSEMBLY TESTED IN ACCORDANCE WITH UL 1784 WITH AN
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS THE FULL BOTTOM
 OF THE DOOR ASSEMBLY.
  
 1B) 15.3.7 DOOR CLOSING. FIRE DOORS SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING IN ACCORDANCE WITH
 THIS SECTION.
  
 1C)715.3.7.1 LATCH REQUIRED. UNLESS OTHERWISE
 SPECIFICALLY PERMITTED, SINGLE FIRE DOORS AND BOTH
 LEAVES OF PAIRS OF SIDE-HINGED SWINGING FIRE DOORS
 SHALL BE PROVIDED WITH AN ACTIVE LATCH BOLT THAT WILL
 SECURE THE DOOR WHEN IT IS CLOSED.
  
 2) SHEET A103 DOOR OPENING # 165 B & C:
  
 2A) DOOR# 165C IS INDICATED IN THE DOOR SCHEDULE AS A 1
 1/2 HR RATED DOOR AND FRAME. THE DOOR SCHEDULE SHEET
 A900 INDICATES THIS TO BE DOOR TYPE "D" PLANS DO NOT
 INDICATE THE SIZE OF THE GLAZED WINDOW TABLE 715.4.3.
 INDICATES FOR A 1 1/2 HR OPENING PROTECTIVE THE MAXIMUM
 SIXE OF WIRE GLASS IS 100 SQ INCHES OR HEIGHTH 33" AND
 WIDTH 10". PLEASE PROVIDE THIS INFORMATION ON THE
 PLANS, DOOR SCHEDULE.
  
 2B) DOOR # 165B IS A STORAGE ROOM WITHIN A STORAGE ROOM
 , WHY DOES THIS DOOR INDICATE A FIRE RATING PLEASE SEE
 DOOR SCHEDULE A900.ADDDITIONAL INFORMATION REQUIRED
 106.1.2.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 08:44 Rev Time 2.22
Received By jwitmer Date 2008-09-09 Time 08:44 Sent To PC
Notes
2008-09-09 08:54:52PEGGY ADAMS ANIMAL
 RESCUE LEAGUE
 3200 N MILITARY TRAIL
 BUILDING PLAN REVIEW
 PERMIT: 07060707
 ADD: 3200 N MILITARY TRAIL
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 ISSUED PLANS
 BUILDING PROVISOS:
  
 1) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 2) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 07060707
 ROOFING NOTES/ NO ROOFING CONTRACTOR SIGNED ON AT TIME
 OF ISSUANCE
 MODIFIED BIT FL644-R3 + ENHANCED FASTENING NOA
 07-0228.04 JOHN MANVILLE MODIFIED
 ZONE 1-P13 SYSTEM B(4)
 ZONE 2-P 9 SYSTEMB(2)
 ZONE 3 ENHANCED FASTENING
 ROOF TILE FL601-R2MONIER LIFETIME NOA07-1023.09

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-08-22 Cont ID  
Sent By jwitmer Date 2008-08-22 Time 10:24 Rev Time 7.77
Received By jwitmer Date 2008-08-22 Time 10:24 Sent To  
Notes
2008-08-22 10:33:42PEGGY ADAMS ANIMAL
 RESCUE LEAGUE
 3200 N MILITARY TRAIL
 BUILDING PLAN REVIEW
 PERMIT: 07060707
 ADD: 3200 N MILITARY TRAIL
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: DENIED
  
 PLANS APPEAR TO BE CODE COMPLIANT WILL BE ABLE TO PASS
 AFTER IMPACT FEE ASSESSMENT.
  
 1) BUILDING PROVISO: WILL REQUIRE NEW PRODUCT APPROVAL
 COVER SHEET FROM THE ARCHITECT OF RECORD SIGNED AND
 SEALED LISTING REVIEWED & AND APPROVED PRODUCT
 APPROVALS.
  
 2) BUILDING PROVISO: FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.24(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) BUILDING PROVISO FBC BUILDING 3110.1.2 / CITY OF WPB
 CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED
 IN AN "A-8" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE
 WILL BE REQUIRED. BASE FLOOD 16.00+ .5'= 16.5'.
  
 4) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-06 Cont ID  
Sent By jwitmer Date 2008-06-06 Time 13:24 Rev Time 3.33
Received By jwitmer Date 2008-06-06 Time 13:24 Sent To  
Notes
2008-06-06 13:53:53PEGGY ADAMS ANIMAL
 RESCUE LEAGUE
 3200 N MILITARY TRAIL
 BUILDING PLAN REVIEW
 PERMIT: 07060707
 ADD: 3200 N MILITARY TRAIL
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) .FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.24(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-6) COMPLIED.
  
 7A)COMPLIED.
  
 7B) COMPLIED.
 8) PROVISO: A-8FLOOD ZONEELE CERTIFICATE MINIMUM
 BASE FLOOD ELEVATION 16.5'.
  
 9) BUILDING PROVISO: 109.3.10 IMPACT OF CONSTRUCTION.
  
 10) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
  
 11) COMPLIED.
  
 10A-C) COMPLIED.
  
 11) COMPLIED.
  
 12) COMMENT DELETED.
  
 13-14) COMPLIED.
  
 15A) 2ND REQUEST,
  
 15B) WINDOWS IN THE PRE-OP AND POST-OP (4) ARE WITHIN
 THE 2 HR RATED WALL A-903 WINDOW SCHEDULE WINDOW# 18 NO
 FIRE RATING IS INDICATED. TABLE 715.3 & TABLE 715.4.
  
 NO COMMENT RESPONCES AFTER 15B.
  
  
 15C) COMPLIED.
  
 16) COMPLIED.
  
 17) 3RDREQUEST, 435.5.1 SHIELDING. EACH X-RAY
 FACILITY SHA 435.5.1 SHIELDING. EACH X-RAY FACILITY
 SHALL HAVE PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS
 NEEDED TO ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A
 RADIATION DOSE IN EXCESS OF THE LIMITS SPECIFIED IN
 PART III OF CHAPTER 64 E-5, FLORIDA ADMINISTRATIVE CODE
 . CONTACT: TOM TOMCZAK (904) 278-5730
 705 ROSE RD SUITE# 300
 ORANGE PARK, FL 32073
  
 435.5.1.1
 STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL
 BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND
 WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET (2.1 M).
 435.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED.
 435.5.1.3
 PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT
 ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS
 OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF
 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC
 PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH
 FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE
 BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD,
 USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
 435.5.1.3.1
 THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING:
 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S
 RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS;
 GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY
 WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S
 BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL.
 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS
 OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS,
 FLOOR AND CEILING OF THE ROOM CONCERNED. 435.5.1.3.1.3
 THE DIMENSIONS OF THE ROOM CONCERNED. 435.5.1.3.1.4 THE
 TYPE OF OCCUPANCY OF ALL ADJACENT AREAS INCLUSIVE OF
 SPACE ABOVE AND BELOW THE ROOM CONCERNED. IF THERE IS
 AN EXTERIOR WALL, THE DISTANCE TO THE CLOSEST AREA
 WHERE IT IS LIKELY THAT INDIVIDUALS MAY BE PRESENT.
 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT
 AND THE MAXIMUM TECHNIQUE FACTORS.
 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS
 WHICH WILL BE PERFORMED WITH THE EQUIPMENT. LL HAVE
 PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS NEEDED TO
 ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A RADIATION
 DOSE IN EXCESS OF THE LIMITS SPECIFIED IN PART III OF
 CHAPTER 64 E-5, FLORIDA ADMINISTRATIVE CODE .
  
 18-21) COMPLIED.
  
 22) COMPLIED.
  
 23) SEMI-COMPLIED. THE DESIGNER OF RECORD DOES INDICATE
 REVIEW OF PRODUCTS LISTED IN A TITLE PAGE AND SIGNED
 TITLE PAGE IN BLUE INK BUT DID NOT SEAL THE TITLE
 PAGE.
  
 24) COMPLIED.
  
 25) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
  
 25I) 2ND REQUEST, ROOFING ASSEMBLIES- FLAT ROOF, THE
 NOA SUBMITTED AND SUB-SYSTEM HIGHLIGHTED IS FOR A
 CONCRETE DECK NOT A STEEL DECKWITH INSULATION, ALL OF
 THE SUB-SYSTEMS LISTED IN THIS NOA ARE FOR CONCRETE
 DECKS EITHER INSULATION OR NOT.
  
 25I)2ND REQUEST, ROOFINFG ASSEMBLIES- CONCRETE TILE
 ROOFING, (2) MONIER TILE SUBMITTED IN BOTH CASES, THE
 CONTRACTOR DID NOT INDICATE AS TO HOW THE ROOF TILE
 WERE TO BE ATTACHED TO RESIST THE MOMENT OF
 OVERTURNING.
  
 25K) NO PRODUCT APPROVALS SUBMITTED FOR PRE-ENGINEERED
 A/C STANDS
  
 25L) EXTERIOR COOLERS-BEFORE THIS REVIEW IT WAS NOT
 CLEAR IF THIS UNIT WAS TO BE CONSIDERED ON THE EXTERIOR
 OF THE BUILDING.
  
 26) SEMI- COMPLIED SEE ABOVE ( 25I).
  
 27) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENTS OFTIME OF THE 2ND REVIEW:
  
 28) 2ND REQUEST, SHEET A-304 VARIOUS SECTIONS INDICATE
 THE USE OF 1/2 INCH PLYWOOD OVER 3 INCH RIGID
 INSULATION OVER A METAL DECK. THIS BUILDING TYPE IS
 DECLARED A TYPE II-B STRUCTURE, PLEASE SEE TABLE 601
 FOOTNOTE (C) (2) REQUIRING THE ROOFING TO BE FIRE
 RETARDANT TREATED WOOD.
  
 29) SHEET S-302ALSO INDICATES THE USE OF WOOD TRUSSES
 BEAMS IN THE SAME BASIC DETAIL NUMBER 2 & 3INDICATES
 WOOD TRUSSES? THIS BUILDING TYPE IS DECLARED A TYPE
 II-B STRUCTURE, PLEASE SEE TABLE 601 FOOTNOTE (C) (2)
 REQUIRING THE ROOFING TO BE FIRE RETARDANT TREATED
 WOOD.
  
 30) SHEET S-419 INDICATES THE USE OF STRUCTURAL GLAZED
 FACING TILE, PLEASE PROVIDE INFORMATION FROM THE
 MANUFACTURER. 106.1.2 ADDITONAL INFORMATION REQUIRED.
 PLEASE CORRECT ALL SHEETS WHERE WOOD TRUSSES OR WOOD
 BEAMS ARE WITHIN THE BUILDING FRAMING OR RECLASSIFY THE
 BUILDING TYPE THAT WOULD MEET THE ALLOWABLE SQUARE
 FOOTAGE AND OCCUPANCY WITH WOOD FRAMING MEMBERS.
  
 31)COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-19 Cont ID  
Sent By jwitmer Date 2008-02-19 Time 16:15 Rev Time 5.55
Received By jwitmer Date 2008-02-19 Time 10:39 Sent To  
Notes
2008-02-19 16:32:35PEGGY ADAMS ANIMAL
 RESCUE LEAGUE
 3200 N MILITARY TRAIL
 BUILDING PLAN REVIEW
 PERMIT: 07060707
 ADD: 3200 N MILITARY TRAIL
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) .FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.24(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-6) COMPLIED.
  
 7A) 2ND REQUEST,THE RESPONSE SHEET INDICATES THE
 RESIDENT INSPECTOR INFORMATION PACKET IS PART OF THE
 RESUBMITTAL, DIDN'T LOCATE IT.FBC* 109.3.7RESIDENT
 INSPECTOR. SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF THE RESIDENT
 INSPECTOR PROGRAM.A RESIDENT INSPECTOR PROGRAM IS
 REQUIRED, ON THIS PROJECT, DUE TO ONE OR MORE OF THE
 FOLLOWING:
 XXX - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 XXX- BUILDINGS OVER 20,000 SQ FT IN AREA (35,772 SQ
 FT)
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 7B) THREE SETS OF PLANS, PRODUCT APPROVALS AND OTHER
 REPORTS WILL BE REQUIRED FOR A RESIDENT INSPECTOR. SEE
 109.3.7.
  
 8) PROVISO: A FLOOD ZONECERTIFICATE WILL BE REQUIRED
 SINCE THIS BUILDING IS LOCATED IN A A-8 FLOOD ZONE.
 THIS DOCUMENT WILL BE REQUIRED BEFORE THE ISSUANCE OF
 ANY C. O.
  
 9) BUILDING PROVISO: 109.3.10 IMPACT OF CONSTRUCTION.
  
 10) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
  
 11) COMPLIED.
  
 10A-C) COMPLIED.
  
 11) 2ND REQUEST,PLEASE SEE A-100 AND A-101 THE MAIN
 LOBBY (101) & SURRENDER LOBBY (180) PROVIDE DETAILS
 SHOWING COMPLIANCE WITH 11-7.2(1) SERVICE COUNTERS WITH
 ELEVATIONS OF 36".SEE DETAILS ON SHEET A-713 DETAILS
 103-105.
  
 12) COMMENT DELETED.
  
 13-14) COMPLIED.
  
 15A) 2ND REQUEST,
  
 15B) 2ND REQUEST, THE EQUIVALENT THICKNESS OF THE
 MASONARY UNITS WOULD BE THICKERTHAN INDICATESD ON THE
 LIFE SAFETY PLAN.THE LIFE SAFETY PLAN ALSO INDICATES
 AROUND THE KENNEL OCCUPANCY WHEREAS NEITHER OF THE
 SHEETS A-100 OR A-101 PROVIDE ANY WALL TAGS INDICATING
 A 2HR SEPARATION. PLEASE PROVIDE THE EQUIVALENT
 THICKNESS FOR CONCRETE BLOCK FROM THE MANUFACTURER
 INDICATING THE EQUIVALENT THICKNESS 721.3.2.
  
 15C) COMPLIED.
  
 16) COMPLIED.
  
 17) 2ND REQUEST, 435.5.1 SHIELDING. EACH X-RAY FACILITY
 SHA 435.5.1 SHIELDING. EACH X-RAY FACILITY SHALL HAVE
 PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS NEEDED TO
 ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A RADIATION
 DOSE IN EXCESS OF THE LIMITS SPECIFIED IN PART III OF
 CHAPTER 64 E-5, FLORIDA ADMINISTRATIVE CODE . CONTACT:
 TOM TOMCZAK (904) 278-5730
 705 ROSE RD SUITE# 300
 ORANGE PARK, FL 32073
  
 435.5.1.1
 STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL
 BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND
 WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET (2.1 M).
 435.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED.
 435.5.1.3
 PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT
 ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS
 OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF
 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC
 PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH
 FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE
 BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD,
 USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
 435.5.1.3.1
 THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING:
 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S
 RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS;
 GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY
 WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S
 BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL.
 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS
 OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS,
 FLOOR AND CEILING OF THE ROOM CONCERNED. 435.5.1.3.1.3
 THE DIMENSIONS OF THE ROOM CONCERNED. 435.5.1.3.1.4 THE
 TYPE OF OCCUPANCY OF ALL ADJACENT AREAS INCLUSIVE OF
 SPACE ABOVE AND BELOW THE ROOM CONCERNED. IF THERE IS
 AN EXTERIOR WALL, THE DISTANCE TO THE CLOSEST AREA
 WHERE IT IS LIKELY THAT INDIVIDUALS MAY BE PRESENT.
 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT
 AND THE MAXIMUM TECHNIQUE FACTORS.
 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS
 WHICH WILL BE PERFORMED WITH THE EQUIPMENT. LL HAVE
 PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS NEEDED TO
 ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A RADIATION
 DOSE IN EXCESS OF THE LIMITS SPECIFIED IN PART III OF
 CHAPTER 64 E-5, FLORIDA ADMINISTRATIVE CODE .
  
 18-21) COMPLIED.
  
 22) COMPLIED.
  
 23) SEMI-COMPLIED. THE DESIGNER OF RECORD DOES INDICATE
 REVIEW OF PRODUCTS LISTED IN A TITLE PAGE AND SIGNED
 TITLE PAGE IN BLUE INK BUT DID NOT SEAL THE TITLE
 PAGE.
  
 24) COMPLIED.
  
 25) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
  
 25I) ROOFING ASSEMBLIES- FLAT ROOF, THE NOA SUBMITTED
 AND SUB-SYSTEM HIGHLIGHTED IS FOR A CONCRETE DECK NOT A
 STEEL DECKWITH INSULATION, ALL OF THE SUB-SYSTEMS
 LISTED IN THIS NOA ARE FOR CONCRETE DECKS EITHER
 INSULATION OR NOT.
  
 25I) ROOFINFG ASSEMBLIES- CONCRETE TILE ROOFING, (2)
 MONIER TILE SUBMITTED IN BOTH CASES, THE CONTRACTOR DID
 NOT INDICATE AS TO HOW THE ROOF TILE WERE TO BE
 ATTACHED TO RESIST THE MOMENT OF OVERTURNING.
  
 25K) NO PRODUCT APPROVALS SUBMITTED FOR PRE-ENGINEERED
 A/C STANDS
  
 25L) EXTERIOR COOLERS-BEFORE THIS REVIEW IT WAS NOT
 CLEAR IF THIS UNIT WAS TO BE CONSIDERED ON THE EXTERIOR
 OF THE BUILDING.
  
 26) SEMI- COMPLIED SEE ABOVE ( 25I).
  
 27) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENTS:
  
 28) SHEET A-304 VARIOUS SECTIONS INDICATE THE USE OF
 1/2 INCH PLYWOOD OVER 3 INCH RIGID INSULATION OVER A
 METAL DECK. THIS BUILDING TYPE IS DECLARED A TYPE II-B
 STRUCTURE, PLEASE SEE TABLE 601 FOOTNOTE (C) (2)
 REQUIRING THE ROOFING TO BE FIRE RETARDANT TREATED
 WOOD.
  
 29) SHEET S-114 ALSO INDICATES THE USE OF WOOD BEAMS IN
 THE SAME BASIC DETAIL NUMBER 43 & 44 THERE IS A
 DISCREPANCY, ONE INDICATES A CONVENTIONAL WOOD FRAME
 ROOF WHILE THE OTHER INDICATES WOOD TRUSSES? THIS
 BUILDING TYPE IS DECLARED A TYPE II-B STRUCTURE, PLEASE
 SEE TABLE 601 FOOTNOTE (C) (2) REQUIRING THE ROOFING TO
 BE FIRE RETARDANT TREATED WOOD.
  
 30) SHEET S-419 INDICATES THE USE OF STRUCTURAL GLAZED
 FACING TILE, PLEASE PROVIDE INFORMATION FROM THE
 MANUFACTURER. 106.1.2 ADDITONAL INFORMATION REQUIRED.
  
 31) PLEASE PROVIDE A UNITY OF TITLE FOR ALL OF THE
 LOTS,UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF OF TITLE' DOCUMENT SO
 THAT FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED
 NOT APPLICABLE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 10:47 Rev Time 12.12
Received By jwitmer Date 2007-08-03 Time 07:47 Sent To  
Notes
2007-08-06 21:32:27PEGGY ADAMS ANIMAL
 RESCUE LEAGUE
 3200 N MILITARY TRAIL
 BUILDING PLAN REVIEW
 PERMIT: 07060707
 ADD: 3200 N MILITARY TRAIL
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET G-001 THE CIVIL ENGINEER CIVIL DESIGN, INC. IS
 MISSING THEIR CERTIFICATE OF AUTHORIZATION. 471.023
 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK
 FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO
 EACH SHEET.THIS MAY BE ADDED BY HAND.
  
 4) SHEET G-001 THE LANDSCAPE ARCHITECT ALSO IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION. ) 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE NUMBER TO
 EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 5) SHEET G-001 SITE BUILDING DATA INDICATES THIS
 PROJECT IS LOCATED IN A **FIRE ZONE**,
 THERE ARE NO LONGER FIRE ZONES IN THE BUILDING CODE.
  
 6) PLEASE PROVIDE ORIGINAL SIGNATURE SOILS REPORTS. FBC
 1802.2.1 QUESTIONABLE SOILS, WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 7) FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTORPROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 XX - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION -
 ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE DESIGN IS
 BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 XX- BUILDINGS OVER 20,000 SQ FT IN AREA( 35,772 SQ
 FT)
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 XX- BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 8) THIS PROJECT IS LOCATED IN A A-8FLOOD ZONE WITH
 THE FINISH FLOOR ELEVATION OF 16.5? MINIMUM FINISH
 FLOOR ELEVATION AND ANY MECHANICAL EQUIPMENT ON THE
 EXTERIOR OF THE BUILDING BE ABOVE THIS SAME ELEVATION.
 PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW
 CONSTRUCTION BEFORE A CERTIFICATE OF OCCUPANCY WILL BE
 ISSUED.
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENTPROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED
 TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 10) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 11) LS-001 THE LIFE SAFETY PLAN FAILS TO IDENTIFYROOM
 TYPES, OCCUPANT LOADS FOR ROOMS,
 OCCUPANT LOADS FOR DOORWAYS. PLEASE SEE TABLE 1004.1&
 1005.1.
  
 10) SHEET C-3.1 THE COVERED ENTRY INDICATES THE DRIVE
 TO BE AT 20.80? WHEREAS THE INTERIOR FINISH FLOOR OF
 THE LOBBY IS 21.00?. PLEASE PROVIDE A SECTION THROUGH
 THIS AREA TO PROVIDE THE FOLLOWING:
 10A) COMPLIANCE WITH 11-4.6.5 VERTICAL CLEARANCE FOR
 PASSENGER LOADING ZONE.
 10B) PROVIDE A CURB DETAIL INDICATING COMPLIANCE WITH
 11-4.6.6 PASSENGER LOADING ZONE.
 10C) DEPENDING ON THE 2? CHANGE IN ELEVATION FROM THE
 PASSENGER LOADING ZONE TO FINISH FLOOR ELEVATIONS CURB
 CUTS 11-4.7.
  
 11) PLEASE SEE A-100 AND A-101 THE MAIN LOBBY (101) &
 SURRENDER LOBBY (180) PROVIDE DETAILS SHOWING
 COMPLIANCE WITH 11-7.2(1) SERVICE COUNTERS WITH
 ELEVATIONS OF 36?.SEE DETAILS ON SHEET A-713 DETAILS
 103-105.
  
 12) COMMENT DELETED.
  
 13)SHEET A-100 & A-103 INDICATES 2 SHOWERS (153 & 155)
 BOTH ARE TO BE HANDICAPPED ACCESSIBLE. SHOW COMPLIANCE
 WITH 11-4.21(1-8).
  
 14) SHEET A-101 DOOR 102B IS MISSING THE 18? ON THE
 PULL SIDE AT LATCH.11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN
 THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 15) THE LIFE SAFETY PLAN INDICATES THERE ARE TWO (2)
 AREAS WITH 2HR FIRE RATED WALLS:
 15A)(1) SALLY PORT, SHEET A-100 & A-103 BOTH ARE
 MISSING THE WALL TAGS INDICATING THEY ARE 2HR FIRE
 RATED WALLS. SEE TABLE 303.3.2. BETWEEN S-2 CLOSED
 GARAGE AND BUSINESS OCCUPANCY. PLEASE PROVIDE THE
 EQUIVALENT THICKNESS FOR CONCRETE BLOCK FROM THE
 MANUFACTURER INDICATING THE EQUIVALENT THICKNESS
 721.3.2.
 15A) (2) SALLY PORT THERE APPEARS TO BE 6 VEHICLES IN
 THE GARAGE AND 2 LARGE OBJECTS, NOT CLEAR AS TO WHAT
 THIS IS POSSIBLY STORAGE?
  
  
 15B) THE LIFE SAFETY PLAN ALSO INDICATES AROUND THE
 KENNEL OCCUPANCY WHEREAS NEITHER OF THE SHEETS A-100 OR
 A-101 PROVIDE ANY WALL TAGS INDICATING A 2HR
 SEPARATION. PLEASE PROVIDE THE EQUIVALENT THICKNESS FOR
 CONCRETE BLOCK FROM THE MANUFACTURER INDICATING THE
 EQUIVALENT THICKNESS 721.3.2.
  
 15C) THE LIFE SAFETY SHEET AS WELL AS SHEET A-100 AND
 A-104 DO NOT INDICATE A 2HR FIRE RATING ON THE MASONRY
 WALLTABLE 303.3.2 INDICATES BETWEEN A BUSINESS AND
 R-2 OCCUPANCY WALLS ARE TO BE RATED. THE DOOR SCHEDULE
 ALSO NEEDS CORRECTING IN THIS MANNER , SEE OPENING
 PROTECTIVE. TABLE 715.3
  
 16) SHEET A-100 ROOM 166 INDICATES THIS IS A FREEZER
 BUT THERE IS A PORTION OF THE WALL THAT IS MISSING, IS
 THIS A DOORWAY, NEED MORE INFORMATION. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 17) ROOM 142 INDICATES THIS IS TO BE USED FOR X-RAYS
 PLEASE PROVIDE COMPLIANCE WITH:
 435.5.1 SHIELDING.
 435.5.2 X-RAY FILM PROCESSING FACILITIES.
  
 18A) SHEET A-105 MEZZANINE # 1THE PLANS INDICATE THIS
 TO HAVE A PULL DOWN STAIRWAY LEADING FROM ROOM 133 OR
 THE TECH AREA. THIS MEZZANINE HAS AN OCCUPANT LOAD OF
 THREE(3).
 505.3 EGRESS WILL ALLOW FOR A SINGLE MEANS OF EGRESS
 BUT THE CODE DOESN?T INDICATE THAT A PULL DOWN STAIRWAY
 MEETS EGRESS REQUIREMENTS. THE SECOND ISSUE WITH THE
 PULL DOWN STAIR IT BLOCKS THE CORRIDOR BELOW.
  
