| 2007-07-24 18:28:25 | PROJECT: 5301 SOUTH DIXIE HIGHWAY |
| | |
| | PROJECT DESCRIPTION: STRUCTURAL REINFORCEMENT OF |
| | EXISTING STRUCTURAL FRAMING |
| | |
| | CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE |
| | W/2006 REVISIONS |
| | 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONSCITY OF |
| | WEST PALM BEACH/ FLORIDA BUILDING CODE/ADMINISTRATION |
| | AMENDMENTS, CHAPTER 1, 2004 EDITION |
| | |
| | STATUS: DENIED |
| | |
| | |
| | COMMENTS: |
| | |
| | |
| | 1) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE |
| | FOLLOWING: |
| | |
| | FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | |
| | 2) PLEASE DESIGNATE LEVEL OF ALTERATION AS PER THE |
| | FOLLOWING: |
| | |
| | 301.5 |
| | A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| | COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 3) INDICATE OCCUPANCY AND USE: |
| | |
| | 301.4OCCUPANCY AND USE. |
| | WHEN DETERMINING THE APPROPRIATE APPLICATION OF THE |
| | REFERENCED SECTIONS OF THIS CODE, THE OCCUPANCY AND USE |
| | OF A BUILDING SHALL BE DETERMINED IN ACCORDANCE WITH |
| | CHAPTER 3 OF THEFLORIDA BUILDING CODE, |
| | BUILDING. |
| | |
| | 4) AS PER THE EXISTING BUILDING CODE, THE FOLLOWING |
| | SHALL APPLY: |
| | |
| | 407.3.1NEW STRUCTURAL FRAME MEMBERS. |
| | NEW STRUCTURAL FRAME MEMBERS USED IN THE REPAIR OF |
| | DAMAGED BUILDINGS, INCLUDING ANCHORAGE AND CONNECTIONS, |
| | SHALL COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 5) PLEASE COMPLY WITH THE FOLLOWING: |
| | |
| | 2101.3 CONSTRUCTION DOCUMENTS. |
| | THE CONSTRUCTION DOCUMENTS SHALL SHOW ALL OF THE |
| | ITEMS REQUIRED BY THIS CODE INCLUDING THE FOLLOWING: |
| | 1.SPECIFIED SIZE, GRADE, TYPE AND LOCATION OF |
| | REINFORCEMENT, ANCHORS AND WALL TIES. |
| | |
| | 6) PLEASE SUBMIT A ROOF FRAMING PLAN. INDICATE THE |
| | CONTINUOUS LATERAL BRACING: |
| | |
| | 2319.17.2.1.8 |
| | ALL TRUSSES SHALL BE PROPERLY BRACED TO ACT AS A |
| | SYSTEM. SUCH BRACING SHALL BE INCLUDED AS PART OF THE |
| | DESIGN DOCUMENT. |
| | |
| | 7)PLEASE SHOW THE BUILDING ELEVATIONS AND INDICATE |
| | THE ROOF PITCH. |
| | |
| | 8)INDICATE SPECIES AND GRADE OF NEW STRUCTURAL LUMBER |
| | TO BE USED. |
| | |
| | 9)PLEASE SPECIFY GRADE AND LENGTH OF ANCHOR BOLTS. |
| | |
| | 10) PLEASE SHOW THE DIMENSIONS OF THE EXISTING |
| | FOUNDATION PADS. |
| | |
| | 11) PLEASE SUBMIT STRUCTURAL CALCULATIONS. |
| | |
| | 12) SUBMIT EPOXY SPECIFICATIONS. |
| | |
| | 13) PLEASE PROVIDE GROUT AND MORTAR SPECIFICATIONS. |
| | |
| | 14) SHOW ALL ACCESSIBILITY DIMENSIONS FOR THE BATHROOMS |
| | TO BE ADDED. |
| | |
| | 15) THE INDICATED CONSTRUCTION VALUATION APPEARS TO BE |
| | LOW. PLEASE PROVIDE SUPPORTING DATA. |
| | |
| | |
| | PLAN REVIEW: KEN CONRAD |
| | PHONE: 561.805.6666 |
| | E-MAIL: [email protected] |