 18B) THE FLOOR HATCH WILL ALSO NEED A GUARD AROUND WHAT
 EVER ACCESS WILL BE CREATED IN THE FLOOR. 1012.2
 HEIGHT. GUARDS SHALL FORM A PROTECTIVE BARRIER NOT LESS
 THAN 42 INCHES
 1012.3 EXCEPTION(2)AT ELEVATED WALKING SURFACES FOR
 ACCESS TO AND USE OF ELECTRICAL, MECHANICAL OR PLUMBING
 SYSTEMS OR EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE
 OF SOLID MATERIALS SUCH THAT A SPHERE WITH A DIAMETER
 OF 21 INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING.
  
  
 19A) SHEET A-105 MEZZANINE # 2 INDICATES THE USE OF A
 VERTICAL SHIPS LADDER. PLEASE SEE MEZZANINE MEANS OF
 EGRESS, THIS MEZZANINE IS LARGER AND AN OCCUPANT LOAD
 OF 8.
 505.3 EGRESS.
 505.3EACH OCCUPANT OF A MEZZANINE SHALL HAVE ACCESS TO
 AT LEAST TWO INDEPENDENT MEANS OF EGRESS WHERE THE
 COMMON PATH OF EGRESS TRAVEL EXCEEDS THE LIMITATIONS OF
 SECTION 1013.3 . WHERE A STAIRWAY PROVIDES A MEANS OF
 EXIT ACCESS FROM A MEZZANINE, THE MAXIMUM TRAVEL
 DISTANCE INCLUDES THE DISTANCE TRAVELED ON THE STAIRWAY
 MEASURED IN THE PLANE OF THE TREAD NOSING.
  
 19B) PLANS INDICATE THE GUARD RAIL TO BE 34? TALL,
 PLEASE SEE. 1012.2 HEIGHT. GUARDS SHALL FORM A
 PROTECTIVE BARRIER NOT LESS THAN 42 INCHES
 1012.3 EXCEPTION(2)AT ELEVATED WALKING SURFACES FOR
 ACCESS TO AND USE OF ELECTRICAL, MECHANICAL OR PLUMBING
 SYSTEMS OR EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE
 OF SOLID MATERIALS SUCH THAT A SPHERE WITH A DIAMETER
 OF 21 INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING.
  
 20) SHEET A-200 IS THE REFLECTED CEILING PLAN, THE PLAN
 IS MISSING EXIT LIGHTS, AND DIRECTIONAL, PLEASE UPDATE
 PLAN SECTION 1006. 1006.1.1
 ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
  
 21) SHEET A-300 ROOF DRAINAGE:
 21A) THE GARAGE ROOF INDICATES THAT THERE WILL BE
 THROUGH THE WALL SCUPPERS AND COLLECTORS AND DOWN
 SPOUTS (R15) THE SAME MARKINGS ARE USED FOR THE
 EMERGENCY OVERFLOW SCUPPERS. THE EMERGENCY OVERFLOW
 SCUPPERS ARE NOT TO BE AT THE SAME HEIGHT AS THE
 SCUPPERS.
 1503.4.3 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 21B) PLEASE PROVIDE A DETAIL INDICATING THE FOLLOWING:
 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 21C) SHEET A-300 INDICATES R9 & R11 EMERGENCY OVERFLOWS
 BUT THE WIDTH IS NOT PROVIDED, AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, PLUMBING. 1503.4.3.PLEASE PROVIDE SIZES OF THE
 OVERFLOW SCUPPERS.
  
 22)1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE PROVISIONS
 OF THE SMALL MISSILE TEST.
  
 23) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 24) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL AREREQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 25) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A)FIXED FRAME, STOREFRONT WINDOWS
 B) HORIZONTAL OR PASS THRU WINDOWS
 C) MULLIONS HORIZONTAL OR VERTICAL
 D) LOUVERS
 E) GLAZED DOORS
 F) HOLLOW EXTERIOR METAL DOORS SINGLE AND PAIRS
 G) OVERHEAD DOORS
 H) SKYLIGHTS
 I) ROOFING ASSEMBLIES FLAT ROOFS BUILT UP OR MODIFIED,
 TILE ROOF AND UNDERLAYMENTS
 K) PRE-ENGINEERED A/C STANDS
  
 26) THESE ARE THE MOST OFTEN REASONS FOR ROOFING REPORT
 FAILURES, THIS ROOF IS MISSING OR NOT INCOMPLIANCE
 WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE INSTALLED.
  
 ___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 ___ .
  
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT
 OR REGISTERED ROOF CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 27) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-11-24 Cont ID  
Sent By dpalmer Date 2009-11-24 Time 11:23 Rev Time 0.00
Received By dpalmer Date 2009-11-24 Time 11:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2009-10-10 Cont ID  
Sent By dpalmer Date 2009-10-10 Time 09:59 Rev Time 0.00
Received By dpalmer Date 2009-10-10 Time 09:59 Sent To  
Notes
2009-10-10 10:00:48 
  
 ** DENIED REVIEW **
 **ORIGINALLY SUBMITTED 8/13 AND PLACED ON HOLD FOR
 ELECTRICAL REVIEW AS NEW REVISED SHEETS NEEDED TO BE
 INSERTED INTO SETS BEFORE REVIEW.
 OTHER REVISED TRADE SHEETS WERE ALSO INCLUDED WHEN
 SHEETS WERE INSERTED WHICH ARE DATED AFTER ORIGINAL
 SUBMITTED DATE. THERE WERE ALSO NEW REVISED PLUMBING
 SHEETS INSERTED AFTER THE PLUMBING REVIEW WAS DONE. NEW
 SHEETS ALSO INSERTED THIS WEEK FOR ZONING.
 ORIGINALLY SUBMITTED AS 28 REVISED SHEETS THERE IS NOW
 A TOTAL OF 47 REVISED SHEETS IN EACH SET. INCLUDING
 FIVE REVISED PLUMBING REVISED SHEETS. ADDITIONAL FEE
 FOR REVISED SHEETS WILL BE DUE.
  
 1) NOTE: AS NOTED PREVIOUSLY. THE SAME ENERGY
 CALCULATIONS AS PREVIOUSLY SUBMITTED ARE NOT REVISED
 AND ARE THE SAME AS SUBMITTED.
  
 ** PREVIOUS NOTES**
 ENERGY CALCULATIONS NOT STAMPED FOR ELECTRIC. AS STATED
 ON PREVIOUS REVIEWS. ALL SYSTEMS AND COMPONENTS IN THE
 BUILDING AND ON SAID PLANS NEED TO COORDINATE WITH THE
 INPUT DATA REPORT. AN EXAMPLE IS TAKING A CREDIT FOR
 ALL ROOMS AND SPACES IN BUILDING TO CONTAIN * CARPET
 AND RUBBER PADDING*. THE FACT THERE IS NUMEROUS AREAS
 AND LOCATIONS WITHIN BUILDING WHICH DO NOT CONTAIN THIS
 TYPE OF FLOORING. THERE ARE ALSO ROOMS AND OTHER AREAS
 SUCH AS ELECTRICAL ROOMS, MECHANICAL ROOMS, SURGERY
 ROOMS, STORAGE ROOMS ETC WHICH WILL NOT HAVE ANY CARPET
 AND RUBBER PADDING.
 SEE COMMENTS FROM OTHER TRADES. SEE FBC CHAPTER 13 AS
 THE SUBMITTED CALCULATIONS DO NOT MEET THE MINIMUM OF
 THE FLORIDA BUILDING CODE IN CHAPTER 13.
  
 2) NOTE: REVISED PLANS SUBMITTED REMOVING PHASE TWO
 SCOPE OF WORK HOWEVER REVISED CIRCUITING, LOADS AND
 PANEL SCHEDULES WERE NOT SUBMITTED OR REVISED FOR AREAS
 WHICH ARE IN THE PHASE ONE SCOPE OF WORK. THERE ARE
 SEVERAL AREAS WHICH OVER LAP FOR THE ABOVE CIRCUITING
 ETC.
 PLEASE SUBMIT REVISED PANEL SCHEDULES PER 408.4 REVISED
 PANEL SCHEDULES WERE NOT SUBMITTED AS PART OF PHASE TWO
 SCOPE OF WORK.
 PLEASE REVISE CIRCUITING AND LOADS PER NEC 220,
 220.12,220.14, 220.42 ETC
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-06-29 Cont ID  
Sent By dpalmer Date 2009-06-29 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2009-06-29 Time 14:29 Sent To  
Notes
2009-06-29 14:30:01** DENIED REVIEW **
  
 1) NOTE: ENERGY CALCULATIONS NOT STAMPED FOR ELECTRIC.
 AS STATED ON PREVIOUS REVIEWS. ALL SYSTEMS AND
 COMPONENTS IN THE BUILDING AND ON SAID PLANS NEED TO
 COORDINATE WITH THE INPUT DATA REPORT. AN EXAMPLE IS
 TAKING A CREDIT FOR ALL ROOMS AND SPACES IN BUILDING TO
 CONTAIN * CARPET AND RUBBER PADDING*. THE FACT THERE IS
 NUMEROUS AREAS AND LOCATIONS WITHIN BUILDING WHICH DO
 NOT CONTAIN THIS TYPE OF FLOORING. THERE ARE ALSO ROOMS
 AND OTHER AREAS SUCH AS ELECTRICAL ROOMS, MECHANICAL
 ROOMS, SURGERY ROOMS, STORAGE ROOMS ETC WHICH WILL NOT
 HAVE ANY CARPET AND RUBBER PADDING.
 SEE COMMENTS FROM OTHER TRADES. SEE FBC CHAPTER 13 AS
 THE SUBMITTED CALCULATIONS DO NOT MEET THE MINIMUM OF
 THE FLORIDA BUILDING CODE IN CHAPTER 13.
  
 2) NOTE: NO OTHER ELECTRICAL REVISIONS SUBMITTED TO
 REVIEW SAID CALCULATIONS AND COORDINATE WITH PLANS. THE
 NEW REVISED CALCULATIONS DO NOT COORDINATE WITH PLANS
 ON FILE.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-01-13 Cont ID  
Sent By dpalmer Date 2009-01-13 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2009-01-13 Time 16:44 Sent To  
Notes
2009-01-13 16:45:07** DENIED REVIEW OF REVISIONS**
  
 ** REVISIONS SUBMITTED 12/11/2008
  
 ELECTRICAL PLANS ARE OK HOWEVER REVIEW TO REMAIN IN
 FAILED STATUS DUE TO ENERGY CALCULATIONS.
  
  
  
  
  
 1) NOTE: PLEASE BE SURE ALL INFORMATION REGARDING
 LIGHTING ON PLANS IS PLACED INTO THE INPUT DATA REPORT.
 REVISED CALCULATIONS WERE SUBMITTED HOWEVER INFORMATION
 ON SOME ITEMS HAS NOT YET BEEN CONFIRMED ON PLANS.
 AN EXAMPLE OF THIS IS THE LOW VOLTAGE FIXTURE *W* WHICH
 NOTES A LOW VOLTAGE REMOTE TRANSFORMER AS NEEDED.
 HOWEVER PLEASE SEE 13-415.2.ABC.1.1,.1.2 AS THE VA
 REQUIRED TO BE PART OF THE IDR IS TO BASED ON THE VA
 RATING OF THAT REMOTE TRANSFORMER. IF THESE ARE NOT YET
 LISTED THEN HOW CAN THE CALCULATIONS BE ACCURATE?
 PLEASE BE SURE TO GO OVER *ALL* FIXTURES ON PLANS AND
 BE SURE THESE ARE ALL IN THE IDR WITH THE LATEST
 REVISIONS OF FIXTURES. THIS WOULD INCLUDE LIGHTING ON
 FANS. THE FIXTURES WILL HAVE A RATING WHICH IS WHAT THE
 IDR IS REQUIRED TO SHOW.
 THE FIXTURE RATING IS THE LOAD USED NOT THE BULB
 RATING.
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-09-08 Cont ID  
Sent By dpalmer Date 2008-09-08 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2008-09-08 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-08-27 Cont ID  
Sent By dpalmer Date 2008-08-27 Time 14:03 Rev Time 0.00
Received By dpalmer Date 2008-08-27 Time 14:03 Sent To  
Notes
2008-08-27 14:03:20 
 ** DENIED4TH REVIEW **
  
  
  
  
 1) NOTE:ENERGY CALCULATIONS DO NOT COORDINATE WITH
 THE PLANS. NOT ALL EXTERIOR LIGHTS ON THE IDR AND NOT
 ALL INTERIOR LIGHTS ON THE IDR COORDINATE WITH PLANS.
 LIGHTING ON MEZZANINE LEVEL IS MISSING MANY FIXTURES.
 LIGHTS FOR *H* FIXTURES ARE MISSING SOME.
 SPOKE TO ENGINEER OF RECORD AND MECHANICAL DESIGNER AND
 WILL CORRECT CALCULATIONS. 13-415.2.ABC.1.1,.1.2,.1.3.
  
 2) NOTE: PLEASE SEE THIRD SET IS MISSING THE SIGNATURE,
 DATE AND SEAL FROM SHEET E-002.
  
 3) NOTE: STILL NEED LETTERING OF UNDERSTANDING FROM
 OWNER THAT PROJECT CO WILL BE PLACED ON HOLD UNTIL FEE
 BALANCE OF 4X FEE IS PAID IN FULL AS REQUIRED BY FS
 553.80(2)(B).
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-12 Cont ID  
Sent By dpalmer Date 2008-06-12 Time 12:31 Rev Time 0.00
Received By dpalmer Date 2008-06-12 Time 12:31 Sent To PC
Notes
2008-06-12 12:32:13** DENIED 3RD REVIEW **
  
 ** PLEASE SEE THERE ARE STILL ITEMS ON PREVIOUS REVIEWS
 WHICH ARE STILL IN NEED OF ADDRESSING THEREFORE SOME
 COMMENTS ARE REPEATED FROM INITIAL REVIEW AS WELL AS
 THE SECOND REVIEW.
  
 ** PLEASE ALSO SEE THERE ARE NEW COMMENTS DUE TO SOME
 ITEMS ONLY NOW SUBMITTED FOR FIRST REVIEW.
  
 1) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEWS
 COMPLIANCE WITH FLORIDA BUILDING CODE AND CHAPTER 13
 FOR ENERGY CODE COMPLIANCE.
 PLEASE SEE ONCE AGAIN THE SUBMITTED ENERGY CALCULATIONS
 ARE REQUIRED TO COORDINATE WITH PLANS. ALL SYSTEMS ON
 PLANS SHALL BE PLACED INTO THE INPUT DATA REPORT. THIS
 IS REQUIRED OF ALL LIGHTING ON PLANS AS WELL AS OTHER
 SYSTEMS SUCH AS BUILDING COMPONENTS. THE FOLLOWING
 ITEMS WILL ONCE AGAIN BE NOTED. THE INPUT DATA REPORT
 WILL BE NOTED AS IDR.
 PLEASE SEE 13-400.3.A, 13-415.1.A, 13-415.1.AB,
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. ALL LIGHTING
 ON PLANS SHALL COORDINATE WITH THE IDR FOR WATTAGE OF
 FIXTURES, THE TYPES OF FIXTURES, THE METHOD OF CONTROLS
 AND THE NUMBER OF FIXTURES. ON THE PREVIOUS REVIEW
 EXAMPLES WERE GIVEN AS A BENEFIT TO HELP LOCATE ALL
 FIXTURES WHICH ARE CLEARLY SHOWN ON PLANS HOWEVER ARE
 NOT BEING SHOWN IN THE CALCULATIONS.
 ONCE AGAIN THIS REVIEWER WILL GIVE SOME EXAMPLES AND
 CAN NOT EXPRESS ENOUGH THE FOLLOWING IS NOT AN
 EXHAUSTED LIST NOR IS IT ALL ITEMS WHICH DO NOT
 COORDINATE.
  
 FOR EXAMPLE:
 PLEASE SEE EXTERIOR LIGHTING ON THE IDR WHICH DOES NOT
 INCLUDE ANY 400W OR 35W FIXTURES.THESE ARE ONLY TWO
 FIXTURES ON EXTERIOR WHICH ARE BEING NOTED. HOW IS THIS
 POSSIBLE WHEN THE PLANS CLEARLY SHOW TYPE *S-1* AND *L*
 ??HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW
 DOZENS OF MORE FIXTURES THAN WHAT IS SHOWN IN THE INPUT
 DATA REPORT?
 THESE TWO FIXTURES ALONE WERE SPECIFICALLY GIVEN AS A
 BENEFIT ON PREVIOUS REVIEW ALONG WITH OTHER YET THESE
 ARE STILL NOT IN THE ENERGY CALCULATIONS. THERE ARE
 OTHER FIXTURES ON PLANS WHICH ALSO DO NOT COORDINATE
 WITH THE NUMBER OF FIXTURES AND THE WATTAGE.
  
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR LIGHTING ON PLANS WHICH ARE ALL
 REQUIRED TO COORDINATE WITH THE IDR OF THE SUBMITTED
 ENERGY CALCULATIONS. PLEASE SEE ONE ZONE SUCH AS THE
 *SURRENDER LOBBY* DOES NOT COORDINATE WITH ALL LIGHTING
 ON PLANS. PLEASE SEE THE NUMBER OF FIXTURES AND WATTAGE
 OF THESE FIXTURES IN THIS AREA IS GREATER THAN THE
 NUMBER OF FIXTURES SHOWN ON THE IDR.
  
 FOR EXAMPLE:
 PLEASE SEE ALL METHOD OF CONTROLS IS REQUIRED TO BE
 AUTOMATIC PER CODE. HOW CAN MANUAL ON/OFF CONTROLS
 STILL BE NOTED IN THE IDR?
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR SHOWS *HOSPITAL* AS THE ALLOWANCE
 FOR LIGHTING HOWEVER BASED ON THE BUILDING CODE AND
 DEFINITIONS IN NFPA-70 AS WELL AS NFPA-101 THIS CAN NOT
 BE CLASSIFIED AS A HOSPITAL. PLEASE SEE THE COVER SHEET
 FOR THE ENERGY CALCULATIONS DOES NOT SHOW HOSPITAL, IT
 SHOW OFFICE. PLEASE ADJUST THE IDR FOR INTERIOR
 LIGHTING ALLOWANCES IN THESE AREAS.
  
 ** AS NOTED ON PREVIOUS REVIEWS, PLEASE BE SURE ALL
 ITEMS ON PLANS ARE PLACED INTO THE IDR/ENERGY
 CALCULATIONS.
 ** SAME AS PREVIOUS REVIEWS.
  
 2) NOTE: PLEASE SEE SOME LIGHTING CONTROLS DO NOT YET
 COMPLY WITH CHAPTER 13. PLEASE SEE MECHANICAL ROOM ON
 FIRST FLOOR WHERE *SHIPS* LADDER IS LOCATED. THIS ROOM
 SHOWS A TWIST TIME YET THIS ROOM ON SHEET E-104 ALSO
 SHOWS A 3-WAY SWITCH AND OCCUPANCY SENSOR. PLEASE
 EXPLAIN HOW THIS WILL OPERATE. PLEASE SEE THE FOLLOWING
 COMMENT WITH RESPECT TO THE PROPOSED TIMERS. PREVIOUS
 REVIEW ALSO REQUESTED THE MAXIMUM TIMES TO BE NOTED ON
 PLANS. THE RESPONSE MENTIONS TO SEE NOTE ADDED TO
 PLANS. PLEASE SEE THE NOTE WAS ADDED HOWEVER THE CODE
 SECTION NOTED NEEDS TO BE ADJUSTED. IT SHOULD BE
 13-415.1.ABC.1.1.( PLEASE ADJUST FOR POSSIBLE
 MISPRINT)
 13-415.1.ABC.1.1, .1.2.
 **PREVIOUS COMMENT AND NEW BASED ON DESIGN CHANGES.
  
 3) NOTE: PLEASE SEE FBC 11-4.27.4 AS TWIST TIMERS AS
 NOTED ON SYMBOL LEGEND MAY NOT BE USED AS THEY DO NOT
 MEET ADA MINIMUM REQUIREMENTS.
 **NEW COMMENT.
  
 4) NOTE: THE MANUFACTURES SPECS/CUT SHEETS ARE ONLY NOW
 BEING SUBMITTED FOR THE FIRST TIME FOR REVIEW. RESPONSE
 AND PLANS NOW SHOW THE OVER CURRENT PROTECTION FROM THE
 GENERATOR BEING REMOVED. THIS IS OK HOWEVER WHEN DOING
 SO THIS NOW REQUIRES THE CONDUCTORS FROM THE GENERATOR
 TO THE FIRST MEANS OF OVER CURRENT PROTECTION TO MEET
 445.13. THIS SECTION OF THE CODE REQUIRES THE
 CONDUCTORS TO BE SIZE AT A MINIMUM OF 115%. PLEASE BE
 AWARE OF THE TEMPERATURE RISE ON SPECS AS THE OUTPUT
 AMPERAGE IS GREATLY AFFECTED. EVEN IF THE OUTPUT IS THE
 LOWER OF THE FOUR SHOWN THE CONDUCTORS AS LISTED ARE
 STILL NOT LARGE ENOUGH. PLEASE KNOW AS THE TEMP RISE IS
 TYPICALLY THE 150C, OR 130C AS SHOWN THE OUTPUT
 AMPERAGE IS 1504 AMPS. THE CONDUCTORS PER 310.16,
 110.14 ARE RATED FOR 1550AMPS. THE 115% RATING FOR
 MINIMUM SHALL BE 1729.6, OR RATHER 1730AMPS MINIMUM.
 PLEASE SEE 240.4C, 310.16 AND 110.14. THE CONDUCTORS ON
 DEVICES RATED OVER 800AMPS SHALL MEET OR EXCEED THIS
 RATING. PLEASE ADJUST CONDUCTORS OR PLACE OVER CURRENT
 PROTECTION BACK ON GENERATOR.
 ** NEW COMMENT BASED ON CHANGES MADE TO DESIGN.
  
 5) NOTE: THE PREVIOUS REVIEWS REQUESTED THE SPECS FOR
 THE ATS. THESE WERE SUBMITTED AND THE GENERAL SHEET
 INDICATES SWITCHES RATED UP TO 4000AMPS.HOWEVER THE
 MANUFACTURES SPECS INSIDE THE PACKAGE DOES NOT INDICATE
 ANY 1600AMP ATS UNITS AS SHOWN ON PLANS. THEY LIST
 1200AMP BUT NOT THE OTHER. PLEASE PROVIDE COORDINATING
 MANUFACTURE SPECS. THIS MAY AFFECT AIC WITHSTAND
 RATINGS ETC.
 90.7, 110.3.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
 **PREVIOUS COMMENTS AND NEW COMMENT.
  
 6) NOTE: PLEASE KNOW THE RESPONSE FOR SLAB ELEVATION
 DOES NOT CLEARLY GIVE ANY INFORMATION ON FLOOD ZONE.
 PLEASE KNOW THIS CAN BE A PROVISO AS THIS IS STRICTLY
 AN OPTIONAL STAND-BY SYSTEM HOWEVER THE EQUIPMENT IS
 STILL REQUIRED TO BE MOUNTED A MINIMUM OF 6INCHES ABOVE
 THE FLOOD LEVEL. A CERTIFICATION BY A LICENSED
 SURVEYOR, ENGINEER OR ARCHITECT WILL BE REQUIRED FOR
 ELEVATION VERIFICATION AND CERTIFICATION OF THE SLAB
 ONCE INSTALLED.
 ** THIS WAS ON PREVIOUS REVIEW AND AS NOTED CAN BE DONE
 AS A *PROVISO*.
  
 7) NOTE: PLEASE SEE THE LIGHTING SHOWN THE UPPER AREA
 OF THE FIRST FLOOR MECHANICAL ROOM ON SHEET E-104 IS
 NOT THE SAME AS THE LIGHTING IN THE SAME ROOM AS SHOWN
 ON E-103.
 PLEASE COORDINATE.
 FBC 106.1.2
 ** NEW COMMENT AS ROOMS ARE NOW LABELED.
  
 8) NOTE: PLEASE KNOW AS THE EGRESS FROM THE SECOND
 LEVEL MECHANICAL ROOM IS NOW CLEAR AS DISCUSSED WITH
 OTHER REVIEWERS IT APPEARS THE EGRESS FROM MECHANICAL
 ROOM #2 IS OUTSIDE AND ACROSS THE ROOF BACK INTO
 MECHANICAL ROOM #1 AND THEN DOWN LADDER. PLEASE KNOW
 EGRESS LIGHTING FOR NORMAL AND EMERGENCY CONDITIONS
 SHALL BE PROVIDED AT THIS ROOF AREA BETWEEN THE DOORS
 ON THE SECOND ROOM BACK INTO THE FIRST ROOM. NFPA-101
 7.8, 7.9.
 ** NEW COMMENT
  
 9) NOTE: PLEASE PLACE NOTE ON PLANS FOR BONDING OF
 METAL FRAMING PER 2704.1. THIS WAS CONFIRMED RECENTLY
 ON A STATE LEVEL THIS NOTE SHOULD BE ON PLANS.
 ** NEW COMMENT
  
 10) NOTE: THE PREVIOUS REVIEW REQUESTED TO SHOW
 COMPLIANCE FOR SOUND LEVELS OF FIRE ALARM HORN DEVICES
 PER FBC 11-4.28.2. RESPONSE MENTIONS TO SEE NOTE ADDED
 TO FA RISER. THE NOTE QUOTES THE SAME CODE SECTION AS
 GIVEN IN REVIEW. THE CODE MAY NOT BE QUOTED IN GENERAL
 IN LIEU OF GIVING SPECIFIC DETAILS. THE LEVEL(S) NEED
 TO BE SHOWN OR NOTED AS REQUIRED IN THE SECTION OF THE
 CODE. THE NOTE ALSO STATES LEVELS ARE REQUIRED DURING
 TESTING. THE LEVELS OF HORN DEVICES DURING INITIAL
 TESTING WOULD ACTUALLY BE LOUDER THAN LEVELS ACTUALLY
 HEARD DURING BUILDING OCCUPANCY. THE CODE REQUIRES THE
 LEVELS TO BE ABOVE THE OTHER MAXIMUM SOUND LEVELS IN
 ANY ONE AREA ETC. PLEASE SEE THE FOLLOWING TEXT IS
 EXTRACTED FROM THE CODE FOR CLARITY OF COMMENTS SO THE
 NOTES, DEVICES AND SOUND LEVELS OF DEVICES CAN BE
 ADJUSTED, SHOWN OR NOTED.
 **IF PROVIDED, AUDIBLE EMERGENCY ALARMS SHALL PRODUCE A
 SOUND THAT EXCEEDS THE PREVAILING EQUIVALENT SOUND
 LEVEL IN THE ROOM OR SPACE BY AT LEAST 15 DBA OR
 EXCEEDS ANY MAXIMUM SOUND LEVEL WITH A DURATION OF 60
 SECONDS BY 5 DBA, WHICHEVER IS LOUDER. SOUND LEVELS FOR
 ALARM SIGNALS SHALL NOT EXCEED 120 DBA.**
  
 11) NOTE: THE PREVIOUS REVIEW GAVE SEVERAL NOTES WITH
 RESPECT TO CIRCUITING AND EVEN GAVE SOME EXAMPLES.
 PLEASE SEE 210.52B1 AS THE MINIMUM OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIRED ON PLANS. THESE SHALL
 NOT CONTAIN ANY OTHER ITEMS ON THESE CIRCUITS WITH THE
 EXCEPTION OF THE ITEMS LISTED IN THE 210.52B1. LIGHTING
 IS NOT PERMITTED TO BE ON THE SMALL APPLIANCE
 CIRCUITS.
 PLEASE SEE SHEET E-102 AS THE LIGHTING CIRCUITS SHOWN
 ARE CIRCUITS P4-1, P4-3 AND P4-5. PLEASE SEE THE PANEL
 SCHEDULE ON SHEET WHICH SHOWS ONLY TWO OF THESE
 LIGHTING CIRCUITS. CIRCUIT SHOWN AS P4-5 IS ACTUALLY
 *BLANK* ON SCHEDULE AS THIS IS NOTED AS *SPARE*. PLEASE
 ALSO SEE SHEET E-202 AS THIS CLEARLY SHOWS THE LIGHTING
 STILL BEING CIRCUITED TO THE SMALL APPLIANCE CIRCUITS
 AS THE SMALL APPLIANCE CIRCUITS ON THIS SHEET E-202 IS
 SHOWING P4-1 AND P4-3 AS THE SMALL APPLIANCE CIRCUITS.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE CODE WHICH INDICATES WHICH ITEMS MAY ON THE SAME
 CIRCUITS AS THE SMALL APPLIANCE CIRCUITS.
 **(B) SMALL APPLIANCES
 (1) RECEPTACLE OUTLETS SERVED IN THE KITCHEN, PANTRY,
 BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF A
 DWELLING UNIT, THE TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS
 COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR
 REFRIGERATION EQUIPMENT.**
 THIS CAN BE FOR RECEPTACLE OUTLETS ONLY IN THESE AREAS,
 NO OTHER OUTLETS ARE PERMITTED. PLEASE ADJUST.
 ** PREVIOUS REVIEWS.
  
 12) NOTE: THE PREVIOUS REVIEW GAVE SEVERAL NOTES WITH
 RESPECT TO CIRCUITING AND EVEN GAVE SOME EXAMPLES.
 PLEASE SEE THE PREVIOUS REVIEWS WITH RESPECT TO
 REQUIRED ARC FAULT PROTECTION REQUIRED ON ALL OUTLETS
 IN BEDROOMS PER 210.12. THE PREVIOUS PANEL SCHEDULE
 ALONG WITH THE CURRENT REVISED PANEL SCHEDULE SUBMITTED
 CONTAINS TWO ASTERISK ( **) AT THE TOP OF THE PANEL
 SCHEDULE WHICH STATES THE CIRCUITS NOTED WITH THE TWO
 ASTERISK (**) ARE TO CONTAIN AFCI BREAKERS/ARC FAULT
 PROTECTION. PLEASE SEE THE PREVIOUS REVIEW GAVE
 SPECIFIC NOTE THAT NOT ALL CIRCUITS WHICH REQUIRED AFCI
 PROTECTION SHOWED THE ASTERISK (**). THE RESPONSE
 MENTIONS THE TWO CIRCUITS WHICH REQUIRE ARC FAULT
 PROTECTION PER THE 2005 NEC DOES SHOW THE PROTECTION.
 ** PLEASE SEE THE 2002 AS WELL AS THE 2005 NEC REQUIRES
 ARC FAULT PROTECTION FOR *ALL OUTLETS* INSIDE THE
 SLEEPING ROOMS. THIS PROTECTION IS NOT FOR RECEPTACLES
 ONLY. THIS IS FOR RECEPTACLES, LIGHTS, SMOKE ALARMS
 (WHEN 120V) , FANS ETC.
 PLEASE SEE THE PLANS STILL DO NOT SHOW ANY PROTECTION
 FOR THE OTHER OUTLETS IN THESE ROOMS. THE CIRCUITS
 WHICH INDICATE PROTECTION STILL ONLY SHOW THIS FOR
 *RECEPTACLES*. PLEASE SEE CIRCUITS NOTED AS P4-1 AND
 P4-5 DO NOT INDICATE PROTECTION.
 PLEASE SEE E-102 AND E-303. AS NOTED ABOVE IN NOTE #11
 CIRCUITS ALSO DO NOT CORRELATE.
 PLEASE COORDINATE PLANS, PLEASE ADJUST FOR CODE
 COMPLIANCE AND PLEASE LIST ALL REQUIRED BRANCH CIRCUITS
 WITH AFCI PROTECTION AS REQUIRED PER 2005 NEC.
 ** PREVIOUS REVIEWS
  
 13) NOTE: DINING ROOM WALL APPEARS TO REQUIRE A SECOND
 RECEPTACLE TO MEET WALL SPACING REQUIREMENTS PER
 210.52. WALL SPACE IS UNCLEAR AND IS BEING NOTED AS THE
 INDENTION IN WALL MAY OR MAY NOT BE CABINETS. AS THIS
 IS DOES NOT SHOW CABINETS AND APPEARS TO BE WALL,
 PLEASE ADD RECEPTACLE AS TOTAL LENGTH OF WALL FROM
 DOORWAY OF LAUNDRY ROOM TO DOORWAY AT FRONT DOOR
 APPEARS TO BE 12FT OR MORE.
 ** NEW COMMENT.
  
 14) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEET
 SHOWING THE 42CIRCUIT PANELS AS 100AMP RATED. AS NOTED
 PREVIOUSLY PANELS AT 100AMP RATED AND 60AMP RATED ARE
 NOT KNOWN TO BE 42CIRCUIT. PLEASE SUBMIT SPEC/CUT
 SHEET. A SEARCH OF A FEW OF THE STANDARD MANUFACTURE
 DID NOT PRODUCE ANY LISTED 42CIRCUIT PANEL BOARDS WHICH
 WERE ONLY 100AMP RATED.
 NEC 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 15) NOTE: PLEASE PLACE NOTE ON PLANS FOR COLOR CODING
 OF CONDUCTORS. THE SPECIFICATION DIVISION SPECS ARE NOT
 PART OF THE RECORD PLANS AND ARE NOT TYPICALLY USED
 DURING INSPECTIONS. THESE ARE NOT PART OF REVIEW FOR
 MINIMUM CODE COMPLIANCE. PLEASE PLACE NOTE ON
 RISER/ALONG WITH CONDUCTORS FOR BROWN, PURPLED AND
 YELLOW. 277/480V.
 90.4, 310.11,310.12 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
 ** PREVIOUS COMMENTS.
  
 16) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH
 MENTIONED THE RECEPTACLE WHICH APPEARED TO BE SHOWN
 ABOVE THE CEILING FOR WATER COOLERS. THE SECTION OF
 CODE GIVEN WAS THAT NO CORDS ARE PERMITTED ABOVE THE
 CEILING. THE RESPONSE COMMENT MENTIONED THESE
 RECEPTACLES ARE FOR REMOTE CHILLER UNIT ABOVE CEILINGS.
 THESE ARE NOT PERMITTED TO BE CORD AND PLUG CONNECTED.
 PLEASE SEE 400.8 AND PLEASE REVISE DESIGN.
 FBC 106.1.2.
  
 17) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO
 FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. THERE ARE SEVERAL CODE
 SECTIONS WHICH HAVE BEEN REPEATED FOR THE THREE
 REVIEWS. THE FEE IS A STATUTORY REQUIRED FEE AND IS NOT
 A LOCAL ORDINANCE, FINE OR REQUIRED BY THE LOCAL LEVEL.
 THE FEE IS ASSESSED TO THE DESIGN TEAM AS REQUIRED BY
 THE STATUTE. THE FEE IS THE PORTION OF THE BASE FEE
 ATTRIBUTED TO PLAN REVIEW TIMES FOUR. THE BASE PERMIT
 FEE OF THIS PROJECT IS $52,000. THE PORTION OF THAT FEE
 WHICH IS ATTRIBUTED TO PLAN REVIEW IS 30% OF THE BASE
 PERMIT FEE WHICH IS $15,600. THIS IS THE AMOUNT TIMES
 FOUR WHICH IS ASSESSED. THIS AMOUNT IS $62,400. THIS IS
 A STATUTE REQUIRED FEE WHICH IS REQUIRED TO BE PAID
 BEFORE PLANS ARE RESUBMITTED FOR THE FOLLOWING REVIEW.
 PLEASE KNOW THAT ONE SET OF ELECTRICAL PLANS ALONG WITH
 ENERGY CALCULATIONS AND OTHER POSSIBLE DOCUMENTS ARE
 BEING RETAINED BY THIS OFFICE.
 IT IS RECOMMENDED IF THERE ARE QUESTIONS TO PLEASE
 CONTACT THIS OFFICE/REVIEWER.
  
 *** PLEASE KNOW THERE MAY VERY WELL BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME DUE
 TO INFORMATION ETC NOT YET IN DESIGN OR ON PLANS.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-07 Cont ID  
Sent By dpalmer Date 2008-02-07 Time 20:07 Rev Time 0.00
Received By dpalmer Date 2008-02-06 Time 19:31 Sent To  
Notes
2008-02-07 20:07:482008-02-07 20:07:48
  
 *** DENIED 2ND REVIEW***
  
  
 NEW GRACE PAVILION
 PEGGY ADAMS ANIMAL RESCUE LEAGUE.
  
 *** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE
 THERE ARE ALSO NEW NOTES DUE TO CHANGES, NEW ITEMS OR
 NOTES BASED ON NEW DOCUMENTS NOT PREVIOUSLY SUBMITTED,
 ** AS MENTIONED ON PREVIOUS REVIEW ALL ITEMS COULD NOT
 BE REVIEWED AND THERE MAY BE NEW COMMENTS WHICH COULD
 NOT HAVE BEEN MADE.
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH
 MENTIONED TO SEE CODE REFLECTED ON PLANS NEED TO BE
 CHANGED TO THE CURRENT CODE IN WHICH THE PROJECT WAS
 UNDER FOR DESIGN. A COUPLE OF EXAMPLES WERE GIVEN AND
 STILL NEED TO ADDRESS THESE.
 PLEASE SEE WITH THE EXCEPTION OF THE CORRECTION FOR
 CODES REFLECTED ON THE BOTTOM OF PANEL P1-S2, ALL OTHER
 PANELS STILL SHOW CODE FROM THE 1999 NFPA-70. PLEASE
 SEE THIS SAME CODE 220.13 IS STILL ALSO BEING REFLECTED
 ON THE PANEL P4 EVEN AS THIS DOES NOT APPLY TO THIS
 RESIDENTIAL UNIT. PLEASE ADJUST.
 PLEASE SHEET E-301 OCTAGONAL NOTE #6 WHICH REFLECTS
 250.81C WHICH IS FROM THE 1996 NFPA-70. PLEASE BE SURE
 TO GO OVER PLANS AND ADJUST ANY CODE REFERENCED. FBC
 106.1.2 FOR COORDINATION.
  
 2) NOTE: PLEASE CLARIFY WHY THE RESPONSE NOTES CONTAIN
 A BOOKLET FOR CAPRI ENGINEERING IN THE MIDDLE OF NOTES
 SHOWING PROJECTS ETC. IF THIS PROJECT IS BEING
 SUBMITTED AS PRIVATE PROVIDER PLEASE FOLLOW
 REQUIREMENTS OF FS 553.791. AS THIS PROJECT HAS NOT
 BEEN SUBMITTED PREVIOUSLY UNDER FS 553.791 WITH ALL
 DOCUMENTS REQUIRED IT IS UNCLEAR WHY OTHER DOCUMENTS
 WERE SUBMITTED.
 PLEASE ALSO VERIFY CURRENT DOCUMENTS FROM CAPRI
 ENGINEERING AS THESE MAY BE UPDATED.
  
 3) NOTE: PLEASE BE SURE TO MAKE SURE ADDRESSING ON ALL
 DOCUMENTS SUBMITTED IS REFLECTED TO THE NEW ADDRESS
 ASSIGNED BY THE ADDRESSING REVIEWER.
 PLEASE SEE FOR EXAMPLE: PLANS SHOW 3100, PERMIT
 APPLICATION SHOWS 3200 AND ENERGY CALCULATIONS SHOW
 3200.
 FBC ADMIN SECTION 106.1.2, 106.5
 FAC 61G1-16.004, 61G15-23.002
  
 4) NOTE: PLEASE SEE NOTES FROM OTHER TRADES FOR ANY
 REFERENCES TO THE GENERATOR, LOCATION, SCREENING ETC.
 PLEASE SUBMIT CALCULATIONS FOR BUILDING REVIEW OF SLAB
 DETAIL. PLEASE KNOW IF IN A FLOOD ZONE, THE UNIT SHALL
 BE REQUIRED TO BE A MINIMUM OF 6INCHES ABOVE GRADE.
 PLEASE SEE THE PLANS SHOW A SLAB THICKNESS OF ONLY
 4INCHES FOR THIS 1000KW GENERATOR. PLEASE KNOW THE
 INSTALLATION SHALL MEET NFPA-110CHAPTER 7 AND MINIMUM
 INSTALLATION REQUIREMENTS AS SET-FORTH BY THE GENERATOR
 MANUFACTURE.
 PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WITH RESPECT TO THE GENERATOR ON THE OTHER
 TRADE PLANS SUCH AS ARCHITECTURAL SITE PLANS, LANDSCAPE
 ETC. THIS IS GIVEN FOR INFORMATION ONLY BY THIS
 REVIEWER AS THIS INFORMATION WAS FORWARDED TO OTHER
 TRADES TO PLACE IN COMMENTS AS APPLICABLE.
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS ON THIS
 UNIT AND FUEL TANK. THE FUEL TANK WILL BE REVIEWED BY
 MECHANICAL AND FIRE REVIEW AND PLEASE SEE NOTES FROM
 THOSE TRADES WITH RESPECT TO DERM STAMPS REQUIRED BASED
 ON THE SIZE OF FUEL CAPACITY.
 FBC 106.1.2
 NEC 110.3, 90.7
  
 5) NOTE: PLEASE SEE THE RISER SHOWS GFP (GROUND FAULT
 PROTECTION) ON THE GENERATOR UNIT ITSELF. IS THIS NOT
 TO READ GFS, (GROUND FAULT SENSING) OR GFA (GROUND
 FAULT ALARM) ? THE CODE REQUIRES THE GFP PROTECTION ON
 THE NORMAL SIDE OF THE SERVICE EQUIPMENT, BUT NOT ON
 THE EMERGENCY SIDE. THE CODE DOES REFERENCE GROUND
 FAULT SENSING.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 THIS UNIT AS NOTED ABOVE AND FOR THE ATS DEVICE. 110.3,
 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 THE RISER STATES TO SEE SPECS FOR THE ATS YET COULD NOT
 LOCATE ANY SUBMITTED IN PACKAGE.
  
 6) NOTE: PLEASE SEE THE RISER HAS THIS GENERATOR AS A
 SEPARATELY DERIVED UNIT WHICH IS CODE COMPLIANT AND
 CORRECT HOWEVER PLEASE SEE THE RISER DOES NOT SHOW ANY
 GROUNDING ELECTRODE SYSTEM FOR THIS UNIT. PLEASE SEE
 250.20, 250.30, 250.50.
 PLEASE SEE NFPA-110 6.2.1.5
  
 7) NOTE: PLEASE SEE THE RAISED SEAL FROM THE ENGINEER
 ON THE SEVERAL SHEETS AND SUPPORTING DOCUMENTS ARE ONCE
 AGAIN FAINT ON MANY SHEETS WHERE THE LICENSE
 INFORMATION CAN NOT BE SEEN. THIS WAS A COMMENT ON
 PREVIOUS REVIEW AND RESPONSE WAS THIS WILL BE
 ADDRESSED. MOST SHEETS ARE OK, HOWEVER SOME ARE STILL
 NOT READABLE. PLEASE SEE ENERGY CALCULATIONS FOR
 EXAMPLE AS ONE OF THE SETS COULD NOT BE READ. PLEASE
 SEE FAC 61G15-23.001 WHICH REQUIRES ALL INFORMATION TO
 BE CLEAR AND VISIBLE.
  
 8) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS FOR
 REVIEW AND BE SURE TO COORDINATE ALL INFORMATION ON THE
 INPUT DATA REPORT WITH THE LIGHTING ON PLANS AND THE
 FIXTURE LEGEND. 13-415.1.A, 13-415.1.AB, 13-415.2 THE
 INPUT DATA REPORT IN THE REST OF THIS COMMENT WILL BE
 REFLECTED AS IDR.
  
 A) ** PLEASE BE SURE TO GO THROUGH ALL ITEMS ON THE
 INTERIOR LIGHTING SHOWN ON THE IDR AND COORDINATE WITH
 PLANS. PLEASE SEE THERE ARE DIFFERENCES IN THE AMOUNT
 OF FIXTURES, THE WATTAGES/TOTALS AND THE METHOD OF
 CONTROLS.
 PLEASE SEE FOR EXAMPLE: LOBBY AREA LIGHTING ON PLANS
 DOES NOT MATCH WITH THE AMOUNT AND TYPE OF FIXTURES ON
 THE IDR.
 PLEASE SEE FOR EXAMPLE: THE METHODS OF CONTROL FOR SOME
 ARE BEING SHOWN AS *MANUAL ON/OFF* YET THE METHOD OF
 CONTROL IS AN AUTOMATED MEANS. PLEASE GO OVER ALL
 FIXTURES ON PLANS AND COORDINATE WITH THE IDR. THIS
 OFFICE CAN NOT EMPHASIZE ENOUGH THE IMPORTANCE. THE
 ENERGY CALCULATIONS SUBMITTED DATED JUNE 07 AND DEC 07
 ARE NOT CHANGED.
  
 B) ** PLEASE BE SURE TO GO OVER PLANS AND THE SQUARE
 FOOTAGE INFORMATION ON THE CALCULATIONS SUBMITTED.
 PLEASE SEE THE PERMIT APPLICATION STATES A SQ FT LESS
 THAN CALCULATIONS AND THE CALCULATIONS COVER SHEET IS
 LESS THAN THATOF THE SQ FT SHOWN ON THE ARCHITECTURAL
 PLANS.
 13-415.1.A, 13-400.3.A
  
 C) ** PLEASE BE SURE ALL INFORMATION ON PLANS FOR
 EXTERIOR LIGHTING COORDINATES WITH THE IDR AND THE
 FIXTURE LEGEND. PLEASE SEE FOR AN EXAMPLE: THE IDR FOR
 EXTERIOR LIGHTING SHOWS A TOTAL OF 24 -40WATT FIXTURES.
 HOW IS THIS POSSIBLE WHEN NOT ONLY THE PLANS SHOWS
 DOZENS MORE FIXTURES FOR EXTERIOR LIGHTING FIXTURES BUT
 THE FIXTURE WATTAGES ON PLANS ARE SUBSTANTIALLY HIGHER
 THAN THE STATED 40WATTS ON THE IDR.
 PLEASE SEE SOME OF THESE FOR EXAMPLE ARE 400W FIXTURES,
 70W, 50W ETC ETC. PLEASE SEE THE FIXTURE LEGEND FOR
 TYPES, P, D1, S-1, L, H ETC . THIS IS NOTED ONLY FOR A
 FEW.
  
 D) ** PLEASE SEE THE CLASSIFICATION OF THE EXTERIOR
 LIGHTING FIXTURES ON THE IDR MENTIONS * LIGHTING THAT
 IS SPECIFICALLY DESIGNATED AS REQUIRED BY A HEALTH OR
 LIFE SAFETY, STATUE, ORDINANCE, OR REGULATION*. PLEASE
 PROVIDE INFORMATION ON ANY OF THESE AS THERE ARE KNOWN
 STATUTES, ORDINANCES, LIFE SAFETY CODES ETC WHICH
 REQUIRES ANY OF THESE EXTERIOR LIGHT FIXTURES. PLEASE
 ADJUST DESIGNATIONS.
  
 E) ** PLEASE BE SURE THE ENERGY CALCULATIONS ARE
 SIGNED, DATED AND SEALED WITH RAISED SEAL AS NOTED
 ABOVE AND REQUIRED PER FAC 61G15-23.002, FS 471.025 AND
 FBC 13-103.1.1.1.
 PLEASE BE SURE THE OWNER AGENT IS ALSO SIGNED ON NEW
 CALCULATIONS.
  
 9) NOTE: PLEASE SUBMIT AND SHOW ALL MAXIMUM TIMES FOR
 ALL LIGHTING CONTROL DEVICES PER 13-415.1.ABC.1.1, .1.2
 AND .1.3
  
 10) NOTE: PLEASE BE SURE TO SHOW AND LABEL ALL ROOM AND
 AREA DESIGNATIONS ON PLANS. PLEASE SEE FOR EXAMPLE
 ROOMS OFF OF LOADING DOCKS/BAY AREAS WHICH DOE NOT
 CONTAIN ANY DESIGNATIONS.
 PLEASE SEE FOR EXAMPLE: THE ROOM NORTH OF STORAGE AND
 WEST OF MECHANICAL ROOM. PLEASE KNOW AS THESE ROOMS ARE
 NOT DESIGNATE * STORAGE 101* ETC THE CIRCUITING CAN NOT
 BE VERIFIED.
 FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
 NEC 408.4 ETC
  
 11) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 THAT OF THE PANEL SCHEDULES SUBMITTED OR TO BE
 SUBMITTED.
 PLEASE SEE SOME EXAMPLES BELOW:
  
 A) ** THE WP GFI CIRCUITED FOR THE ROOF-TOP UNITS
 INDICATE A P-78, YET NO *P* PANEL IS ON RISER OR
 SUBMITTED WITH SCHEDULES. THIS IS ASSUMED AS MISPRINT.
  
 B) **PLEASE SEE PANEL P4 WHICH CONTAINS MANY CIRCUITS
 WHICH DO NOT CORRELATE. PLANS SHOW LAUNDRY ROOM
 RECEPTACLE ON CIRCUIT 4, YET THE PANEL SCHEDULE SHOWS
 6.
  
 C) ** PLEASE SEE PLANS SHOWS WASHER ON CIRCUIT P-14,
 YET THE PANEL SCHEDULE SHOWS P-12. THIS AFFECTS THE
 DRYER AND OTHER CIRCUITS.
  
 D) ** PLEASE SEE P4-16 AS THIS IS BEDROOM ON PLANS AND
 BATH ROOM ON SCHEDULE.
  
 ** THESE ARE SOME EXAMPLES OF THE PLANS FOR ALL. PLEASE
 SEE THERE ARE OTHERS ALSO AND SOME ARE NOTED BELOW WITH
 RESPECT TO OTHER CODES AFFECTED BY MANY NOT CIRCUITED
 CORRECTLY.
 408.4, 240.4, 310.16, ETC
 FBC 106.3.5.4, 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 12) NOTE: PLEASE SEE NFPA-70 210.11C3 WHICH REQUIRES
 DEDICATE BATH CIRCUIT(S) IN ONLY TWO SCENARIOS. PLEASE
 KNOW WHEN THE GFI IS FED IN ONE BATH ROOM AND FEEDS
 OTHER ITEMS IN THAT *SAME* BATH, IT MAY NOT FEED ANY
 OTHER ROOMS, BATHROOMS OR APPLIANCES.
 PLEASE SEE FOR EXAMPLE: THE CIRCUIT SHOWN ON PLANS FOR
 P4-18 SHOWS THE GFI BEING FED AND THEN THE PANEL
 SCHEDULE ALSO NOTES THIS AS FEEDING NOT ONLY THE
 EXHAUST FAN IN THE SAME BATHROOM WHICH IS OK, BUT THE
 PANEL SCHEDULE ALSO SHOWS THIS FEEDING EF-82 AND83
 WHICH IS NOT PERMITTED PER CODE SECTION NOTED ABOVE.
 PLEASE ALSO SEE FOR EXAMPLE: THE PANEL SCHEDULE SHOWS
 THE P4-6 AS FEEDING BATH AND LAUNDRY ROOM COMMON
 RECEPTACLE WHICH IS NOT PERMITTED. THE PLANS ACTUALLY
 SHOW THE LAUNDRY ROOM RECEPTACLE ON WITH THE BEDROOM.
  
 13) NOTE: PLEASE SEE THE PANEL SCHEDULE SHOWS PANEL P4
 WITH THREE SMALL APPLIANCE CIRCUITS YET THE LOAD
 CALCULATIONS ONLY INDICATE TWO.
 PLEASE ALSO SEE THE PLANS ARE MISSING THE THIRD CIRCUIT
 ALSO: (15).
 PLEASE SEE 210.52B1, 210.11C1, 220.52
  
 14) NOTE: PLEASE SEE COUNTER SPACE IN BETWEEN RANGE AND
 WALL TOWARDS ELECTRICAL PANEL APPEARS TO BE MISSING A
 GFI RECEPTACLE PER 210.52C1 FOR 12 INCHES OR MORE OF
 COUNTER SPACE BASED ON SCALE ON PLANS.
  
 15) NOTE: PLEASE SEE ARC FAULT PROTECTION IS NOT SHOWN
 FOR ALL OUTLETS IN THE BEDROOMS AS REQUIRED PER 210.12
 OF THE 2005 NEC>
 PLEASE KNOW THIS REQUIRES ALL RECEPTACLES, FANS, LIGHTS
 ETC
 PLEASE SEE FOR EXAMPLE: CIRCUIT # 16 DOES NOT INDICATE
 ANY DOUBLE ** ASTERISK AS NOTED ON PANEL FOR AFCI
 BREAKER.
 PLEASE ADJUST.
  
 16) NOTE: PLEASE VERIFY SOUNDING LEVELS FOR ADA
 COMPLIANCE ON PLANS PER FBC 11-4.28.2.
  
 17) NOTE: PLEASE CLARIFY THE NOTE AND LOCATIONS OF
 LIGHTING ON SHEET E-104. THE TITLE ON THIS SHEET
 MENTIONS MECHANICAL SPACE STILL YET THE RESPONSE TO ONE
 OF THE PREVIOUS COMMENTS IS THAT MECHANICAL EQUIPMENT
 IS ON ROOF.
 PLEASE SEE THE RESPONSE TO NOTE #15 STILL MENTIONS A
 MEZZANINE LEVEL HOWEVER LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.1 AND .1.2 ARE NOT LOCATED ON THIS
 SHEET.
 THERE IS A NOTE ON LIGHTING PLANS E-103 WHICH MENTIONS
 TO INDIRECT LIGHTING ABOVE. ARE THE FIXTURES ON E-104
 OPEN AND ABOVE FIRST FLOOR AREA?
 ARE THESE SEPARATE AREAS? SEE NOTES FORM OTHER TRADES.
 NO FINAL DETERMINATION CAN BE DONE AT THIS TIME.
  
 18) NOTE: PLEASE SEE THE COLOR CODING FOR THE 277/480V
 SYSTEM CONDUCTORS WILL BE REQUIRED TO BE BROWN, PURPLE,
 AND YELLOW.
 PLEASE KNOW FOR SEVERAL DECADES ALL OF PALM BEACH
 COUNTY ALONG WITH THE CITY OF WEST PALM BEACH CONTAINED
 TECHNICAL AMENDMENTS TO THE CODE FOR COLOR CODING OF
 CONDUCTORS AS NFPA-70 DOES NOT PROVIDE COLOR CODING OF
 SYSTEM VOLTAGES. AS THE TECHNICAL AMENDMENTS ARE NO
 LONGER IN EFFECT AND KEEPING WITH THE CONSISTENCY OF
 SAFE INSTALLATION PRACTICES WITHIN THE CITY THIS IS
 REQUIRED ON A LOCAL LEVEL. THE COLOR ORANGE AS STATED
 IN DIVISION SPECS IS CLEARLY REQUIRED FOR *HIGH-LEG*
 DELTA SYSTEMS IN THE NEC AND WOULD NOT APPLY FOR
 277/480V SYSTEMS.
 PLEASE ADJUST COLOR CODING AS NOTED ABOVE. PLEASE ALSO
 SEE PAGE #4 IN 16120 3.01.
 90.4
  
 19) NOTE: PLEASE CLARIFY EMERGENCY BACK UP LIGHTING.
 THE RESPONSE MENTIONS THAT HALF SHADED FIXTURES WILL BE
 BATTERY BACK UP AND DETAILS ON LIGHTING PLANS SHOW THAT
 BATTERIES ARE PART OF THE FIXTURE WIRING HOWEVER THE
 FIXTURE SCHEDULE DOES NOT CONTAIN ANY NOTES FOR BACK UP
 BALLAST/BATTERIES. PLEASE ALSO SEE THE SHADED FIXTURES
 ON THE ELECTRICAL SYMBOL LEGEND ONLY SHOWS FIXTURES
 *B*.
 PLEASE ADJUST AND COMPLETE FIXTURE LEGENDS FOR ALL NEW
 FIXTURES AS NOTED.
 LS -101 7.8, 7.9
  
 20) NOTE: **ONLY NOTED** ANY PROPOSED INSTALLED
 LIGHTNING PROTECTION SYSTEM WILL BE UNDER SEPARATE
 PLANS, PERMIT AND MOST IMPORTANTLY SHALL MEET
 NFPA-780.
  
 21) NOTE: PLEASE CLARIFY J-BOX BEING SHOWN ABOVE
 CEILINGS FOR WATER COOLERS.
 PLEASE KNOW NO CORDS ARE PERMITTED ABOVE CEILINGS FOR
 CORD AND PLUG CONNECTED UNITS.
 PLEASE KNOW THIS CAN BE REDLINED BUT WILL STILL NEED TO
 SHOW FINAL CONNECTIONS PER NEC.
 THIS CAN BE DONE AT THIS TIME OR WILL BE NEED TO BE
 REVISED AT A LATER DATE.
 400.8
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 22) NOTE: PLEASE KNOW THE REQUIRED CALCULATIONS FOR
 SITE LIGHTING POLES MAY BE PART OF A *PROVISO* WHICH
 WILL REQUIRE THESE TO BE SUBMITTED BEFORE INSTALLATION.
 THIS IS GIVEN FOR INFORMATION AT THIS TIME. IF WIND
 LOAD CALCULATIONS ARE PROVIDED AT THIS TIME, THERE WILL
 BE NO NEED FOR PROVISO.
  
 23) NOTE: PLEASE SEE THERE IS A LOSS IN TRANSLATION FOR
 THE CLARIFICATION OF THE PANEL RATINGS. THE PREVIOUS
 REVIEW NOTES MENTIONED THERE WERE SEVERAL PANELS SHOWN
 AS 60AMP RATED MAIN LUG ONLY PANELS AND 30 CIRCUITS.
 THE COMMENT MENTIONED THAT THIS OFFICE WAS NOT AWARE OF
 30CIRCUIT 60AMP RATED MLO PANELS AND TO VERIFY. THE
 PLANS HAVE NOW COME BACK WITH 42CIRCUIT 60AMP RATED MLO
 PANELS.
 IF THE PANEL IS FED FROM A 60AMP BREAKER THIS WOULD NOT
 BE A 60AMP RATED MLO PANEL. IT WOULD STILL BE RATED AT
 THE AMPERAGE RATING OF THE PANEL. IE; 150A RATED, 200
 AMP RATED, 225AMP RATED MLO.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR ANY
 60AMP RATED 42 CIRCUIT PANELS.
 110.3, 90.7.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION
  
 24) NOTE: PLEASE CLARIFY THE AIC RATINGS OF ALL THE
 PANELS AND EQUIPMENT. PLEASE SEE FOR EXAMPLE THE SAME
 PANELS AS NOTED ABOVE IN NOTE #23 ARE BEING SHOWN WITH
 A 22,000 RATING. IS THIS FOR THE PANEL? THE BRANCH
 BREAKERS? OR BOTH?
 PLEASE SEE THE MSB IS SHOWN AS 42,000 AIC RATED ON
 SCHEDULE YET THE NOTES ON RISER ON SHEET E-301 MORE
 SPECIFICALLY MSB NOTES 2A INDICATES 100,000 AIC RATED
 MAIN. WHICH ONE IS THIS?
 PLEASE INDICATE THE RATINGS OF PANELS AND BRANCH
 BREAKERS AND ANY MAIN BREAKERS.
 IF THE AIC RATING IS SHOWN AS 22K, THEN THIS IS WHAT
 WILL BE REQUIRED TO BE INSTALLED.
 110.9, 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 25) NOTE: PLEASE SEE THE CEILING FANS IN THE
 RESIDENTIAL UNIT WILL REQUIRE LIGHT KITS OR OTHER MEANS
 OF TURNING ON LIGHTING IN ROOMS PER 210.70 SHALL BE
 SUPPLIED. THIS CAN BE DONE WITH SWITCHED RECEPTACLE OR
 OTHER LIGHTING MEANS. THE FIXTURE LEGEND FOR FANS
 INDICATES NO LIGHTING TO BE A PART OF THE FANS. IN FACT
 IT IS BLANK.
 LS 101 7.8
  
 26) NOTE: PLEASE KNOW AS MENTIONED ON PREVIOUS REVIEW
 AND IN MEETING HELD AFTER THE FIRST REVIEW, IF THE
 DISCONNECTING MEANS ON THE GENERATOR DOES NOT MEET THE
 *EXCEPTIONS* IN THE CODE MORE SPECIFICALLY 702.11. A
 DISCONNECT RATED FOR THE LOAD SERVED SHALL BE REQUIRED
 AT THE BUILDING PER 225.31-225.39. THIS DISCONNECT AS
 PREVIOUSLY MENTIONED DOES NOT REQUIRE OVER CURRENT
 PROTECTION. THIS ONLY REQUIRES DISCONNECT TO BE RATED
 FOR THE LOAD SERVED. THE SHUNT/BUTTON SHOWN ON RISER
 DOES NOT MEET CODE FOR THIS REQUIREMENT.
  
 27)NOTE: PLEASE SEE NOTICE TO FLORIDA STATUTES
 553.80(2)(B) IS BEING GIVEN WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY GIVEN AS A
 NOTICE AT THIS TIME.
 PLEASE KNOW THAT ONE SET OF ELECTRICAL PLANS MAY BE
 RETAINED BY THIS OFFICE ALONG WITH ONE SET OF THE
 ENERGY CALCULATIONS.
  
 28) NOTE: PLEASE CONFIRM THE LOCATION OF THE FACP WHICH
 IS NOW IN THE TELECOM ROOM.
 PLEASE BE SURE TO CONTACT THE FIRE MARSHAL AS THIS WILL
 HAVE AN AFFECT ON THE ELECTRICAL PLANS AND ANY
 RELOCATION NEEDED.
  
 ** AS THERE ARE ITEMS NOT YET SUBMITTED, OR ITEMS FROM
 OTHER TRADES WHICH MAY AFFECT PROJECT DESIGN, PLEASE
 KNOW THAT ANY CHANGES ETC WHICH ARE NOT PART OF THIS
 SUBMITTED PACKAGE COULD NOT BE REVIEWED AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-02-06 19:31:372008-02-06 19:31:37
  
 ONE SET OF PLANS AND SPECS IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 11:50 Rev Time 0.00
Received By dpalmer Date 2007-07-02 Time 18:36 Sent To I
Notes
2007-07-03 11:51:132007-07-03 11:51:13
  
 *** UNSAT ***
  
  
 NEW GRACE PAVILION
 PEGGY ADAMS ANIMAL RESCUE LEAGUE.
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT YET
 SUBMITTED FOR REVIEW, WHEN PLANS AND DOCUMENTS ARE
 SUBMITTED FOR REVIEW ON THE NEXT RE-SUB THEY WILL BE
 THE FIRST TIME IN FOR REVIEW. THERE MAY BE NEW COMMENTS
 ONCE ADDITIONAL INFORMATION IS SUBMITTED.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC.
 PLEASE SEE SOME OF THE CORRECT CODES ARE REFLECTED ON
 PLANS BUT NOT ALL. PLEASE SEE SOME PREVIOUS CODES NO
 LONGER IN EFFECT ARE STATED. PLEASE SEE SOME CODE
 SECTIONS WHICH ARE STATED ON PLANS ARE NOT FROM THE
 CURRENT NEC.
 PLEASE LIST THE FOLLOWING:
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2002 NFPA-110
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR THE CIVIL ENGINEERING FIRM PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.023.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
 ** THIS IS REQUIRED FOR ALL *C* SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR
 LANDSCAPE ARCHITECTURAL FIRM AS REQUIRED PER FAC
 61G1-16.004 AND FS 481.219.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 ALSO KNOWN AS THE FIRM LICENSE NUMBER.
 ** PLEASE SEE THIS IS REQUIRED FOR ALL SHEETS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE ELECTRICAL SHEETS ARE MISSING
 TITLE BLOCKS FOR THE MEP FIRM AS SHOWN ON OTHER
 SHEETS.
  
 PLEASE COMPLETE THESE SHEETS WITH THE INFORMATION AS
 REQUIRED PER FAC 61G15-23.002.
  
 5) NOTE: PLEASE SEE THE RAISED SEAL FROM THE ENGINEER
 ON THE ELECTRICAL AND FP SHEETS ARE EXTREMELY FAINT.
 THE INFORMATION ON SAID SEALS ARE NOT VISIBLE OR EASILY
 READ. PLEASE SEE FAC 61G15-23.001 WHICH REQUIRES ALL
 INFORMATION TO BE CLEAR AND VISIBLE.
 ** PLEASE SEE THIS IS REQUIRED OF ALL TRADES AND FOR
 ALL SHEETS, ALTHOUGH IT IS MAINLY ON THE E AND FP
 SHEETS.
  
 6) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS FOR
 REVIEW. PLEASE SEE FBC CHAPTER 13, 13-415.1.AB.1.1,
 13-415.1.C, AND PERFORMANCE CALCULATIONS PER 13-415.2.
 AS NO INFORMATION WAS SUBMITTED, NO REVIEW OF THESE
 COULD BE DONE.
 PLEASE BE SURE TO SEE 13-103.1.1.1 FOR SIGNED, DATED
 AND SEALED SHEETS.
 ** PLEASE CHECK WITH FLA-COM FOR LATEST VERSION AS
 EFFECTIVE DATE OF DECEMBER 8TH, 2006 WHEN THE LATEST
 CODE CHANGE WENT INTO EFFECT.
  
 7) NOTE: PLEASE INDICATE THE WORST CASE SCENARIOS FOR
 VOLTAGE DROP OF CIRCUITS FOR FEEDERS AND BRANCH
 CIRCUIT(S). 13-413.1.ABC.1
  
 8) NOTE: PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW
 ANY AUTOMATED DEVICES FOR LIGHTING CONTROLS OR SHUT
 OFFS. PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 OF THE
 2004 FBC W/2006 REVISIONS.
 PLEASE BE SURE ALL MAXIMUM TIMES ON DEVICES ARE NOTED
 AND SHOWN.
 PLEASE SEE AS THERE ARE AREAS WHICH DO NOT SHOW CONTROL
 AT THIS TIME INCLUDING UPPER LEVELS, SOME ITEMS CAN NOT
 BE REVIEWED AT THIS TIME.
  
 9) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMITS. THESE SUBMITTED
 PLANS MAY BE USED TO REFERENCE HOWEVER SEPARATE PERMIT
 APPLICATIONS, AND FEES WILL BE DUE FOR THAT SCOPE OF
 WORK SUCH AS LV CATV< PHONE, DATA, ETC. IF THESE ARE
 ALL DONE BY THE SAME CONTRACTOR, ALL CAN BE ON ONE
 PERMIT.
 PLEASE KNOW THAT LOW VOLTAGE PERMITS FOR FIRE ALARM
 SYSTEMS ARE SEPARATE AND REQUIRE PLANS ALONG WITH
 PERMIT APPLICATION.
 ** NO CHANGES NEED TO BE MADE TO PLANS; THIS IS BEING
 NOTED FOR INFORMATIONAL PURPOSE ONLY.
  
 10) NOTE: PLEASE SEE THE MAIN ELECTRICAL ROOM SHOWS THE
 MDF WHICH IS PART OF THE IT EQUIPMENT. PLEASE SEE THIS
 ROOM IS A HIGH VOLTAGE ELECTRICAL ROOM AND ACCESS TO
 THIS ROOM SHOULD BE LIMITED TO *QUALIFIED PERSONNEL* AS
 STATED IN THE NEC. PLEASE SEE THAT MANY TIME THIS
 EQUIPMENT ON THE MDF REQUIRES ACCESS TO OTHER THAN
 *QUALIFIED PERSONNEL*. PLEASE SEE THAT CONSIDERATION TO
 THE LOCATION OF THIS EQUIPMENT SHOULD BE TAKEN AND
 RELOCATED OR SEPARATE FROM THE MAIN ELECTRICAL ROOM AND
 EQUIPMENT.
 110.26, 110.27, 110.16, 110.18
  
 11) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS FOR THE
 SITE LIGHTING POLES. PLEASE KNOW THESE ARE ALREADY
 STATED ON SITE PLANS MEETING THE FBC FOR WIND
 REQUIREMENTS HOWEVER THE CALCULATIONS ARE STILL NEEDED
 FOR REVIEW. THESE ARE REQUIRED TO CONTAIN THE TITLE
 BLOCKS FROM THE DESIGN PROFESSIONAL AND TO BE SIGNED,
 DATED AND SEALED.
 FBC 106.1.2
  
 12) NOTE: PLEASE CLARIFY LIGHTING FIXTURES ON PLANS.
 THE FIXTURE SCHEDULE DOES NOT INDICATE ANY BATTERY BACK
 UP LIGHT FIXTURES EVEN THOUGH MANY OF THE FIXTURES ARE
 HALF SHADED WHICH TYPICALLY STANDS FOR BATTERY BACK UP
 LIGHT FIXTURES.
 PLEASE ADJUST AND INDICATE BATTERY BACK UP FIXTURES ARE
 THE MINIMUM AMOUNT OF BATTERY BACK UP FIXTURES WILL BE
 REQUIRED TO MEET THE MINIMUM FOOT CANDLES IN EGRESS
 PATHS TO THE PUBLIC RIGHT OF WAY OUTSIDE OF THE
 BUILDING. PLEASE SEE NFPA-101 7.8 AND 7.9.
 PLEASE ALSO SEE THE MAIN ELECTRICAL ROOM WILL ALSO BE
 REQUIRED TO CONTAIN AN BATTERY BACK UP LIGHT OF SOME
 KIND.
 PLEASE SEE 700.12F FOR CIRCUITING AND 700.16.
  
 13) NOTE: PLEASE BE SURE TO STATE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS AND BE SURE THESE CORRELATE WITH
 THE PANEL SCHEDULES AS SUBMITTED ON PLANS. MOST ARE
 DONE HOWEVER SOME ARE MISSING.
 FBC 106.1.2, 106.3.5.1.2
 NEC 408.4
  
 14) NOTE: PLEASE CLARIFY UPPER LEVEL PLANS FOR LIGHTING
 AND POWER. PLEASE SEE THERE ARE ELECTRICAL AND
 MECHANICAL ON PLANS HOWEVER NO CIRCUITING, NO ROOM
 DESIGNATIONS, ETC. PLEASE SEE THE SHADED AREAS ON THE
 LOWER RIGHT HAND CORNER OF PLANS ON E104 AND 204 WHICH
 INDICATES THE AREA OF THE BUILDING IN WHICH THESE AREAS
 ARE LOCATED HOWEVER THE SHADED ARE ENCOMPASSES THE
 ENTIRE BUILDING AS SHOWN. AS THESE AREAS ARE CLEAR OF
 USE, HOW AREA IS ACCESSED, CIRCUITING, LIGHTING
 CONTROLS ETC REVIEW FOR MANY ITEMS CAN NOT BE DONE AT
 THIS TIME.
 PLEASE SE FBC ADMIN SECTION 106.1.2 AND 106.3.5.1.2 FOR
 ADDITIONAL INFORMATION NEEDED.
 PLEASE SEE NEC 408.4, AND THE FOLLOWING WHICH IS TAKEN
 FROM THE NEC COMMENTARY.
  
 15) NOTE: PLEASE CLARIFY ANY ROOF-TOP GFI RECEPTACLES
 REQUIRED FOR A/C EQUIPMENT. PLEASE SEE 210.63, 210.8B3.
 AT THIS TIME THE LOCATION OF ALL EQUIPMENT IS NOT
 CERTAIN.
  
 16) NOTE: PLEASE SEE THE APARTMENT/RESIDENTIAL UNIT AS
 SHOWN ON PLANS WILL BE REQUIRED TO MEET THE NEC FOR A
 DWELLING UNIT.
 PLEASE SEE MISSING THE TWO MINIMUM REQUIRED SMALL
 APPLIANCE CIRCUITS. 210.52B1, 210.11C1, 220.52 PLEASE
 SEE THE DINGING ROOM RECEPTACLES ARE SHOWN CIRCUITED TO
 THE LIVING ROOM WHICH IS NOT PERMITTED. SAME CODE
 SECTION.
 PLEASE SEE THE MINIMUM VA FOR THESE REQUIRED CIRCUITS.
 PLEASE SEE THE MINIMUM REQUIRED FOR WASHER IS NOT
 CORRECT.210.11C2, 220.52
 PLEASE SEE THE MINIMUM FOR THE DRYER IS NOT CORRECT.
 220.54
 PLEASE SEE MISSING ARC FAULT PROTECTION PER 210.12 TO
 BE LISTED ON PANEL SCHEDULE.
 PLEASE SEE MISSING THE REQUIRED DEDICATED BATH
 CIRCUIT(S) PER 210.11C3.(THESE ARE SHOWN SHARING WITH
 OTHER DEVICES IN OTHER ROOMS AS LISTED ON PANEL
 SCHEDULE.
 PLEASE SEE MISSING GFI RECEPTACLE/PROTECTION REQUIRED
 FOR WASHING MACHINE. THIS IS NOW WITHIN 6FT OF A
 LAUNDRY TUB. IT DOES NOT MATTER IF THIS DEDICATED
 DEVICE/OUTLET UNDER THE NEW CODE. 210.8A7
 PLEASE VERIFY THE LOAD SHOWN FOR THE RANGE AS IT
 APPEARS LOW.
 PLEASE SUBMIT LOAD CALCULATIONS FOR A DWELLING FOR THIS
 PANEL.
 PLEASE SEE THE CODE SECTION AS REFLECTED TO 220.13 IS
 NOT UNDER THE 2005 NEC AND WOULD NOT APPLY.
 PLEASE SEE NEC 220, FBC 106.3.5.4
  
 17) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR, ATS, SUB-BASE FUEL TANK ETC
 FOR REVIEW.
 PLEASE SEE THE MECHANICAL REVIEW AS THE PLANS WILL BE
 REQUIRED TO BE REVIEWED AND STAMPED BY DERM DUE TO THE
 SIZE OF THE TANK.
 ** PLEASE SEE THE SITE, SURVEY, CIVIL, LANDSCAPE AND
 OTHER PLANS DO NOT INDICATE ANY GENERATOR UNIT. THIS
 NOTE WILL BE FORWARDED TO OTHER TRADES AS THERE WILL BE
 COMMENTS FROM OTHER TRADES SUCH AS ELEVATION, LOCATION,
 SETBACKS, ETC.
 110.3, 90.7
 FBC 106.1.2, 106.3.5.1.2
  
 18) NOTE: PLEASE SEE THE SERVICE IS BEING SHOWN AS GFI
 PROTECTED ALONG WITH GFI PROTECTION ON THE GENERATOR?
 PLEASE SEE THE REQUIRED PROTECTION PER 230.95, 240.13
 ETC IS FOR *GFP* PROTECTION WHICH IS NOT THE SAME AS
 CLASS A GFI PROTECTION FOR PERSONNEL.
 PLEASE ADJUST THE DESIGNATION.
 PLEASE ALSO SEE THE FOLLOWING AS GFP ON THE EMERGENCY
 SECONDARY SIDE IS NOT REQUIRED AND IN FACT ON ANY
 SYSTEMS WHICH ARE CONSIDERED LEGALLY REQUIRED OR
 EMERGENCY SYSTEMS ARE NOT RECOMMENDED BY THE CODE TO
 CONTAIN SUCH PROTECTION. PLEASE KNOW BASED ON THE
 INTEREST OFLIFE SAFETY THIS AHJ WILL NOT PERMIT THIS
 AS IT CREATES THIS HAZARD TO OCCUPANTS.
 PLEASE ALSO SEE THE ATS IS BEING SHOWN AS 3-POLE AND
 NOT 4-POLE WHEN A 4-POLE SWITCH WOULD BE NEED WHEN
 THERE IS GFP PROTECTION ON THE MAIN.
 PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL
 CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING
 CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND
 THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM "ASCO"
 WHITE PAPER: THERE ARE NUMEROUS OTHER NOTED DOCUMENTS
 FROM MULTIPLE MANFACTURES WHICH STATE ROUGHLY THE
 SAME:
 * WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE
 CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED,
 SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT
 SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE
 SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND
 FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE
 MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT
 DISCONNECT THE ARCING FAULT FROM THE GENERATOR.
 COORDINATION IS THUS LOST.*
 PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL
 MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE
 REQUIRED TO BE REVISED.
 PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95,
 700.7D, 700.26
  
 19) NOTE: PLEASE INDICATE ALL TRANSFORMER GROUNDING
 ATTACHMENTS ON THE RISER AND SIZES OF CONDUCTORS.
 250.20, 250.50, 250.66, 250.58
  
 20) NOTE: PLEASE PROVIDE AN ENLARGED VIEW OF THE MAIN
 ELECTRICAL ROOM WITH EXACT SCALE FOR REVIEW OF
 ELECTRICAL EQUIPMENT.
 110.26
 FBC 106.1.2
  
 21) NOTE: PLEASE CORRELATE PLANS AND RISER FOR THE
 SIZES OF THE TRANSFORMER. PLEASE SEE RISER SHOWS 30KVA
 AND THE PLAN SHOWS 45 KVA.
 PLEASE SEE THIS MAY BE THE REASON FOR THE FOLLOWING
 COMMENT IS THE TRANSFORMER IS INDEED A 45KVA UNIT. FBC
 106.1.2 COORDINATION.
  
 22) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION SHOWN
 FOR THE BREAKER TO THE 30KW TRANSFORMER ON RISER IS TOO
 HIGH AS LISTED IN THE MSB PANEL SCHEDULE AND RISER.
 PLEASE SEE 450.3 AND THE MAXIMUM OF 125%.(UNLESS
 MEETING EXCEPTION, IF SO, PLEASE PROVIDE ALL
 INFORMATION FOR THE TRANSFORMER.
  
 33) NOTE: PLEASE SEE THERE ARE SEVERAL PANELS ON RISER
 AND PANEL SCHEDULES WHICH INDICATE 60AMP MLO AND PANEL
 BEING ACTUALLY A HIGHER RATED PANEL. PLEASE KNOW IF
 PANEL HAS A 60AMP/100AMP FEED ETC AND THE PANEL IS A
 100AMP/150AMP OR 200AMP RATED PANEL PLEASE INDICATE THE
 ACTUAL PANEL RATING. THERE IS NO 60AMP RATED PANELS
 WHICH ARE 30CIRCUIT KNOWN TO THIS OFFICE.
 PLEASE SEE SEVERAL COMMENTS BELOW FOR COORDINATION OF
 PANELS, RISER, AMPERAGES, AND WHETHER OR NOT PANELS
 CONTAIN MLO OR MCB.
 FBC 106.1.2 FOR COORDINATION.
  
 34) NOTE: PLEASE SEE H3 WHICH IS SHOWN AS 60AMP MLO ON
 RISER AND SHOWN AS 400AMP MCB ON PANEL SCHEDULE. PLEASE
 CORRELATE.
 FBC 106.1.2, 106.3.5.1.2
  
 35) NOTE: PLEASE SEE PANEL P4 WHICH IS SHOWN A S 60AMP
 MLO, YET CONTAINS 30CIRCUITS.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 36) NOTE: PLEASE SEE PANEL C3 WHICH IS SHOWN AS 60AMP
 MCB ON PANEL SCHEDULE AND 60AMP MLO ON RISER. PLEASE
 CORRELATE.
 FBC 106.1.2
  
 37) NOTE: PLEASE SEE PANEL C1 WHICH IS SHOWN AS 100AMP
 MCB ON RISER AND 60AMP MCB ON PANEL SCHEDULE. PLEASE
 CORRELATE.
 FBC 106.1.2
  
 38) NOTE: PLEASE SEE C2 AS THIS IS SHOWN AS 60AMP MCB
 AND MLO ON RISER.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 39) NOTE: PLEASE SEE RISER INDICATES BOTH PANEL C2 AND
 C3 BEING FED FROM PANEL C1, HOWEVER PANEL C1 SCHEDULE
 DOES NOT INDICATE EITHER OF THESE TWO PANELS? PLEASE
 CORRELATE AND ADJUST LOAD CALCULATIONS ETC. THIS WILL
 AFFECT SEVERAL ITEMS.
 FBC 106.1.2, 106.3.5.1.2
 NEC 240.4, 310.16, 408.4, 215.5 ETC.
  
 40) NOTE: PLEASE SEE PANEL H2 IS SHOWN AS 150AMP MLO ON
 RISER AND 200AMP MLO ON SCHEDULE.
 PLEASE ADJUST AND CORRELATE.
 FBC 106.1.2
  
 41) NOTE: PLEASE SEE CODE SECTION NOTED BELOW ALL PANEL
 SCHEDULES WHICH INDICATES NEC 220.13? PLEASE SEE ANY
 SECTIONS OF THE NEC TO BE NOTED MUST BE FROM THE 2005
 NEC>
 PLEASE ADJUST. FBC 106.1.2
  
 42) NOTE: PLEASE SEE LOAD CALCULATIONS WILL NEED
 ADJUSTMENTS ONCE OTHER CALCULATIONS HAVE BEEN
 CORRECTED.
 PLEASE SEE THE CONTINUOUS LOADS WHICH ARE NOTED ON MANY
 OF THE PANEL SCHEDULES ARE NOT SHOWN FIGURED INTO THE
 MAIN SERVICE AND THE MSB DOES NOTE OR SHOW ANY
 CONTINUOUS LOADS AT 125%.
 215.3, 230.42, 220 ETC.
  
 43) NOTE: PLEASE KNOW PLANS WILL BE ROUTED TO
 ADDRESSING AS THIS IS A NEW BUILDING WHICH IS NOT THE
 SAME AS THE EXISTING BUILDING ON THE SAME SITE. BOTH
 BUILDINGS CAN NOT HAVE THE SAME ADDRESS.
 PLEASE ADJUST TITLE BLOCKS AS NEEDED ONCE THE ADDRESS
 HAS BEEN DETERMINED.
 FAC 61G1-16.004, 61G15-23.002.
  
 ** PLEASE SEE ONE SET OF PLANS CONTAINS MANY AREAS
 NOTED AND REDLINED IN AREAS OF NOTES.
  
 *** PLEASE KNOW AS THERE ARE SEVERAL DESIGN CHANGES
 REQUIRED AND THERE ARE NUMEROUS ITEMS ON PLANS WHICH
 ARE NOT COMPLETE THERE MAY VERY WELL BE NEW COMMENTSON
 THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2007-07-03 07:01:402007-02-03 07:01:40
 REVIEW CONTINUED.
2007-07-02 20:03:302007-07-02 20:03:30
 REVIEW STOPPED, REVIEW TO CONTINUE AND NOTES TO FOLLOW.
2007-07-02 18:38:372007-07-02 18:38:37
 PLANS REMOVED FROM INCOMING AND ONE ROLL IN ELEC FOR
 REVIEW. PLANS WILL BE RETURNED BACK TO INCOMING WAITING
 FOR COMM BOARD ONCE REVIEW HAS BEEN COMPLETED.

Review Stop ENG ENGINEERING CSD
Rev No 6 Status N Date 2009-10-23 Cont ID  
Sent By mgonzale Date 2009-10-23 Time 07:52 Rev Time 0.50
Received By mgonzale Date 2009-10-23 Time 07:52 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 5 Status N Date 2009-06-16 Cont ID  
Sent By dlauderm Date 2009-06-16 Time 13:08 Rev Time 0.00
Received By dlauderm Date 2009-06-16 Time 13:08 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2009-01-14 Cont ID  
Sent By efabian Date 2009-01-14 Time 13:54 Rev Time 0.00
Received By efabian Date 2009-01-14 Time 13:53 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2008-08-28 Cont ID  
Sent By rchokshi Date 2008-08-28 Time 13:32 Rev Time 0.00
Received By rchokshi Date 2008-08-28 Time 13:32 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-01-09 Cont ID  
Sent By rchokshi Date 2008-01-09 Time 11:21 Rev Time 0.00
Received By rchokshi Date 2008-01-03 Time 08:58 Sent To  
Notes
2008-01-09 11:21:08ENG PASSED.
 ENG DRAWINGS & PACKAGE WILL BE STAMPED & SIGNED LATER
 ALONG WITH ALL OTHER TRADES.
 DEWEY P. JUST MENTIONED THAT DRAWINGS WILL BE REVISED
 FOR OTHER TRADES & HE IS GOING TO CALL FOR PICK UP.
 CIVIL DESIGN IS REQUESTED TO RESUBMIT THE ENG DWGS &
 ALL OTHER SUPPORTING PACKAGE WITH LATEST REVISION FOR
 FINAL STAMPS FOR ENG APPROVAL. 3 COPIES REQUESTED.
  
 RASIK CHOKSHI805-6723
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-08-16 Cont ID  
Sent By rchokshi Date 2007-08-16 Time 14:33 Rev Time 0.00
Received By rchokshi Date 2007-08-16 Time 14:10 Sent To  
Notes
2007-08-16 14:33:30***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE PER CITY OF WPB, LOCATION MUST BE
 ACCESSIBLE FOR PICKUP TRUCK.
 3. PLEASE SHOW IN YOUR CALCULATION HOW DID YOU
 DETERMINR FIRST FLOOR ELEVATION, PARKING LOT ELEVATION
 USING CENTER LINE OF ROAD , SIDEWALK ELEVATION, FLOOD
 ZONE AREA OF THIS SITE, & 5,10, 25, 100 YEAR FLOOD
 CRITERIATO DETERMINE THE FIRST FLOOR ELEVATION.
 PLEASE PROVIDE CALCULATIONS.
 4. PLEASESHOW ON DRAWING THE TOTAL SITE AREA,
 PERVIOUS AREA, IMPERVIOUS AREA, LAKE AREA, GREEN AREA,
 PARKING/SIDEWALK AREA, BUILDING AREA ETC.ALSO PROVIDE
 WATER QUALITY CALCULATIONS FOR THIS SITE
 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, FROM YOUR CALCULATIONS.DO
 YOU HAVE EXFILTRATION TRENCHES? . PLEASE SHOW DRY
 DETENTION/WET DETENTION AREAS IN YOUR CALS.
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND
 YOUR SITE EVENTHOUGH THEY ARE NOT IN YOUR SITE.
 7. PLEASE PROVIDE A COPY OF SFWMD OR NPBID PERMIT,, A
 COPY OF GEO-TECH REPORT AND A LATESTEST COPY OF STORM
 STORM WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT
 45TH STREET.
 8. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 SILT FENCE AROUND THE WHOLE SITE & CATCH BASINS NOT
 PARTIALLY OPEN.HEIGHT OF FENCE SHOULD BE HIGH ENOUGH
 PER FDEP TO STOP DUST & PARTICLES.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-11-10 Cont ID  
Sent By mawillia Date 2009-11-10 Time 11:40 Rev Time 0.00
Received By mawillia Date 2009-11-10 Time 11:08 Sent To  
Notes
2009-11-10 11:12:35 
 *****REVISION APPROVED*****
  
  
 OF THE SUBMITTED REVISED SHEETS, A-100, A-400, FP-102,
 AND FP-103 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-07-06 Cont ID  
Sent By mawillia Date 2009-07-06 Time 11:18 Rev Time 0.00
Received By mawillia Date 2009-07-06 Time 10:44 Sent To  
Notes
2009-07-06 11:10:41*****REVISION, DATED/PRINTED APR.'09, APPROVED*****
  
  
 OF THE SUBMITTED REVISED SHEETS, A-100, A-400, AND
 A-900 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-01-20 Cont ID  
Sent By mawillia Date 2009-01-20 Time 15:01 Rev Time 0.00
Received By mawillia Date 2009-01-20 Time 12:26 Sent To  
Notes
2009-01-20 15:05:51*****REVISIONS APPROVED*****
  
  
 REVISED PLAN SHEETS LS-001 & LS-002, A-122, A-400,
 FP-001 THRU FP-201, E101 THRU E104, AND E201 THRU E204
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-09-03 Cont ID  
Sent By mwennerg Date 2008-09-03 Time 15:35 Rev Time 0.00
Received By mwennerg Date 2008-09-03 Time 15:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-06-05 Cont ID  
Sent By mwennerg Date 2008-06-05 Time 10:21 Rev Time 0.00
Received By mwennerg Date 2008-06-05 Time 10:21 Sent To  
Notes
2008-06-05 10:55:06***DENIED***
  
 IT APPEARS THAT THE PLANS ARE CODE COMPLIANT. PLEASE
 SEE THE FOLLOWING COMMENTS:
  
 6) OK
  
 7) CITY OF WEST PALM BEACH PROPERTY SHALL HAVE A CITY
 APPROVED KNOX BOX INSTALLED FOR EMERGENCY RESPONSES AS
 CLARRIFICATION.
  
 16) THIS WRITER HAS HAD NO COMMUNICATION REGARDING FLOW
 DATA INFORMATION. IF THIS PROJECT IS IN THE CITY LIMITS
 OF WEST PALM BEACH, A FLOW TEST SHALL BE CONDUCTED BY
 WEST PALM BEACH FIRE RESCUE PRIOR TO PERFORMING FIRE
 SPRINKLER WORK UNDER A SEPARATE PERMIT.
  
 17) ADD COMMENT TO SEPARATE SHOP DRAWINGS WHEN APPLYING
 FOR FIRE SPRINKLER PERMIT.
  
 PLANS CAN BE STAMPED WHEN RETURNED WITH CORRECTIONS FOR
 OTHER REVIEW COMMENTS IF FIRE COMMENTS #7 AND #16 HAVE
 BEEN SATISFIED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-02-27 Cont ID  
Sent By mawillia Date 2008-02-27 Time 17:56 Rev Time 0.00
Received By mawillia Date 2008-02-27 Time 16:23 Sent To  
Notes
2008-02-27 17:56:44*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 06.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.ADD COMMENT TO THE FIRE ALARM
 NOTES
  
 07.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. SHOW
 THE LOCATION OF THE KNOX BOX IN AN ACCESSIBLE LOCATION
 ON THE APPROPIATE EXTERIOR ELEVATION..FOR
 APPLICATIONS, CONTACT WPB FIRE PREVENTION BUREAU AT
 561-804-4724.ANY INQUIRIES AND/OR REQUIREMENTS TO
 THIS MATTER SHALL BE WITH THE AHJ = CITY OF WEST PALM
 BEACH, NOT PALM BEACH COUNTY
  
 15.IN ADDITION TO THE ELECTRONIC SWITCHES FOR THE
 DOUBLE CHECK DETECTOR ASSEMBLY (DCDA), CHAIN AND LOCK
 WILL BE REQUIRED.ADD COMMENT TO AN APPROPIATEFP
 SHEET
  
 16.FLOW TEST DATA (03/28/07) WAS GATHERED BY PALM
 BEACH COUNTY FIRE DEPARTMENT.IF THIS PROJECT IS TRULY
 IN THE JURISDICTION OF THE CITY OF WEST PALM BEACH, WHY
 WASN'T THE DATA SUPPLIED BY WEST PALM BEACH FIRE
 RESCUE'S PREVENTION DIVISION.ANY INQUIRIES AND/OR
 REQUIREMENTS TO THIS MATTER SHALL BE WITH THE AHJ =
 CITY OF WEST PALM BEACH, NOT PALM BEACH COUNTY
  
 17.KNOX LOCKING CAPS WILL BE REQUIRED ON THE FIRE
 DEPARTMENT CONNECTIONS (FDC).CONTACT 561-804-4724 FOR
 APPLICATIONS.ANY INQUIRIES AND/OR REQUIREMENTS TO
 THIS MATTER SHALL BE WITH THE AHJ = CITY OF WEST PALM
 BEACH, NOT PALM BEACH COUNTY
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By mawillia Date 2007-09-04 Time 23:48 Rev Time 0.00
Received By mawillia Date 2007-09-04 Time 20:00 Sent To AD
Notes
2007-09-04 23:47:02*****DENIED*****
  
 01.ON SHEET G-001 UNDER APPLICABLE CODES, INCLUDE AS
 LIFE SAFETY CODE:NFPA 101 2003 EDITION.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.NFPA 13, STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS, 2002 EDITION SHALL BE REFERENCED.
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM INSTALLATION.
  
 04.NFPA72, NATIONAL FIRE ALARM CODE, 2002 EDITION
 SHALL BE REFERENCED.SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FOR THE FIRE ALARM SYSTEM INSTALLATION.
  
 05.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY
 ADDRESSIBLE.
  
 06.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 07.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. SHOW
 THE LOCATION OF THE KNOX BOX IN AN ACCESSIBLE LOCATION
 ON THE APPROPIATE EXTERIOR ELEVATION..FOR
 APPLICATIONS, CONTACT WPB FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 08.FIRE DOORS AND FIRE WINDOWS TO COMPLY WITH NFPA
 80.
  
 09.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS FOR THE EXITS, EXIT CORRIDORS, AND OTHER
 AREAS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 10.SPECIFY THE INTERIOR FLOOR FINISHES IN TERMS OF
 CLASS I OR CLASS II.
  
 11.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING VISIBLE FROM NORTH
 MILITARY TRAIL.IT IS RECOMMENDED THAT THE FARTHER THE
 BUILDING IS FROM THE ROADSIDE, THAT ADDRESS NUMBERS BE
 LARGER THAN THE DIMENSION OF NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH (AS REQUIRED BY WEST PALM
 BEACH CODE) .IF A MONUMENT SIGN IS TO BE USED,
 ADDRESS NUMBERS SHALL BE POSTED.
  
 12.ON SHEET A-400, INDICATE FRONT AND REAR
 ELEVATIONS.
  
 13.UNABLE TO LOCATE ON SHEET A-500, THE OVERHEAD
 GARAGE DOOR(S) SHOWN ON SHEET A-400'S EAST EXTERIOR
 ELEVATION.
  
 14.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.
  
 15.IN ADDITION TO THE ELECTRONIC SWITCHES FOR THE
 DOUBLE CHECK DETECTOR ASSEMBLY (DCDA), CHAIN AND LOCK
 WILL BE REQUIRED.
  
 16.FLOW TEST DATA (03/28/07) WAS GATHERED BY PALM
 BEACH COUNTY FIRE DEPARTMENT.IF THIS PROJECT IS TRULY
 IN THE JURISDICTION OF THE CITY OF WEST PALM BEACH, WHY
 WASN'T THE DATA SUPPLIED BY WEST PALM BEACH FIRE
 RESCUE'S PREVENTION DIVISION.
  
 17.KNOX LOCKING CAPS WILL BE REQUIRED ON THE FIRE
 DEPARTMENT CONNECTIONS (FDC).CONTACT 561-804-4724 FOR
 APPLICATIONS.
  
 18.PLEASE EXPLAIN THE USAGE OF THE GENERATOR, THE
 TYPE OF FUEL(S) THAT WILL BE UTILIZED, AND THE STORAGE
 OF SUCH FUEL(S) & QUANTITIES STORED.SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED FOR ITS INSTALLATION.
  
 19.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA110.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2009-08-20 Cont ID  
Sent By kstevens Date 2009-08-20 Time 09:44 Rev Time 0.00
Received By kstevens Date 2009-08-20 Time 09:44 Sent To  
Notes
2009-08-20 09:45:07GAS REVISION OK -- P1-103

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2009-06-23 Cont ID  
Sent By kstevens Date 2009-06-23 Time 16:12 Rev Time 0.00
Received By kstevens Date 2009-06-23 Time 16:12 Sent To  
Notes
2009-06-23 16:13:02REVISION DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT P1-103 GAS ISOMETRIC. THE MINIMUM PIPE SIZING IS
 NOT CORRECT ON SOME PIPES. 4" IS REQUIRED, (3,502 MBH @
 125 FEET), FROM THE METER TO THE FIRST TEE. 3" IS
 REQUIRED FOR 2,600 MBH. 2-1/2" IS REQUIRED FOR 1,300
 MBH. 2" IS REQUIRED FOR 902 MBH, (STILL SHOWN AS 750
 MBH). 2" IS REQUIRED FOR 750 MBH, (NO SIZE INDICATED).
 TABLE 402.4(2).
 ****RESPONSE NOTED, BUT THE REQUIREMENT FOR THE 3" PIPE
 FOR 2,600 MBH AND THE REQUIREMENT FOR THE 2-1/2" FOR
 THE 902 MBH HAS NOT BEEN ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-05-28 Cont ID  
Sent By kstevens Date 2008-05-28 Time 15:09 Rev Time 0.00
Received By kstevens Date 2008-05-27 Time 12:38 Sent To  
Notes
2008-08-12 10:19:29SEPARATE GAS PERMIT REQUIRED

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-02-15 Cont ID  
Sent By kstevens Date 2008-02-15 Time 15:00 Rev Time 0.00
Received By kstevens Date 2008-02-14 Time 15:00 Sent To  
Notes
2008-02-28 15:01:26DENIED.--SEE GAS COMMENTS ON PLUMBING PLAN REVIEW
 STOP THIS DATE

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-23 Cont ID  
Sent By kstevens Date 2007-08-23 Time 10:03 Rev Time 0.00
Received By kstevens Date 2007-08-23 Time 10:03 Sent To  
Notes
2007-08-23 16:28:41DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS
 REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (NOT SHOWN FOR GB1
 UNITS).
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2009-11-18 Cont ID  
Sent By lmartine Date 2009-11-18 Time 17:05 Rev Time 0.00
Received By lmartine Date 2009-11-18 Time 17:05 Sent To  
Notes
2009-11-18 17:05:45IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 13:29 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 13:29 Sent To  
Notes
2009-09-02 13:33:12SENT TO FIRE.

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-08-14 Cont ID  
Sent By lmartine Date 2009-08-14 Time 14:18 Rev Time 0.00
Received By lmartine Date 2009-08-14 Time 14:16 Sent To  
Notes
2009-08-14 14:18:15C-1, REVISION DELETING PHASE 2 FROM PHASE 1.

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-07-29 Cont ID  
Sent By lmartine Date 2009-07-29 Time 09:28 Rev Time 0.00
Received By lmartine Date 2009-07-29 Time 09:28 Sent To  
Notes
2009-07-29 09:29:15IN MECH. BOX

Review Stop I INCOMING/PROCESSING
Rev No 13 Status   Date 2009-07-06 Cont ID  
Sent By jwitmer Date 2009-07-06 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2009-06-03 Time 16:22 Sent To  
Notes
2009-06-04 16:30:05REVISION TO C6

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-05-28 Cont ID  
Sent By lmartine Date 2009-05-27 Time 16:35 Rev Time 0.00
Received By lmartine Date 2009-05-27 Time 16:34 Sent To  
Notes
2009-05-28 16:38:32MECHANICAL AS-BUILTS, GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-05-28 Cont ID  
Sent By lmartine Date 2009-05-13 Time 16:34 Rev Time 0.00
Received By lmartine Date 2009-05-13 Time 09:54 Sent To  
Notes
2009-05-13 09:55:05INCOMINGTO MECHANICAL: SHOP DRAWINGS FOR DUCT WORK

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-05-01 Cont ID  
Sent By lmartine Date 2009-05-01 Time 16:57 Rev Time 0.00
Received By lmartine Date 2009-05-01 Time 16:57 Sent To M
Notes
2009-05-01 16:58:27 
  
 TO RON

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-02-02 Cont ID  
Sent By adarroug Date 2009-02-02 Time 10:03 Rev Time 0.00
Received By adarroug Date 2009-02-02 Time 10:03 Sent To B
Notes
2009-02-02 10:05:36TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-01-27 Cont ID  
Sent By adarroug Date 2009-01-27 Time 11:13 Rev Time 0.00
Received By adarroug Date 2009-01-27 Time 11:13 Sent To B
Notes
2009-01-27 11:13:19TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-12-19 Cont ID  
Sent By adarroug Date 2008-12-19 Time 09:27 Rev Time 0.00
Received By adarroug Date 2008-12-19 Time 09:26 Sent To B
Notes
2008-12-19 09:28:36TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-12 Cont ID  
Sent By adarroug Date 2008-12-12 Time 15:02 Rev Time 0.00
Received By adarroug Date 2008-12-12 Time 15:02 Sent To  
Notes
2008-12-12 15:07:55TO "COMM" BD#5/PLANS ON RACK/3 ROLLS/1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 13:13 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 13:13 Sent To  
Notes
2008-08-04 13:14:33TO "COMM" BD#52/PLANS ON RACK, 4 ROLLS AND 1 BOX
2008-07-30 13:36:527/30/08 PLANS NEED TO BE SENT TO "Z" FOR LANDSCAPE
 REVIEW.ADARROUGH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 16:23 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 16:23 Sent To  
Notes
2008-05-13 16:28:49TO "COMM" BD#8--PLANS ON RACK/4 ROLLS, AND 1 BOX WITH
 BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-17 Cont ID  
Sent By adarroug Date 2008-01-17 Time 11:22 Rev Time 0.00
Received By adarroug Date 2008-01-17 Time 11:22 Sent To  
Notes
2008-01-17 11:26:08TO "COMM" BD#55/PLANS ON RACK--4 ROLLS, 1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-31 Cont ID  
Sent By spalmer Date 2007-12-31 Time 09:35 Rev Time 0.00
Received By spalmer Date 2007-12-31 Time 09:35 Sent To  
Notes
2007-12-31 09:36:03TO COMM BOARD # 22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-05 Cont ID  
Sent By mawillia Date 2007-09-05 Time 15:46 Rev Time 0.00
Received By mawillia Date 2007-06-24 Time 12:57 Sent To  
Notes
2007-07-09 14:34:10TO "COMM"BD#22/PLANS ON RACK--3 ROLLS
2007-06-24 12:57:45WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 5 Status P Date 2009-11-20 Cont ID  
Sent By rkussner Date 2009-11-20 Time 15:56 Rev Time 0.00
Received By rkussner Date 2009-11-20 Time 15:56 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 4 Status P Date 2009-10-20 Cont ID  
Sent By rkussner Date 2009-10-20 Time 16:21 Rev Time 0.00
Received By rkussner Date 2009-10-20 Time 13:50 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-06-09 Cont ID  
Sent By rkussner Date 2009-06-09 Time 11:20 Rev Time 0.00
Received By rkussner Date 2009-06-09 Time 11:20 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-08-06 Cont ID  
Sent By rkussner Date 2008-08-06 Time 09:25 Rev Time 0.00
Received By rkussner Date 2008-08-06 Time 09:25 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By rkussner Date 2008-02-19 Time 15:17 Rev Time 0.00
Received By rkussner Date 2008-02-19 Time 15:17 Sent To  
Notes
2008-02-19 15:24:041. A NOTE INDICATING THAT ALL PROHIBITED PLANT SPECIES
 SHALL BE REMOVED FROM THE DEVELOPMENT SITE SHALL APPEAR
 ON THE LANDSCAPE PLAN.
  
 2. PURSUANT TO SECTION 94-442(D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE SHALL BE PLANTED WITH GRASS. THIS APPLIES TO ALL
 RIGHTS-OF-WAY THAT ARE ADJACENT TO THE SITE. A NOTE
 SHALL APPEAR ON THE LANDSCAPE PLAN.
  
 3. ALL FENCING ADJACENT TO A RIGHT-OF-WAY SHALL BE
 INSTALLED ALONG THE INSIDE PERIMETER OF THE LANDSCAPE
 SETBACK WITH THE LANDSCAPING INSTALLED ON THE STREET
 SIDE OF THE FENCE. THIS APPLIES TO 12TH STREET AND
 MILITARY TRAIL.
  
 4. SITE LIGHTING SHALL BE CENTERED BETWEEN PROPOSED
 TREES. ALL CONFLICTS BETWEEN PROPOSED STREET LIGHTS AND
 TREES SHALL BE RESOLVED PRIOR TO PERMITTING.

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2009-11-04 Cont ID  
Sent By rregueir Date 2009-11-04 Time 09:29 Rev Time 0.00
Received By rregueir Date 2009-11-04 Time 08:31 Sent To  
Notes
2009-11-04 09:28:51REVISED M1-102 DELTA 10, M1-103 DELTA 11, M1-105 DELTA
 10, M1-106 DELTA 10
  
  

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2009-08-04 Cont ID  
Sent By rregueir Date 2009-08-04 Time 16:44 Rev Time 0.00
Received By rregueir Date 2009-08-04 Time 16:44 Sent To PC
Notes
2009-08-04 16:44:59REVISED M1-105 DELTA 9

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2009-07-20 Cont ID  
Sent By rregueir Date 2009-07-20 Time 20:36 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 20:35 Sent To PC
Notes
2009-07-20 20:36:46REVISED M1-101 THRU M1-106, M2-101, M3-101, M5-103

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-07-14 Cont ID  
Sent By rregueir Date 2009-07-14 Time 13:20 Rev Time 0.00
Received By rregueir Date 2009-07-14 Time 13:19 Sent To PC
Notes
2009-07-14 13:20:44REVISION M1-101, M1-102, M1-103, M1-201 DELTA 9...
 REVISION M1-104, M1-105, M1-106 DELTA 8

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2009-06-03 Cont ID  
Sent By dwise Date 2009-06-03 Time 15:59 Rev Time 0.00
Received By dwise Date 2009-06-03 Time 15:59 Sent To  
Notes
2009-06-03 16:04:15ACCEPTED INTERIM RECORD OF "AS-BUILT" CONDITION FOR USE
 IN CONDUCTING ROUGH INSPECTIONS WITH THE FOLLOWING
 PROVISIONS:
 1. APPLICANT IS RESPONSIBLE TO PROVIDE A MATCHING
 REVISION WHICH IS SIGNED AND SEALED BY THE EOR FOR
 REVIEW AND ACCEPTANCE PRIOR TO REQUESTING A FINAL
 MECHANICAL INSPECTION.
 2. INTERIM PLAN SHALL BE VALID FOR ONLY ROUGH
 INSPECTIONS
 3. APPLICANT AGREED TO PROCEED AT THEIR OWN RISK AND
 WILL CORRECT ANY DISCREPANCIES WHICH ARE NOT APPROVED
 BY THE EOR.
 4. AN APPROVED CITY COPY OF THE EOR REVISION SHALL BE
 ON SITE FOR FINAL MECHANICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2009-05-29 Cont ID  
Sent By rregueir Date 2009-05-29 Time 10:37 Rev Time 0.00
Received By rregueir Date 2009-05-29 Time 08:18 Sent To PC
Notes
2009-05-29 10:37:19M1-101, M1-102, M1-103, M2-101 REVISION 8

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2009-05-05 Cont ID  
Sent By rregueir Date 2009-05-05 Time 09:44 Rev Time 0.00
Received By rregueir Date 2009-05-05 Time 09:38 Sent To PC
Notes
2009-05-05 09:44:27REVIEW #: REVISION
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS SUBMITTED ARE LABELED AND STAMPED AS "SHOP
 DRAWINGS." HOWEVER, THESE DRAWINGS INDICATE SEVERAL
 CHANGES FROM THE PREVIOUSLY APPROVED CONSTRUCTION
 DOCUMENTS (PERMIT SET OF PLANS). WORK SHALL BE
 INSTALLED IN ACCORDANCE WITH THE APPROVED CONSTRUCTION
 DOCUMENTS, AND ANY CHANGES MADE DURING CONSTRUCTION
 THAT ARE NOT IN COMPLIANCE WITH THE APPROVED
 CONSTRUCTION DOCUMENTS SHALL BE RESUBMITTED FOR
 APPROVAL AS AN AMENDED SET OF CONSTRUCTION DOCUMENTS IN
 ACCORDANCE WITH FBC-B 106.4. PLEASE SUBMIT A REVISED
 SET OF PLANS SIGNED AND SEALED BY THE DESIGNER OF
 RECORD TO DOCUMENT THESE CHANGES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-01-20 Cont ID  
Sent By rregueir Date 2009-01-20 Time 08:05 Rev Time 0.00
Received By rregueir Date 2009-01-20 Time 08:01 Sent To  
Notes
2009-01-20 08:04:17REVISED ENTIRE SET OF MECHANICAL PLANS. REV 6.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-25 Cont ID  
Sent By rregueir Date 2008-08-25 Time 09:22 Rev Time 0.00
Received By rregueir Date 2008-08-22 Time 13:28 Sent To  
Notes
2008-08-25 09:22:56*************PROVISO**************
  
 DOCUMENTATION FROM APPLIANCE MANUFACTURER SHALL BE
 PROVIDED SHOWING ALL OUTDOOR APPLIANCES WHICH ARE
 EXPOSED TO WIND ARE DESIGNED TO RESSIST WIND PRESSURES
 IN ACCORDANCE WITH FBCM SECTION 301.13. THIS
 INFORMATION SHALL BE SUBMITTED FOR PLAN REVIEW PRIOR TO
 INSTALLATION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-05-29 Cont ID  
Sent By rregueir Date 2008-05-29 Time 14:14 Rev Time 0.00
Received By rregueir Date 2008-05-28 Time 16:56 Sent To  
Notes
2008-05-29 14:14:35REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1-5: OK
  
 6A ? 6C: OK
  
 6D: A SYSTEM SIZING SUMMARY HAS BEEN PROVIDED IN LIEU
 OF COOLING LOAD CALCULATIONS AS ALLOWED UNDER EXCEPTION
 #1 OF FBCB 13-407.1.ABC.1. HOWEVER, THIS EXCEPTION
 REQUIRES THAT THE SYSTEM SIZING SUMMARY BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL. THE SYSTEM SIZING
 SUMMARY WHICH WAS SUBMITTED IN RESPONSE TO THIS COMMENT
 WAS NOT SIGNED AND SEALED. PLEASE CORRECT AND
 RESUBMIT.
  
 7. OK. LOUVERS INCLUDED IN PRODUCT APPROVAL PACKAGE AND
 WILL BE REVIEWED BY BUILDING PLAN REVIEWER.
  
 8-15: OK
  
 16. FAN SCHEDULE ON PAGE M3-103 STILL CALLS FOR EF81
 AND EF 83 TO BE CONTROLLED BY LIGHT SWITCH RATHER THAN
 INTERLOCKED WITH AH4 AS INDICATED IN WRITTEN RESPONSE
 (DATED 3/14/08) TO PREVIOUS REVIEW COMMENT (DATED
 2/7/08) . PLEASE CORRECT AND RESUBMIT. FBCM 403.2.1.
  
 17. OK
  
 18. FAN SCHEDULE ON M3-103 STILL CALLS FOR EF84 TO BE
 CONTROLLED BY WALL SWITCH RATHER THAN RUN CONTINUOUS AS
 STATED IN WRITTEN RESPONSE (DATED 3/14/08) TO PREVIOUS
 REVIEW COMMENT (DATED 2/7/08). FBCM 404.
  
 19. OK
  
 20. ATTACHMENT DETAILS WITH SUPPORTING CALCULATIONS
 HAVE BEEN PROVIDED AND WILL BE REVIEWED BY THE BUILDING
 PLAN REVIEWER. HOWEVER, NO INFORMATION WAS PROVIDED, AS
 PREVIOUSLY REQUESTED, DEMONSTRATING THAT THE OUTDOOR
 APPLIANCES ARE DESIGNED TO WITHSTAND ANTICIPATED WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 21 AND 22: OK
  
 23. THE THROUGH-PENETRATION FIRESTOP DETAILS PROVIDED
 ON PAGE M4-104 DO NOT INCLUDE ANY PENETRATING PIPES
 WHICH ARE INSULATED. WHAT SYSTEM IS TO BE USED FOR
 INSULATED PIPE?
  
 24. OK
  
 25. GENERATOR INFORMATION: PAGE E-203 INDICATES AN 840
 GALLON IN-BASE FUEL TANK IS TO BE USED. THE FOLLOWING
 ISSUES NEED TO BE ADDRESSED:
 A) AS STATED IN FIRST AND SECOND REVIEWS, PROPOSED
 ABOVE GROUND FUEL STORAGE TANKS WITH A FUEL STORAGE
 CAPACITY IN EXCESS OF 550 GALLONS SHALL BE SUBMITTED TO
 PALM BEACH COUNTY DERM FOR APPROVAL PRIOR TO PERMIT
 ISSUANCE. NO INFORMATION WAS PROVIDED WITH THIS
 SUBMITTAL INDICATING THAT THE PROPOSED FUEL TANK AND
 LOCATION HAVE BEEN APPROVED BY DERM. PBC DERM APPROVED
 PLANS SHALL BE INCLUDED WITH EACH SET OF PLANS
 SUBMITTED TO THIS JURISDICTION FOR PERMIT. SEE ORIGINAL
 COMMENT #25 (DATED 7/23/07) FOR PBC DERM CONTACT
 INFORMATION.
  
 B) THE SUBMITTAL PROVIDED FOR THE GENERATOR FUEL TANK
 INDICATES THAT THE MAXIMUM CAPACITY FOR AN IN-BASE FUEL
 TANK (WHICH IS SHOWN ON E-203) 77 GALLONS. THERE IS NO
 840 GALLON IN-BASE TANK OPTION, AS INDICATED ON PLANS,
 IN THE SUBMITTAL FROM THE MANUFACTURER. PLEASE VERIFY
 THE TYPE OF TANK TO BE USED AS WELL AS A CAPACITY FOR
 THE TANK WHICH CORRESPONDS WITH THE MANUFACTURER?S
 SUBMITTAL DATA.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-13 Cont ID  
Sent By rregueir Date 2008-02-13 Time 07:43 Rev Time 0.00
Received By rregueir Date 2008-02-11 Time 18:28 Sent To  
Notes
2008-02-13 07:43:31REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1 THROUGH 5: OK
  
 6. THIS IS THE FIRST REVIEW OF THE ENERGY CALCULATIONS
 AS THEY WERE NOT INCLUDED WITH THE ORIGINAL SUBMITTAL.
 THE FOLLOWING DISCREPANCIES WERE FOUND IN THE ENERGY
 CALCULATIONS:
 A) THE DESIGN IPLV ON THE PLANT PORTION OF THE INPUT
 DATA REPORT (IDR) DOES NOT CORRESPOND WITH THE IPLV ON
 THE EQUIPMENT SCHEDULE. ADDITIONALLY, THE DATA IN THE
 EQUIPMENT SCHEDULE DOES NOT CORRESPOND WITH THE
 MANUFACTURER?S DATA FROM THEIR WEBSITE (WWW.TRANE.COM).
  
 B) THE IDR CALLS FOR 1.5 INCH THICK INSULATION ON
 DOMESTIC HOT WATER PIPING, BUT THE SPECIFICATIONS
 (SEC.15250) CALL FOR 1 INCH THICK INSULATION.
 C) THE IDR CALLS FOR 2 INCH THICK INSULATION ON 2 INCH
 CHILLED WATER HVAC PIPING AND THE SPECIFICATIONS
 (SEC.15250) CALL FOR 1.5 INCH THICK INSULATION.
 THE VALUES IN THE IDR SHALL MATCH THE VALUES ON THE
 PLANS AND SPECIFICATIONS IN ACCORDANCE WITH FBC
 13-103.2
 D) COOLING LOAD CALCULATIONS FOR THE PURPOSE OF SYSTEM
 SIZING SHALL BE APPENDED TO THE ENERGY CALCULATIONS IN
 ACCORDANCE WITH FBC 13-407.1.ABC.1.
  
 7. NO CUT SHEETS WERE FOUND IN THE PACKAGE SUBMITTED.
 ALSO, NO LOUVERS WERE PROVIDED IN THE PRODUCT APPROVAL
 BOOKLET. WALL LOUVERS ARE DEFINED AS PANEL WALLS PER
 FAC RULE 9B-72 AND ARE SUBJECT TO THE FLORIDA PRODUCT
 APPROVAL SYSTEM. PRODUCT APPROVALS SHALL BE APPROVED IN
 WRITING BY THE DESIGNER OF RECORD AND SUBMITTED PRIOR
 TO PERMIT IN ACCORDANCE WITH FBC 106.3.3
  
 8 ? 13: OK
  
 14. A 100% OUTSIDE AIR DUCT HAS BEEN ADDED TO AREA
 SERVED BY BC-1. HOWEVER, THERE IS AN 8 INCH FLEX DUCT
 SHOWN ON FLOOR PLAN, PAGE M1-102, WHICH IS PENETRATING
 A TWO-HOUR FIRE RESISTANCE RATED WALL. SEE PAGE
 LS-001SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN
 ACCORDANCE WITH FBC, M 607.5.2.
  
 15. OK
  
 16. THERE IS NO INDICATION ON PLANS AS TO HOW THIS
 COMMENT WAS ADDRESSED. FAN SCHEDULE ONLY CALLS FOR
 INTERLOCK WITH THE LIGHT SWITCH. WHAT PROVISIONS ARE
 MADE TO ENSURE THE EFS ARE RUNNING WHENEVER BC-1 IS
 RUNNING? SHOW COMPLIANCE WITH FBC, M 403.2.1(3).
  
 17. THERE IS STILL A DETAIL FOR A DRYWELL ON PAGE
 M4-101. WILL THERE STILL BE A DRYWELL AS PART OF THE
 CONDENSATE DISPOSAL SYSTEM?
  
 18. FAN SCHEDULE CALLS FOR EF84 TO BE CONTROLLED BY
 WALL SWITCH. MECHANICAL VENTILATION SYSTEMS FOR
 ENCLOSED PARKING GARAGES ARE NOT REQUIRED TO OPERATE
 CONTINUOUSLY WHERE THE SYSTEM IS ARRANGED TO OPERATE
 AUTOMATICALLY UPON DETECTION OF A CONCENTRATION OF
 CARBON MONOXIDE OF 25 PARTS PER MILLION (PPM) BY
 APPROVED AUTOMATIC DETECTION DEVICES IN ACCORDANCE WITH
 FBC, M 404.1. IN LIEU OF BEING CONTROLLED BY APPROVED
 CARBON MONOXIDE SENSOR(S) THE VENTILATION FAN FOR THE
 SALLY PORT SHALL OPERATE CONTINUOUSLY AT A MINUM RATE
 OF 1.5 CFM PER SQUARE FOOT IN ACCORDANCE WITH THIS
 SECTION. AUTOMATIC OPERATION OF THE SYSTEM SHALL NOT
 REDUCE THE CONTINUOUS VENTILATION RATE BELOW0.05 CFM
 PER SQUARE FOOT OF THE FLOOR AREA AND THE SYSTEM SHALL
 BE CAPABLE OF PRODUCING A VENTILATION RATE OF 1.5 CFM
 PER SQUARE FOOT OF FLOOR AREA IN ACCORDANCE WITH FBC, M
 404.2 SHOW HOW THE CONTINUOUS OR VARIABLE RATES ARE TO
 BE PROVIDED. IF A CARBON MONOXIDE DETECTION SYSTEM IS
 EMPLOYED, SHOW LOCATION(S) OF DETECTOR(S) AND PROVIDE
 MANUFACTURER?S SUBMITTAL AND INSTALLATION INSTRUCTIONS
 FOR REVIEW. FBC 106.1.2.
  
 19. OK
  
 20. NO INFORMATION COULD BE FOUND IN STRUCTURAL PLANS
 RELATED TO WIND LOADS OR ATTACHMENTS FOR MECHANICAL
 EQUIPMENT AND APPLIANCES. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING PER
 FBC, M 301.13. PLEASE NOTE THAT THIS CODE REQUIREMENT
 NOT ONLY APPLIES TO ATTACHMENTS BUT TO THE EQUIPMENT
 AND APPLIANCES THEMSELVES. IT INCLUDES BUT IS NOT
 LIMITED TO ERUS, EXHAUST FANS, OUTSIDE AIR INTAKES AND
 CHILLERS. PROVIDE DATA SHOWING EQUIPMENT, APPLIANCES
 AND INSTALLATION METHODS SUFFICIENT TO WITHSTAND
 ANTICIPATED WIND PRESSURES WITH SUPPORTING CALCULATIONS
 TO DEMONSTRATE COMPLIANCE WITH THIS SECTION.
  
 21 AND 22: OK
  
 23. NO DETAIL OF ANY THROUGH-PENETRATION FIRESTOP
 SYSTEM FOR PIPE PENETRATIONS OF FIRE-RESISTANCE RATED
 ASSEMBLIES COULD BE FOUND ON PG P4-101 AS SPECIFIED IN
 DESIGNER?S WRITTEN RESPONSE. THIS COMMENT HAS NOT BEEN
 ADDRESSED. SHOW COMPLIANCE WITH FBC 712.3 AND 712.4.
  
 24. OK
  
 25. THIS COMMENT REMAINS ESSENTIALLY UNADDRESSED. AS
 LONG AS THE GENERATOR IS SHOWN AS PART OF THIS PERMIT
 APPLICATION, ALL RELEVANT INFORMATION (SEE PREVIOUS
 REVIEW COMMENT #25) SHALL BE PROVIDED PRIOR TO PERMIT
 ISSUANCE.
 NOTE: ADDITIONAL COMMENTS ARE POSSIBLE DUE TO THE LACK
 OF INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By rregueir Date 2007-07-26 Time 09:55 Rev Time 0.00
Received By rregueir Date 2007-07-23 Time 16:53 Sent To  
Notes
2007-07-25 17:59:10--------------DENIED---------------
  
 FBC 2004 CODE FAMILY WITH 2005 AND 2006 REVISIONS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: LOCATIONS ON PLANS RELATED TO THE FOLLOWING
 COMMENTS WERE MARKED ON ONE SET OF PLANS, WHEN
 PRACTICAL, TO HELP CLARIFY THE NATURE AND LOCATION OF
 THE COMMENTS.
  
 1. M0-101: GENERAL NOTE 1(M) REFERENCES ASHRAE 62-01.
 AS OF DECEMBER 8,2006 THE CORRECT STANDARD IS ASHRAE
 62.1-2004. FBC,M CH.15. PLEASE CORRECT.
  
 2. M0-101: GENERAL NOTE 7 IS IN CONFLICT WITH
 CONDENSATE DRAIN TRAP DETAIL ON M4-101. IS TRAP TO BE
 AT STATIC +1" OR STATIC +2"? CONDENSATE DRAINS SHALL BE
 TRAPPED AS REQUIRED BY THE EQUIPMENT OR APPLIANCE
 MANUFACTURER. FBC,M 307.2.4
  
 3. M0-101: HVAC LEGEND SHOWS AN "OPTION" FOR FIRE
 DAMPERS. FIRE DAMPER EXCEPTIONS HAVE CHANGED AND THE "5
 FOOT RULE" NO LONGER APPLIES. SEE FBC,M 607.5 FOR
 REQUIREMENTS. THE UPDATED EXCEPTIONS DO NOT APPLY TO
 2-HOUR ASSEMBLIES AS ARE INDICATED ON LIFE SAFETY PLAN.
 ALSO, PLANS SHALL CLEARLY INDICATE WHERE FIRE DAMPERS
 ARE TO BE INSTALLED PER FBC,M 607.8. PLEASE REMOVE
 "OPTIONAL" NOTES FROM PLANS AND INSTEAD SHOW ON PLANS
 WHERE FIRE DAMPERS ARE REQUIRED AND TO BE INSTALLED.
 ALSO SEE FBC 106.1.1.
  
 4. M0-102: ASHRAE 62-2001 IS NOT CORRECT. SEE COMMENT
 #1.
  
 5. M0-102: AH1-AH4 AND AH7, PLEASE PROVIDE MISSING
 INFORMATION ON SCHEDULES REGARDING ACTUAL REQUIRED
 QUANTITIES (CFM/PERSON OR CFM/SQ FT WITH TOTAL FOR EACH
 SPACE) OF OUTDOOR AIR, EVEN IF THE SYSTEM IS DESIGNED
 TO SUPPLY FAR IN EXCESS OF THE MINIMUM REQUIREMENT. THE
 SCHEDULES, AS SHOWN, DO OT CONTAIN ACCURATE
 INFORMATION. EXAMPLE: AH7 IN LOBBY 301, SCHEDULE
 INDICATES 8070 CFM OUTDOOR AIR IS REQUIRED.
 NOTE: 13-409.1.ABC.1.1 VENTILATION SYSTEMS SHALL BE
 DESIGNED TO BE CAPABLE OF REDUCING THE SUPPLY OF
 OUTDOOR AIR TO THE MINIMUM VENTILATION RATES REQUIRED
 BY SECTION 6.1.3 OF ASHRAE 62. SYSTEMS MAY BE DESIGNED
 TO SUPPLY OUTSIDE AIR QUANTITIES EXCEEDING MINIMUM
 LEVELS, BUT THEY SHALL BE CAPABLE OF OPERATING AT NO
 MORE THAN MINIMUM LEVELS THROUGH THE USE OF RETURN
 DUCTS, MANUALLY OR AUTOMATICALLY OPERATED CONTROL
 DAMPERS, FAN VOLUME CONTROLS, OR OTHER DEVICES.
  
 6. PROVIDE ENERGY CALCULATIONS AND ALL REQUIRED
 ACCOMPANYING DOCUMENTATION. FBC 106.3.5, FBC
 13-400.0.ABC, FBC 13-400.3.ABC.2
  
 7. PROVIDE ALL REQUIRED SUBMITTALS FOR LISTED AND
 LABELED EQUIPMENT AND MATERIALS SUCH AS AHUS, CHILLERS,
 VAVS, FANS, PUMPS, ERVS, VALVES, FITTINGS, HEAT COILS.
 PRODUCT APPROVAL IS REQUIRED FOR LOUVERS PER FAC RULE
 9B-72.
  
 8. M1-101: DUCT SIZES ARE MISSING ON TWO EXHAUST DROPS
 ON ERU 81. PLEASE CORRECT.
  
 9. M1-101: ARE ERU81 AND ERU82 BOTH FEEDING AH7 THROUGH
 THE SAME DUCT? IT APPEARS THAT THE OA RISER DUCT FOR
 ERU82 IS INCORRECTLY MARKED AS THE RETURN/EXHAUST GRILL
 IN THE CEILING ABOVE THE RECEPTION DESK.
  
 10. M1-101: ERU81 AND 82 ARE BOTH FEEDING AH7.
 ACCORDING TO CONTROL SEQUENCE DIAGRAM ON M5-101, AH AND
 ERU DESIGNATION NUMBERS SHOULD CORRELATE. IT IS UNCLEAR
 WHETHER AH7 AND AH* OR ERU81 AND ERU 82 ARE MISLABELED.
 CONTROL DIAGRAM IDENTIFIES AH8 AS A 100% OA UNIT IN ONE
 PLACE BUT INDICATES AH7 AS THE SAME IN ANOTHER. PLEASE
 COORDINATE ALL THESE ISSUES SO PLANS, SCHEDULES AND
 CONTROL DIAGRAMS CORRELATE.
  
 11. M1-102: ON FLOOR PLANS, AH6 IS IN A MECHANICAL ROOM
 ON FIRST FLOOR AND AH8 IS IN A STORAGE ROOM. HOWEVER,
 ON EQUIPMENT SCHEDULE, BOTH ARE SHOWN TO BE ON THE
 MEZANNINE LEVEL. PLEASE COORDINATE FLOOR PLANS AND
 SCHEDULES.
  
 12. M1-102: AH6 SUPPLY DUCT, LOCATION OF TRANSITION
 BETWEEN 34X18 AND 34X16 DUCT IS NOT SHOWN. PLEASE
 CLARIFY.
  
 13. SMOKE DETECTORS ARE REQUIRED ON ALL SUPPLY, OUTSIDE
 AIR AND EXHAUST DUCTS RELATED TO AH1, AH2, AH3, AH4 AND
 AH7 PER FBC,M 607.2.2. ALSO ON SUPPPLY SIDE OF AH5, AH6
 AND BC-1 PER FBC,M 606.2.1. SOME ARE SHOWN ON PLANS AND
 OTHERS ARE NOT. PLEASE SHOW LOCATION OF ALL DUCT SMOKE
 DETECTORS. FBC 106.1.1
  
 14. PROVIDE VENTILATION INFORMATION FOR AREA BEING
 SERVED BY BC-1 (DWELLING UNIT?) FBC 401.2.
  
 15. SSHOW MEANS AND LOCATION OF DRYER EXHAUST PER FBC,M
 504.4. ALSO, VERIFY IF MAKE-UP AIR IS REQUIRED PER
 FBC,M 504.5.
  
 16. M1-102: EF 71 AND EF 73 SHALL BE INTERLOCKED WITH
 BC-1 PER FBC,M 403.2.1(3) AND WITH BATHROOM LIGHTS PER
 FBC,M 401.3.
  
 17. PLEASE SHOW MEANS AND LOCATION OF ALL CONDENSATE
 DISPOSAL, INCLUDING THE LOCATION OF DRYWELLS. FBC
 307.2.1
  
 18. "SALLY PORT" AREA SHALL BE VENTILATED PER FBC,M
 TABLE 403.3 AND SEC 404.
  
 19. NO INFORMATION COULD BE FOUND ON PLANS FOR VENTING
 OR COMBUSTION AIR FOR GAS APPLIANCES IN THE MECHANICAL
 ROOM ASIDE FROM GENERIC DETAIL FOR A WATER HEATER. IS
 THE MECHANICAL ROOM A CONFINED SPACE? IF SO, PROVIDE
 COMBUSTION AIR FOR A TOTAL OF 335,000 BTU/H PER FBC,FG
 304.5 AND SHOW SPECIFIC MEANS AND LOCATION OF VENTING
 PER FBC,FG 503.2.
  
 20. M4-101: ROOF EQUIPMENT SUPPORT DETAIL, PROVIDE
 COMPLETE DETAIL FOR FASTENING OF CURBS AND SUPPORTS TO
 STRUCTURE AS WELL AS ATTACHMENTS OF EQUIPMENT TO CURBS
 AND SUPPORTS. PROVIDE WIND LOAD CALCULATIONS FOR
 BUILDING PLAN REVIEW SHOWING THAT ALL ATTACHMENTS ARE
 DESIGNED TO THE 140 MPH WIND ZONE PER FBC,M 301.13 AND
 FBC CH.16.
  
 21.M4-101: IF PATE CURBS ARE USED AS SUPPORTS, AND
 ROOFING MATERIAL EXTENDS UNDER THE EQUIPMENT (INCLUDING
 DUCTWORK), CLEARANCES ABOVE FINISHED ROOF SHALL BE IN
 ACCORDANCE WITH FBC TABLE 1509.7, NOT NECESSARILY 14"
 AS SHOWN ON DETAIL.
  
 22. M4-101: FIRE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. FBC 607.2
  
 23. M4-102: PIPE PENETRATIONS OF RATED FLOOR/CEILING
 ASSEMBLIES SHALL COMPLY WITH FBC 712.4. PIPE
 PENETRATIONS OF RATED WALLS SHALL COMPLY WITH 712.3.
 PROVIDE UL ASSEMBLY DETAILS AS REQUIRED.
  
 24. BOTH OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL
 BE EQUIPPED WITH MOTORIZED DAMPERS THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED
 ARE NOT IN USE. VENTILATION OUTSIDE AIR DAMPERS SHALL
 BE CAPABLE OF AUTOMATICALLY SHUTTING OFF DURING
 PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND SETBACK,
 EXCEPT WHEN VENTILATION REDUCES ENERGY COSTS (E.G.,
 NIGHT PURGE) OR WHEN VENTILATION MUST BE SUPPLIED TO
 MEET CODE REQUIREMENTS. FBC 13-409.1.ABC.3.3
  
 25. NO INFORMATION WAS PROVIDED REGARDING EMERGENCY
 GENERATOR AS SHOWN ON E-301. PLEASE PROVIDE PLANS,
 SPECIFICATIONS, LOCATION ON SITE PLAN FOR GENERATOR AND
 FUEL TANK. SHOW DISTANCE FROM PROPERTY LINES, ADJACENT
 BUILDINGS AND ANY OPENINGS INTO BUILDINGS WITHIN 10' OF
 GENERATOR EXHAUST. ALL ABOVE GROUND FUEL TANKS OF 550
 GALLONS OR MORE REQUIRE PALM BEACH COUNTY DERM APPROVAL
 PRIOR TO PERMITTING BY THE CITY OF WEST PALM BEACH. FOR
 MORE INFORMATION CONTACT DERM DIRECTLY AT 561-233-2400
 OR VISIT WWW.PBCGOV.COM/ERM.
  
 NOTE: ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE
 NATURE AND COMPLETENESS OF INFORMATION WHICH IS TO BE
 PROVIDED IN RESPONSE TO THIS REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2009-08-20 Cont ID  
Sent By kstevens Date 2009-08-20 Time 13:55 Rev Time 0.00
Received By kstevens Date 2009-08-20 Time 09:45 Sent To  
Notes
2009-08-20 13:56:39REVISION SUBMITTED 8-13-09 OK

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2009-06-23 Cont ID  
Sent By kstevens Date 2009-06-23 Time 15:53 Rev Time 0.00
Received By kstevens Date 2009-06-23 Time 15:52 Sent To  
Notes
2009-06-23 15:55:36 
  
  
 SEPARATE MED-GAS PERMIT REQUIRED.
 OXYGEN SHALL BE INSTALLED PER LEVEL 3 GAS REQUIREMENTS
 OF NFPA 99C-99.
  
  
 .

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 08:06 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 08:06 Sent To  
Notes
2009-01-27 08:07:21DENIED
 REFERENCE:
 NFPA 99C MED-GAS
  
 NEW SHEET ADDED: SEPARATE MED-GAS PERMIT REQUIRED.
  
 1. SHT P8-101 PLEASE INDICATE THE LOCATION OF THE VENT
 FOR THE VACUUM SYSTEM. SECTIONS 4-5.2.1.4 & 4-5.2.1.5.
 CLEANOUTS ARE REQUIRED PER SECTION 4-5.2.2.3. PLEASE
 INDICATED ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 11 Status F Date 2009-10-28 Cont ID  
Sent By kstevens Date 2009-10-28 Time 16:24 Rev Time 0.00
Received By kstevens Date 2009-10-28 Time 16:23 Sent To  
Notes
2009-10-28 16:27:33REVISIONS DENIED FOR SHTS IR-1, IR-2 & IR-3. REVISIONS
 SUBMITTED HAVE LATEST REVISION AS REVISION #6 DATED
 DEC. 21 2007 BUT SHEETS ON FILE FOR PUBLIC RECORD HAVE
 LATEST REVISION AS REVISION #7 DATED JULY 6, 2009.
 IRRIGATION SHTS TO BE RETURNED.

Review Stop P PLUMBING
Rev No 10 Status P Date 2009-10-28 Cont ID  
Sent By kstevens Date 2009-10-28 Time 16:22 Rev Time 0.00
Received By kstevens Date 2009-10-28 Time 16:22 Sent To  
Notes
2009-10-28 16:23:42REVISIONS OK -- SHTS P1-102, P1-105, P2-101, P3-101 &
 P6-101.

Review Stop P PLUMBING
Rev No 9 Status P Date 2009-09-08 Cont ID  
Sent By kstevens Date 2009-09-08 Time 08:55 Rev Time 0.00
Received By kstevens Date 2009-09-08 Time 08:55 Sent To  
Notes
2009-09-08 08:56:00REVISION OK -- SHTS IR-1, IR-2 & IR-3. (REVISION 7).

Review Stop P PLUMBING
Rev No 8 Status F Date 2009-08-20 Cont ID  
Sent By kstevens Date 2009-08-20 Time 13:37 Rev Time 0.00
Received By kstevens Date 2009-08-20 Time 09:45 Sent To  
Notes
2009-08-20 13:55:19DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1. SHT P1-102 ON FILE FOR PUBLIC RECORD SHOWS REVISION
 #6 DATED 11-7-2008. THE NEW REVISED SHEET SUBMITTED
 8-13-2009 SHOWS REVISION 6 DATED 9-4-2008. A REVISION
 #6 IS ALREADY ON FILE. NEW REVISION NUMBERS ARE
 REQUIRED FOR EACH NEW REVISION AND THE REVISION HISTORY
 SHALL REMAIN THRU THE LIFE OF THE PROJECT. SECTION
 106.1.3. NO CHANGES TO THE PLUMBING WAS NOTED ON THIS
 SHEET. PLEASE CLARIFY.
  
 2. SHT P1-105 ON FILE FOR PUBLIC RECORD SHOWS REVISION
 #3 DATED 12-27-2007 & REVISION #6 DATED 11-7-2008. THE
 REVISED NEW SHEET SUBMITTED 8-13-09 ONLY SHOWS
 REVISIONS 1 & 2 WHICH ARE ALREADY ON FILE. PLEASE
 INDICATE NEW REVISIONS WITH CLOUDS AND NEW REVISION
 NUMBERS. THE REVISION HISTORY SHALL REMAIN THRU THE
 LIFE OF THE PROJECT. SECTION 106.1.3. NO CHANGES TO THE
 PLUMBING WAS NOTED ON THIS SHEET. PLEASE CLARIFY.
  
 3. SHT P2-101 ON FILE FOR PUBLIC RECORD SHOWS REVISION
 #6 DATED 11-7-2008. THE NEW REVISED SHEET SUBMITTED
 8-13-2009 SHOWS REVISION #6 DATED 9-4-2008. PLEASE
 INDICATE NEW REVISIONS WITH CLOUDS AND NEW REVISION
 NUMBERS. THE REVISION HISTORY SHALL REMAIN THRU THE
 LIFE OF THE PROJECT. SECTION 106.1.3. NO CHANGES TO THE
 PLUMBING WAS NOTED ON THIS SHEET. PLEASE CLARIFY.
  
 4. SHT P3-101 ON FILE FOR PUBLIC RECORD SHOWS REVISION
 #6 DATED 11-7-2008. THE NEW REVISED SHEET SUBMITTED
 8-13-2009 SHOWS REVISION 6 DATED 9-4-2008. PLEASE
 INDICATE NEW REVISIONS WITH CLOUDS AND NEW REVISION
 NUMBERS. THE REVISION HISTORY SHALL REMAIN THRU THE
 LIFE OF THE PROJECT. SECTION 106.1.3. NO CHANGES TO THE
 PLUMBING WAS NOTED ON THIS SHEET. PLEASE CLARIFY.
  
 5. SHT P6-101 ON FILE FOR PUBLIC RECORD SHOWS REVISION
 #6 DATED 11-7-2008. THE NEW REVISED SHEET SUBMITTED
 8-13-2009 SHOWS REVISION 6 DATED 9-4-2008. PLEASE
 INDICATE NEW REVISIONS WITH CLOUDS AND NEW REVISION
 NUMBERS. THE REVISION HISTORY SHALL REMAIN THRU THE
 LIFE OF THE PROJECT. SECTION 106.1.3. NO CHANGES TO THE
 PLUMBING WAS NOTED ON THIS SHEET. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 7 Status F Date 2009-06-18 Cont ID  
Sent By kstevens Date 2009-06-18 Time 15:01 Rev Time 0.00
Received By kstevens Date 2009-06-18 Time 15:01 Sent To  
Notes
2009-06-18 16:57:16REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 NFPA 99C MED-GAS
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT P1-103 GAS ISOMETRIC. THE MINIMUM PIPE SIZING IS
 NOT CORRECT ON SOME PIPES. 4" IS REQUIRED, (3,502 MBH @
 125 FEET), FROM THE METER TO THE FIRST TEE. 3" IS
 REQUIRED FOR 2,600 MBH. 2-1/2" IS REQUIRED FOR 1,300
 MBH. 2" IS REQUIRED FOR 902 MBH, (STILL SHOWN AS 750
 MBH). 2" IS REQUIRED FOR 750 MBH, (NO SIZE INDICATED).
 TABLE 402.4(2).
 ****RESPONSE NOTED, BUT THE REQUIREMENT FOR THE 3" PIPE
 FOR 2,600 MBH AND THE REQUIREMENT FOR THE 2-1/2" FOR
 THE 902 MBH HAS NOT BEEN ADDRESSED.
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-01-26 Cont ID  
Sent By kstevens Date 2009-01-26 Time 16:39 Rev Time 0.00
Received By kstevens Date 2009-01-26 Time 16:38 Sent To  
Notes
2009-01-26 16:58:15DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 NFPA 99C MED-GAS
  
 1. SHT P1-103 GAS ISOMETRIC. THE MINIMUM PIPE SIZING IS
 NOT CORRECT ON SOME PIPES. 4" IS REQUIRED, (3,502 MBH @
 125 FEET), FROM THE METER TO THE FIRST TEE. 3" IS
 REQUIRED FOR 2,600 MBH. 2-1/2" IS REQUIRED FOR 1,300
 MBH. 2" IS REQUIRED FOR 902 MBH, (STILL SHOWN AS 750
 MBH). 2" IS REQUIRED FOR 750 MBH, (NO SIZE INDICATED).
 TABLE 402.4(2).
  
 2. SHT P1-103 REVISIONS 4 & 5 NOT FOUND OR APPROVED.
 PLEASE INDICATE WHERE THESE REVISIONS CAN BE FOUND BY
 CLOUDING THE REVISIONS AND INDICATING WITH REVISION
 NUMBERS. SECTION 106.1.3.
  
 3. SHT P1-104 INDICATES REVISIONS 3, 4, 5 & 6. THIS
 SHEET ON FILE FOR PUBLIC RECORD SHOWS REVISIONS 1 & 2
 ONLY. NO REVISION CLOUDS OR REVISION NUMBERS ARE
 INDICATED ON THE SHEET SUBMITTED FOR REVIEW. PLEASE
 CLOUD AND NUMBER ALL REVISIONS AFTER REVISION 2.
 SECTION 106.1.3.
  
 4. SHT P 4-101 INDICATES REVISIONS 5 & 6. THIS SHEET ON
 FILE FOR PUBLIC RECORD SHOWS REVISIONS 1, 2, 3 & 4. NO
 REVISION CLOUDS OR REVISION NUMBERS ARE INDICATED ON
 THE SHEET SUBMITTED FOR REVIEW. PLEASE CLOUD AND NUMBER
 ALL REVISIONS AFTER REVISION 2. SECTION 106.1.3.
  
 5. SHT P5-101 INDICATES REVISIONS 3, 4, 5 & 6. THIS
 SHEET ON FILE FOR PUBLIC RECORD SHOWS REVISIONS 1 & 2
 ONLY. NO REVISION CLOUDS OR REVISION NUMBERS ARE
 INDICATED ON THE SHEET SUBMITTED FOR REVIEW. PLEASE
 CLOUD AND NUMBER ALL REVISIONS AFTER REVISION 2.
 SECTION 106.1.3.
  
 6. SHT P7-101 INDICATES REVISIONS 3, 4, 5 & 6. THIS
 SHEET ON FILE FOR PUBLIC RECORD SHOWS REVISIONS 1 & 2
 ONLY. NO REVISION CLOUDS OR REVISION NUMBERS ARE
 INDICATED ON THE SHEET SUBMITTED FOR REVIEW. PLEASE
 CLOUD AND NUMBER ALL REVISIONS AFTER REVISION 2.
 SECTION 106.1.3.
  
 7. SHT P8-101 PLEASE INDICATE THE LOCATION OF THE VENT
 FOR THE VACUUM SYSTEM. SECTIONS 4-5.2.1.4 & 4-5.2.1.5.
 CLEANOUTS ARE REQUIRED PER SECTION 4-5.2.2.3. PLEASE
 INDICATE ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-01-26 Cont ID  
Sent By kstevens Date 2009-01-26 Time 16:34 Rev Time 0.00
Received By kstevens Date 2009-01-23 Time 11:05 Sent To  
Notes
2009-01-26 16:38:49REVISIONS OK -- SHTS P0-1-1 (REVISIONS 3,4 & 5 NOT
 FOUND OR APPROVED), P1-101 (REVISIONS 3,4 & 5 NOT FOUND
 OR APPROVED), P1-102 (REVISIONS 3,4 & 5 NOT FOUND OR
 APPROVED), P1-105 (REVISIONS 4 & 5 NOT FOUND OR
 APPROVED), P2-101 (REVISION 5 NOT FOUND OR APPROVED),
 P3-101 (REVISION 5 NOT FOUND OR APPROVED), P4-102 (NEW
 SHEET), P6-101 (REVISION 5 NOT FOUND OR APPROVED).

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-08-12 Cont ID  
Sent By kstevens Date 2008-08-12 Time 10:19 Rev Time 0.00
Received By kstevens Date 2008-08-12 Time 10:18 Sent To  
Notes
2008-08-12 10:20:03SEPARATE PLUMBING & IRRIGATION PERMITS REQUIRED

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-05-28 Cont ID  
Sent By kstevens Date 2008-05-28 Time 14:43 Rev Time 0.00
Received By kstevens Date 2008-05-27 Time 12:38 Sent To  
Notes
2008-05-28 15:09:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW: (2ND REVIEW)
  
 ******FROM PREVIOUS REVIEWS: (3RD REVIEW)
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH
 SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD
 APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
 ****RESPONSE NOTED, BUT SHT A-709 DETAILS 79 & 81 SHOW
 THE FLOOD RIM LEVEL, (COUNTER TOP), AT 3'0". PER CODE
 34" IS MAXIMUM HEIGHT ALLOWED. SECTION 11-4.24.2. ALSO
 NOT SHOWN IS THE SINK DEPTH, SECTION 11-4.24.4, THE
 CLEAR FLOOR SPACE, SECTION 11-4.24.5, OR COMPLIANCE FOR
 THE FAUCET, SECTION 11-4.24.7.
 ******RESPONSE NOTED, BUT THE FOLLOWING IS STILL NOT
 SHOWN: THE SINK DEPTH, SECTION 11-4.24.4, THE CLEAR
 FLOOR SPACE, SECTION 11-4.24.5, OR COMPLIANCE FOR THE
 FAUCET, SECTION 11-4.24.7. ALSO INDICATE THE CLEARANCE
 REQUIRED BY SECTION 11-4.24.3.
  
 15. OK
 16. OK
 17. OK
 18. OK
  
 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE
 PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER
 BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS.
 SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS
 AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES
 NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY).
 ****RESPONSE NOTED, BUT IT WAS A SELECTIVE RESPONSE. NO
 DETAIL FOR THE CANINE PRE-OP/POST-OP KENNELS WERE
 SUBMITTED. ALSO NO DETAIL FOR THE BACKFLOW PROTEDTION
 TO THE CONNECTION TO THE DOG BOWLS IS INDICATED ON SHT
 P2-101. THE ONLY BACKFLOW PROTECTION SHOWN IS FOR THE
 P-16 FIXTURES. INDICTE MANUFACTURE AND MODEL OF
 BACKFLOW PER TABLE 608.1.
 ******RESPONSE NOTED, BUT BACKFLOW PREVENTERS SHALL BE
 INSTALLED MAXIMUM 4 FEET ABOVE THE FLOOR FOR SERVICING
 AND TESTING. THE BACKFLOW PREVENTER IN THE RECESSED
 SHALL BE ACCESSIBLE FOR SERVICING & TESTING ALSO.
  
 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS
 REVIEW:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. N/A
 H. N/A
  
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
  
 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE
 SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) &
 710.1(2).
 ****RESPONSE NOTED, BUT THE DFU'S ARE NOT INDICATED AS
 THEY ACCUMULATE IN THE SYSTEM.
 ******RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT
 SHOWN. (EXAMPLE: ALL PIPING TO THE CAGES FOR PRE-OP &
 POST-OP).
  
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
  
 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES &
 INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION
 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105).
 106.3.5.1.3(7)(13).
 ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM IS NOT INDICATED.
 ******RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM IS STILL NOT INDICATED ON THE
 RISER DIAGRAM. ALSO PER TABLE 1106.3, MINIMUM 6" PIPE
 IS REQUIRED FOR 1625SF @ 1/8"/FT.
  
 36. OK
 37. OK
  
 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE
 RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS
 INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY.
 --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK.
 PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE
 TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF
 VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS.
 SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 ****RESPONSE NOTED, BUT NO CLARIFICATION OF HOW THE
 COLD WATER SUPPLY TURNS INTO THE HOT WATER SUPPLY.
 ******RESPONSE NOTED, BUT THE COLD WATER IS STILL SHOWN
 AS COLD WATER TO THE WATER HEATER, BUT HOT WATER TO THE
 STORAGE TANK. ALSO THE PUMP IS INDICATED AS PUMPING THE
 HOT WATER FROM THE STORAGE TANK AND INTO THE HOT WATER
 HEATER. PLEASE SHOW THE PUMP AS PUMPING FROM THE WATER
 HEATER AND INTO THE STORAGE TANK AND INDICATE DIRECTION
 OF FLOW.--THE MANUF. PIPING DIAGRAM STATES "THIS
 ILLUSTRATION IS FOR CONCEPT ONLY AND SHOULD NOT BE USED
 FOR ACTUAL INSTALLATION WITHOUT ENGINEERING OR
 TECHNICAL ADVICE FROM A LICENSED ENGINEER."
  
 39. OK
  
  
 **********NEW COMMENT**********
  
 1B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE FOR THE REQUEST TO SUBMIT ONE SET OF
 OLD/VOID SHEETS TO HELP EXPEDITE THE REVIEW PROCESS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-15 Cont ID  
Sent By kstevens Date 2008-02-15 Time 09:35 Rev Time 0.00
Received By kstevens Date 2008-02-14 Time 14:23 Sent To  
Notes
2008-02-15 10:37:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. CIVIL DRAWINGS. THE ADDRESS FOR THE ENGINEERING
 CONPANY IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS
 INDICATED ON THE FLORIDA STATE DBPR WEBSITE. PLEASE
 UPDATE THE WEBSITE OR THE TITLE BLOCKS PRIOR TO
 RESUBMITTING. ALSO THE ENGINEER SHALL LEGIBLY INDICATE
 HER ADDRESS IN THE TITLE BLOCK.FAC 61G15-23.002(2) &
 FS 471.025. PLEASE INDICATE ENGINEER'S ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS INDICATED IN THE
 DBPR WEBSITE IS 6380 SANDY HILL WAY LAKE WORTH FLA
 33463, NOT 120 S. OLIVE AVE. ETC. AS INDICATED IN THE
 TITLE BLOCK. BUSINESS LICENSE NUMBER IS 9664 AS SHOWN
 ON THE TITLE BLOCK THE CORPORATION NUMBER IS OF NO
 RELEVANCE TO THIS COMMENT.
  
 4. OK
  
 5. ALL ARCHITECTURAL SHEETS. THE SIGNATURE IS REQUIRED
 FOR THE ARCHITECT. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, THEN A SIGNED, SEALED, DATED, NOTORIZED
 LETTER INDICATING THE LEGAL SIGNATURE OF THE ARCHITECT
 SHALL BE SUBMITTED FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004(5) & FS 481.2055.
 ****RESPONSE NOTED, BUT THE SEAL IS STILL SIGNED WITH
 WHAT APPEARS TO BE INITIALS AND NO LETTER HAS BEEN
 SUBMITTED.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
  
 12. SHT A-300 UPPER ROOF AT N.E. CORNER INDICATES R5 AS
 AN O.S. PLEASE CLARIFY.--LOWER ROOF DRAINS ARE
 INDICATED AS O.S., NOT PRIMARY SCUPPER DRAINS. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT DETAIL R7/A302 DOES NOT REFLECT
 THE PARAPET FOR THE UPPER ROOF. SECONDARY ROOF DRAIN
 REQUIRED. (SEE DETAIL R4/A-301).
  
 13. SHT A-300 INDICATES R15 FOR THE SCUPPER WITH
 DOWNSPOUT & O.S. R15 SHOWS NO COLLECTOR HEAD OR
 DOWNSPOUT. ALSO SHEET A-400 SHOWS NO DOWNSPOUTS. PLEASE
 CLARIFY AND INDICATE THE SIZE OF THE DOWNSPOUTS AND
 SHOW COLLECTOR HEAD WITH DIMENSIONS. TABLES 1106.3 &
 1106.7.--ALSO INDICATE HOW THE PRIMARY DRAIN & O.S.
 CAN BE AT THE ROOF LEVEL. SECTIONS 1503.4.2 &
 1503.4.3.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. DETAIL
 R15 STILL DOES NOT SHOW A COLLECTOR HEAD OR
 DOWNSPOUTS.
  
 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH
 SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD
 APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
 ****RESPONSE NOTED, BUT SHT A-709 DETAILS 79 & 81 SHOW
 THE FLOOD RIM LEVEL, (COUNTER TOP), AT 3'0". PER CODE
 34" IS MAXIMUM HEIGHT ALLOWED. SECTION 11-4.24.2. ALSO
 NOT SHOWN IS THE SINK DEPTH, SECTION 11-4.24.4, THE
 CLEAR FLOOR SPACE, SECTION 11-4.24.5, OR COMPLIANCE FOR
 THE FAUCET, SECTION 11-4.24.7.
  
 15. OK
 16. OK
 17. OK
  
 18. SHT P1-101. SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE SN-1 FIXTURE INCLUDING INSTALLATION
 INSTRUCTIONS. SECTION 106.1.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED. TABLE 604.3
 & 604.5, SECTION 608.2.
  
 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE
 PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER
 BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS.
 SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS
 AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES
 NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY).
 ****RESPONSE NOTED, BUT IT WAS A SELECTIVE RESPONSE. NO
 DETAIL FOR THE CANINE PRE-OP/POST-OP KENNELS WERE
 SUBMITTED. ALSO NO DETAIL FOR THE BACKFLOW PROTEDTION
 TO THE CONNECTION TO THE DOG BOWLS IS INDICATED ON SHT
 P2-101. THE ONLY BACKFLOW PROTECTION SHOWN IS FOR THE
 P-16 FIXTURES. INDICTE MANUFACTURE AND MODEL OF
 BACKFLOW PER TABLE 608.1.
  
 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS
 REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT NOT ALL SECTIONS OF PIPE SHOW
 THE CORRESPONDING LENGHTS AS REQUIRED. ALSO THE PIPING
 IS NOT CLEAR AT THE GB1 APPLIANCES. (DELETE BACKGROUND
 FLOOR PLAN & GAS APPLIANCES).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT SPECIFICATION 15483 IS REFERENCED AS BEING
 DESIGNED BY FBC-2001. THE ADOPTED CODE IS FBC-2004.
 PLEASE CHECK THE INFORMATION IS THE SPECIFICATION BOOKS
 AS THEY WILL BE REVIEWED COMPLETLY UPON RESUBMISSION
 AND THEY SHALL BE REQUIRED TO REFLECT THE PLANS TO BE
 APPROVED.
  
 C. OK
 D. OK
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE GAS PLANS WILL NOT BE
 APPROVED UNTIL THE COMMENT IS COMPLIED WITH. COMMENT
 NOT ADDRESSED.
  
 G. N/A
 H. N/A
  
 21. OK
  
 22. SHT P1-105 A RELIEF VENT, (GOOSE-NECK) FITTING
 SHALL BE INSTALLED IN THE CONDENSATE DRAIN LINE AS IT
 EXITS THE BUILDING.
 ****RESPONSE NOTED, BUT P1-105 DOES NOT REFLECT THE
 RISER DIAGRAM ON SHT P1-101. PLEASE CORRELATE. SECTION
 106.1.1.
  
 23. OK
 24. OK
 25. OK
 26. OK
  
 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE
 SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) &
 710.1(2).
 ****RESPONSE NOTED, BUT THE DFU'S ARE NOT INDICATED AS
 THEY ACCUMULATE IN THE SYSTEM.
  
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
  
 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES &
 INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION
 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105).
 106.3.5.1.3(7)(13).
 ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM IS NOT INDICATED.
  
 36. OK
 37. OK
  
 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE
 RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS
 INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY.
 --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK.
 PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE
 TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF
 VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS.
 SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 ****RESPONSE NOTED, BUT NO CLARIFICATION OF HOW THE
 COLD WATER SUPPLY TURNS INTO THE HOT WATER SUPPLY.
  
 39. OK
  
  
 **********NEW COMMENT**********
  
 1B. INFORMATIONAL: THE CERTIFICATIONS AND WELDING
 PROCEDURE WILL BE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE FOR THE REQUEST TO SUBMIT ONE SET OF
 OLD/VOID SHEETS TO HELP EXPEDITE THE REVIEW PROCESS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-23 Cont ID  
Sent By kstevens Date 2007-08-23 Time 10:03 Rev Time 0.00
Received By kstevens Date 2007-08-11 Time 18:14 Sent To  
Notes
2007-08-23 11:59:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. SHT G-001 OCCUPANCY DATA. PLEASE CLARIFY SQUARE
 FOOTAGE FOR THE BUSINESS AND STORAGE OCCUPANCY. PER
 DATA INDICATED IT SEEM THAT THE AREA FOR THE STORAGE IS
 APPROXIMATLY TWICE THAT OF THE BUSINESS AREA. LOOKING
 AT THE FLOOR PLAN THIS DOES NOT SEEM TO BE THE CASE.
 PLEASE INDICATE EACH AREA TO BE INDICATED AS STORAGE
 WITH THE SQUARE FOOTAGE FOR EACH AREA. ALSO INDICATE
 EACH AREA TO BE BUSINESS OCCUPANCY AND SHOW SQUARE
 FOOTAGE OF EACH AREA. SECTION 106.3.5.1.1(2). THIS WILL
 HELP VERIFY OCCUPANCY DATA.
  
 2. SHT G-001 BUILDING DATA INDICATES 37,772SF, BUT THE
 APPLICATION INDICATES 27,308SF. PLEASE CORRELATE
 INFORMATION ON PLANS WITH THE APPLICATION. SECTION
 106.1.1.
  
 3. CIVIL DRAWINGS. THE ADDRESS FOR THE ENGINEERING
 CONPANY IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS
 INDICATED ON THE FLORIDA STATE DBPR WEBSITE. PLEASE
 UPDATE THE WEBSITE OR THE TITLE BLOCKS PRIOR TO
 RESUBMITTING. ALSO THE ENGINEER SHALL LEGIBLY INDICATE
 HER ADDRESS IN THE TITLE BLOCK.FAC 61G15-23.002(2) &
 FS 471.025. PLEASE INDICATE ENGINEER'S ADDRESS.
  
 4. SHTS L-1 THRU L-6 THEFIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK PER FAC 61G1-16.004(2) & FS 481.219,
 481.2055. PLEASE SHOW FIRM LICENSE NUMBER IN TITLE
 BLOCK.
  
 5. ALL ARCHITECTURAL SHEETS. THE SIGNATURE IS REQUIRED
 FOR THE ARCHITECT. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, THEN A SIGNED, SEALED, DATED, NOTORIZED
 LETTER INDICATING THE LEGAL SIGNATURE OF THE ARCHITECT
 SHALL BE SUBMITTED FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004(5) & FS 481.2055.
  
 6. SHT A-104 DETAILS 1 THRU 4. SHOW THE 5' TURNING AREA
 REQUIRED IN THE TOILET ROOMS PER SECTION 11-4.22.3.
  
 7. SHT A-104 DETAIL 4 SHOW THE CLEAR FLOOR SPACE FOR
 ALL REQUIRED ACCESSIBLE FIXTURES PER SECTIONS
 11-4.16.2, 11-4.19.3 & 11-4.21.2.--A TURNING AREA
 IS REQUIRED FOR THE SHOWER ROOMS PER SECTION 11-4.2.3.
 PLEASE SHOW ON DETAIL.--DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SECTION
 11-4.23.2. THIS WILL INCLUDE THE SHOWERS AND THE LAVS
 OUTSIDE THE SHOWERS.
  
 8. SHT A-104 DETAIL 4. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 ___FOR SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
  
 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH THE SECTION 11-4.15 AND
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 10. SHT A-300 SUBMIT CALCULATIONS FOR PRIMARY &
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. SHOW THE SQUARE FOOT AREA OF EACH
 ROOF DRAIN WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AS WELL AS THE SQUARE FOOTAGE OF ALL
 ROOFS THAT DRAIN ONTO EACH AREA FROM ABOVE ADDED IN THE
 CALCULATIONS.
  
 11. SHT A-300 LOWER ROOF ON THE WEST SIDE OF THE
 BUILDING INDICATES R5 TYP FOR O.S. DETAIL R5 INDICATES
 A PARAPET WALL. SECONDARY ROOF DRAIS REQUIRED PER
 SECTION 1107.2. IS THE DRAIN SHOWN A SCUPPER DRAIN OR
 AN OVERFLOW SCUPPER DRAIN? PLEASE CLARIFY AND INDICATE
 SECONDARY DRAIN. SECTION 106.1.1.
  
 12. SHT A-300 UPPER ROOF AT N.E. CORNER INDICATES R5 AS
 AN O.S. PLEASE CLARIFY.--LOWER ROOF DRAINS ARE
 INDICATED AS O.S., NOT PRIMARY SCUPPER DRAINS. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 13. SHT A-300 INDICATES R15 FOR THE SCUPPER WITH
 DOWNSPOUT & O.S. R15 SHOWS NO COLLECTOR HEAD OR
 DOWNSPOUT. ALSO SHEET A-400 SHOWS NO DOWNSPOUTS. PLEASE
 CLARIFY AND INDICATE THE SIZE OF THE DOWNSPOUTS AND
 SHOW COLLECTOR HEAD WITH DIMENSIONS. TABLES 1106.3 &
 1106.7.--ALSO INDICATE HOW THE PRIMARY DRAIN & O.S.
 CAN BE AT THE ROOF LEVEL. SECTIONS 1503.4.2 &
 1503.4.3.
  
 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH
 SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD
 APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
  
 15. ALL PLUMBING, MECHANICAL, ELECTRICAL & FIRE
 PROTECTION SHEETS. THE ENGINEER SHALL LEGIBLY INDICATE
 THEIR ADDRESS. FAC 61G15-23.002(2) & FS 471.025.
  
 16. SHT P0-1-1 IS INDICATED AS HVAC LEGEND, SCHEDULE &
 GENERAL NOTES IN THE SHEET TITLE. PLEASE CHANGE
 REFERENCE TO IDENTIFY INFORMATION ON SHEET. SECTION
 106.1.1.
  
 17. SHT P0-101 THE MAXIMUM DISTANCE OF THE FIXTURE TRAP
 FROM THE VENT SHALL COMPLY WITH TABLE 906.1. SOME FLOOR
 DRAINS APPEAR TO EXCEED THE LIMIT, BUT NO PIPE/TRAP
 SIZE IS INDICATED. PLEASE CHECK THE DISTANCE FROM THE
 VENT AND INDICATE PIPE/TRAP SIZE. TABLE 709.1.
  
 18. SHT P1-101. SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE SN-1 FIXTURE INCLUDING INSTALLATION
 INSTRUCTIONS. SECTION 106.1.2.
  
 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE
 PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER
 BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS.
 SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS
 AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES
 NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY).
  
 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS
 REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (NOT SHOWN FOR GB1
 UNITS).
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 21. SHT P1-103 DETAIL (2) GB1(1300MBTH) NOT INDICATED
 ON THE PLUMBING EQUIPMENT SCHEDULE ON SHT P5-101.
 PLEASE IDENTIFY THESE FIXTURES. SECTION 106.1.2.
  
 22. SHT P1-105 A RELIEF VENT, (GOOSE-NECK) FITTING
 SHALL BE INSTALLED IN THE CONDENSATE DRAIN LINE AS IT
 EXITS THE BUILDING.
  
 23. SHT P2-101 WATER HAMMER ARRESTORS ARE REQUIRED ON
 ALL QUICK CLOSING VALVES PER SECTION 604.9. (ICE
 MAKERS, DISH WASHERS, WASH MACHINES ETC.). PLEASE SHOW
 ON THE WATER ISOMETRIC RISER DIAGRAM. WHA'S TO BE
 LOCATED NEAR THE FIXTURE, NOT IN THE CEILING. PDI-WH
 201.
  
 24. SHT P2-101 2" WATER SUPPLY LINE DOES NOT CONNECT TO
 THE WATER SUPPLY LINE IN THE CEILING ABOVE THE
 VESTIBLUE FOR THE MEN'S LOCKER ROOM. (ALSO SEE SHT
 P1-103). SECTION 106.1.1. PLEASE INDICATE WHERE THE 2"
 CW CONNECTS.
  
 25. SHT P2-101 PLEASE IDENTIFY THE FIXTURE THAT
 CONNECTS TO THE COLD WATER SUPPLY LINE THEN INDICATES
 HOT WATER LINE CONNECTING TO THE 3/8TH" STAINLESS STEEL
 TUBING INDICATED AS A COLD WATER LINE. THIS IS ABOVE
 ROOM #174. PLEASE CLARIFY SECTION 106.1.2.
  
 26. SHT P2-101 SHOW ALL PIPE SIZES. SECTIONS 106.2.1 &
 604.
  
 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE
 SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) &
 710.1(2).
  
 28. SHT P3-101 INDICATE HOW THE VENT CONNECTS TO THE
 BRANCH LINE BEHIND THE W/C IN TOILET ROOM 183. SECTIONS
 905.3 & 905.4. (ALSO SEE SHT P1-101).
  
 29. SHT P3-101 A TRAP AND A VENT ARE REQUIRED FOR THE
 SINK IN ROOM 172. SECTIONS 901.2.1 & 1002.1. (ALSO SEE
 SHT P1-101).
  
 30. SHT P3-101 NOT ALL KENNELS SHOW A TD1. PLEASE
 CLARIFY. (ALSO SEE SHT P1-101). SECTION 106.2.1.
  
 31. SHT P3-101 TRAPS FOR TD1'S ON SANITARY RISER
 ISOMETRIC DIAGRAM ARE NOT LEGIBLE. PLEASE CLARIFY HOW
 THE TRAPS ARE TO BE CONNECTED TO THE BRANCH LINE.
 SECTION 106.1.1.
  
 32. SHT P3-101 NOTE "PROVIDE FUNNEL" FOR RESIDENTIAL
 AREA CONDENSATE NOT APPROVED. CONDENSATE SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM. CONDENSATE SHALL DRAIN
 SEPARATELY OUT OF THE BUILDING AND TERMINATE INTO THE
 STORM, A CATCH BASIN, DRWELLL, OR PLANTED AREA A
 MINIMUM 1 FOOT FROM THE STRUCTURAL WALL.MUNICIPAL
 CODE ARTICLE III SECTION 90-125(5). PLEASE INDICATE HOW
 CONDENSATE TO BE DRAINED FROM RESIDENTIAL AREA. SECTION
 106.1.2.
  
 33. SHT P3-101 THE WASH MACHINES REQUIRE A STANDPIPE,
 MINIMUM 18" AND A CLEANOUT, MINIMUM 4FT ABOVE THE
 FLOOR. SECTIONS 708.9 & 802.4. PLEASE SHOW ON THE SANT.
 RISER DIAGRAM.
  
 34. SHT P3-101 CLEANOUTS REQUIRED PER SECTIONS 708.3.1
 & 708.3.5. PLEASE INDICATE ON THE SANT. RISER DIAGRAM &
 ON THE FLOOR PLANS SHTS P1-101, P1-102 & P1-103.
  
 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES &
 INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION
 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105).
 106.3.5.1.3(7)(13).
  
 36. SUBMIT A CONDENSATE RISER DIAGRAM. INDICATE ALL
 PIPE SIZES AND SHOW PIPES FROM A/C UNIT THRU
 TERMINATION. INDICATE MATERIAL FOR CONDENSATE PIPING.
 SECTION 106.3.5.1.3(13).
  
 37. SHT P4-1-1 WATER HAMMER ARRESTOR DETAIL. THE
 LOCATION OF THE WATER HAMMER ARRESTORS SHALL BE NEAR
 THE FIXTURE, IN AN "EFFECTIVE RANGE" NOT IN THE CEILING
 AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE
 RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS
 INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY.
 --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK.
 PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE
 TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF
 VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS.
 SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
  
 39. SHT P4-101 GAS WATER HEATER FLUE DETAIL SHOWS 2
 VENTS. IS THE CAT 1, CLASS B VENT TO THE WALL A DIRECT
 VENT? PLEASE CLARIFY. (IF DIRECT VENT, CLASS B NOT
 REQUIRED). SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. RESUBMIT
 MARKED UP PLUMBING SHEETS TO ALLSO HELP EXPEDITE PLAN
 REVIEW. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 11 Status P Date 2009-10-21 Cont ID  
Sent By eschneid Date 2009-10-21 Time 11:05 Rev Time 0.25
Received By eschneid Date 2009-10-21 Time 11:05 Sent To  
Notes
2009-10-21 11:05:46PASSED
  
 PLANS FROM 9/23/09 MINOR AMENDMENT SUBMITTED WITH THIS
 REVISION.

Review Stop Z ZONING
Rev No 10 Status F Date 2009-09-16 Cont ID  
Sent By eschneid Date 2009-09-16 Time 17:13 Rev Time 0.75
Received By eschneid Date 2009-09-16 Time 17:12 Sent To  
Notes
2009-09-16 17:22:50FAILED
  
 1) STAFF IS PROCESSING A MINOR AMENDMENT TO THE SITE,
 LANDSCAPE AND CIVIL PLANS THAT IS NOT REFLECTED
 CORRECTLY ON SHEETS A-010 AND A-012 THAT HAVE BEEN
 SUBMITTED WITH THIS REVISION.
  
 2) NO REVISED LANDSCAPE AND CIVIL PLANS WERE SUBMITTED
 WITH THIS REVISION. THE LATEST STAMPED CIVIL AND
 LANDSCAPE PLANS DO NOT MATCH THOSE INCLUDED WITH THE
 MINOR AMENDMENT NOR DO THEY MATCH THE SITE PLANS
 SUBMITTED WITH THIS REVISION.
  
 3) THIS PERMIT IS FOR PHASE I REVISIONS, YET IT SHOWS
 CHANGES THAT ARE TO OCCUR IN PHASE II, BUT IT DOES NOT
 SHOW WHAT PHASE I WILL LOOK LIKE PRIOR TO THE WORK
 COMMENCING ON PHASE II.
  
 CONTACT ERIC SCHNEIDER @ (822-1446).

Review Stop Z ZONING
Rev No 9 Status F Date 2009-07-14 Cont ID  
Sent By eschneid Date 2009-07-14 Time 13:16 Rev Time 0.25
Received By eschneid Date 2009-07-14 Time 13:16 Sent To  
Notes
2009-07-14 13:18:24FAILED IN PART REVISION SUBMITTED ON JUNE 25, 2009.
  
 THE FOLLOWING SHEET IS NOT PASSED:
  
 L-1
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 8 Status P Date 2009-07-14 Cont ID  
Sent By eschneid Date 2009-07-14 Time 13:15 Rev Time 0.25
Received By eschneid Date 2009-07-14 Time 11:00 Sent To  
Notes
2009-07-14 13:15:08PASSED IN PART REVISION SUBMITTED ON JUNE 25, 2009.
  
 THE FOLLOWING SHEETS ARE PASSED:
  
 C 2.1
 C 3.1
 C 5.1
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 7 Status F Date 2009-06-09 Cont ID  
Sent By eschneid Date 2009-06-09 Time 11:52 Rev Time 1.00
Received By eschneid Date 2009-06-09 Time 11:52 Sent To  
Notes
2009-06-09 11:56:49FAILED IN PART REVISION SUBMITTED 6-3-09
  
 1) THE FOLLOWING SHEETS SUBMITTED AS PART OF THE
 REVISION HAVE FAILED AS THEY DO NOT MATCH THE APPROVED
 SITE AND LANDSCAPE PLANS - LOCATION OF TRANSFORMER PAD,
 FENCE LOCATION AND WIDTH OF THE SIDEWALK ADJACENT TO
 THE GENERATOR PAD:
  
 C 2.1
 C 3.1
 C 5.1
  
 2) SHEET L-1 SHOWING THE LATEST REVISIONS IS REQUIRED.
 THE EXISTING L-1 IS VOIDED BASED ON THE REVISIONS TO
 THE SITE. PLEASE VOID THE FIELD SET.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 6 Status P Date 2009-06-09 Cont ID  
Sent By eschneid Date 2009-06-09 Time 11:25 Rev Time 1.00
Received By eschneid Date 2009-06-09 Time 11:25 Sent To  
Notes
2009-06-09 11:52:21PASSED IN PART REVISION SUBMITTED 6-3-09
  
 THE FOLLOWING SHEETS SUBMITTED AS PART OF THE REVISION
 HAVE PASSED:
  
 A-010
 A-012
 A-100A
 A-400
 L-2
 L-3
 L-4
 L-8
 L-9
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 5 Status F Date 2008-12-19 Cont ID  
Sent By eschneid Date 2008-12-19 Time 16:43 Rev Time 0.00
Received By eschneid Date 2008-12-19 Time 11:34 Sent To  
Notes
2008-12-19 16:43:46FAILED
  
 1) THE CHANGES TO THE SITE AND LANDSCAPE PLANS AND
 ELEVATIONS REQUIRE APPROVAL BY THE PLANNING AND ZONING
 DEPARTMENT THROUGH THE MINOR AMENDMENT PROCESS.
  
 2) NO LANDSCAPE PLAN SHOWING THE CHANGES WAS SUBMITTED
 WITH THE PERMIT.
  
 3) EARLIER DISCUSSIONS WITH PLANNING STAFF INDICATED
 THAT A TRANSFORMER WOULD BE LOCATED AT THE SOUTHERN END
 OF THE WESTERN PARKING. IF A TRANSFORMER HAS BEEN
 INSTALLED, IT SHALL BE SHOWN ON ALL PLANS.
  
 4) THE NEW PARKING SPACE HAS CAUSED THE FIRE HYDRANT TO
 CONFLICT WITH THE REQUIRED TERMINAL ISLAND TREE. THE
 HYDRANT AND REQUIRED TREE CONFLICT NEEDS TO BE
 RESOLVED.
  
 5) THE NEW SECTIONS OF WALL THAT SCREEN THE GENERATOR
 AND CHILLERS REQUIRE HEDGES ON THE EXTERIOR TO ACT AS
 SCREENING OF THE WALLS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status P Date 2008-08-06 Cont ID  
Sent By eschneid Date 2008-08-06 Time 12:10 Rev Time 0.00
Received By eschneid Date 2008-08-06 Time 12:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-27 Cont ID  
Sent By eschneid Date 2008-05-27 Time 18:00 Rev Time 0.00
Received By eschneid Date 2008-05-27 Time 18:00 Sent To  
Notes
2008-05-27 18:01:35PASSED
  
 NOTES:
  
 THE SIGNAGE AND FENCE/GATES SHALL BE UNDER SEPARATE
 PERMITS.
  
 ALL RIGHT-OF-WAY AREAS ADJACENT TO THE SITE SHALL BE
 SODDED, IRRIGATED AND MAINTAINED.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-19 Cont ID  
Sent By eschneid Date 2008-02-19 Time 15:29 Rev Time 0.00
Received By eschneid Date 2008-02-19 Time 15:29 Sent To  
Notes
2008-02-19 15:37:00FAILED
  
 PLEASE RESPOND IN WRITING TO COMMENTS:
  
 1) THE FOLLOWING ITEMS FROM ORDINANCE NO. 4901 HAVE NOT
 BEEN ADDRESSED:
  
 A. ALL UTILITIES ON THE PORTION OF THE CSPD THAT WILL
 HOUSE THE GRACE PAVILION SHALL BE BURIED UNDERGROUND.
  
 B. THE EXISTING CHAIN LINK FENCE ON THE GRACE PAVILION
 SITE AND ALONG THE ENTIRE MILITARY TRAIL FRONTAGE SHALL
 BE REPLACED BY EITHER VINYL COATED CHAIN LINK OR OTHER
 DECORATIVE FENCE, SUBJECT TO PLANNING AND ZONING
 DEPARTMENT APPROVAL.
  
 D. PRIOR TO THE ISSUANCE OF ANY PERMIT, THE FOLLOWING
 SHALL OCCUR:
  
 I. A TREE ALTERATION PERMIT SHALL BE OBTAINED BY THE
 DEVELOPER FROM THE CITY?S PLANNING AND ZONING
 DEPARTMENT.
  
 II. RECORD A PLAT FOR ALL OF THE PARCELS WITHIN THE
 ANIMAL RESCUE LEAGUE COMMUNITY SERVICE PLANNED
 DEVELOPMENT.
  
 III. ABANDON THE EASEMENTS THAT CONFLICT WITH THE
 BUILDING, AS WELL AS ANY OTHER UNNECESSARY EASEMENTS.
  
 2) SHEETS C4.1 AND A-011 HAVE DIFFERENT DUMPSTER
 DETAILS.THE ONE ON C4.1 MEETS CITY CODE, BUT DOES NOT
 INCLUDE THE RECYCLE AREA.THE ONE ON A-001 HAS THE
 RECYCLE AREA AND LOOKS LIKE THE ONE ON THE SITE PLAN,
 BUT DOES NOT MEET CITY STANDARDS.PLEASE REVISE
 ACCORDINGLY.
  
 3) ALL SIGNAGE, TO INCLUDE THE TEMPORARY CONSTRUCTION
 SIGN SHALL BE UNDER SEPARATE PERMIT.
  
 4) THE EASTERN PARKING LOT AND DETENTION POND LAYERS
 ARE NOT VISIBLE ON SHEET A-010.
  
 5) IRRIGATION PLANS ARE REQUIRED.
  
 CONTACT ERIC SCHNEIDER@ (561) 822-1435.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By eschneid Date 2007-07-12 Time 08:51 Rev Time 0.00
Received By eschneid Date 2007-07-12 Time 15:43 Sent To  
Notes
2007-07-12 15:49:42FAILED
  
 THIS PROJECTS REQUIRES ZONING APPROVAL PRIOR TO ANY
 BUILDING PERMIT APPROVAL.IF THE OFFICE BUILDING IS TO
 OPERATE AS A SEPARATE ENTITY FROM THE REMAINDER OF THE
 ARL, THEN SHALL BE APPROVED AS A FORMAL SITE PLAN
 REVIEW.IF IT IS TO OPERATE AS A PART OF THE MAIN
 CAMPUS, THEN IT WILL NEED TO HAVE A SITE PLAN APPROVED
 BY THE CITY COMMISSION.
  