Plan Review Details - Permit 07060684
Plan Review Stops For Permit 07060684
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-11-02 Cont ID  
Sent By mjacobs Date 2007-11-02 Time 14:17 Rev Time 0.00
Received By mjacobs Date 2007-11-02 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2007-10-13 Cont ID  
Sent By mjacobs Date 2007-10-13 Time 07:43 Rev Time 0.00
Received By mjacobs Date 2007-10-12 Time 18:01 Sent To  
Notes
2007-10-13 07:43:09BUILDING PLAN REVIEW
 PERMIT: 07060684
 ADD: 4047 OKEECHOBEE BLVD
 CONT: CB BOVENKAMP, INC.
 TEL: (305)233-4438
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 4TH
 ACTION: DENIED
 10/12-13/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION. LOOSE SHEETS ARE NOT
 ACCEPTABLE. SUBMIT THE TWO COMPLETE NEW SETS WITH NEW
 INFORMATION AND ONE OLD SET, THE ENERGY CALCUALTIONS
 INCLUDED.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. ****THE
 NOC HAS TO BE FILED AT THE COURT HOUSE AND THEN
 SUBMITTED TO OUR OFFICE. SEE NOC APPLICATION FORM IN
 PACKAGE.
  
 3)OK
  
 4)OK
  
 5)OK
  
 **NEW**
 A)THE ENGINEER?S SEAL ON THE MECHANICAL AND PLUMBING
 SHEETS IS OUT-DATED. THE SEAL WITH THE WORD
 ?CERTIFICATE? WAS ELIMINATED FROM THE SEAL. THE WORD
 ?CERTIFICATE? WAS REPLACED WITH ?LICENSE?. THE SEAL ON
 THESE SHEETS SHALL REFLECT THE NEW SEAL PER RULE
 61G15-23.001(1) F.A.C.
 **NOTE**THE ARCHITECTURAL SHEET ARE OK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-08 Cont ID  
Sent By mjacobs Date 2007-09-08 Time 16:17 Rev Time 0.00
Received By mjacobs Date 2007-09-08 Time 13:37 Sent To  
Notes
2007-09-08 16:17:03BUILDING PLAN REVIEW
 PERMIT: 07060684
 ADD: 4047 OKEECHOBEE BLVD
 CONT: CB BOVENKAMP, INC.
 TEL: (305)233-4438
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION. LOOSE SHEETS ARE NOT
 ACCEPTABLE. SUBMIT THE TWO COMPLETE NEW SETS WITH NEW
 INFORMATION AND ONE OLD SET, THE ENERGY CALCUALTIONS
 INCLUDED.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. ****THE
 NOC HAS TO BE FILED AT THE COURT HOUSE AND THEN
 SUBMITTED TO OUR OFFICE. SEE NOC APPLICATION FORM IN
 PACKAGE.
  
 3)OK
  
 4)FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTION 303, 304 AND 305 OF THIS
 CODE.
 **** NOTE: ALTERATION LEVEL 2 AND 3 INCLUDES THE
 RECONFIGURATION OF SPACE. IF ANY WALLS ARE REMOVED OR
 ADDED,THE SPACE IS CONSIDERED RECONFIGURED. SEE
 SHEET G100.
 **THIS IS NOT A LEVE 1 ALTERATION. ONCE AGAIN SEE THE
 CODE SECTIONS MENTIONED ABOVE.
  
 5)INDICATE THE TYPE OF BACKING FOR THE GRAB BARS
 WHICH WILL MEET THE REQUIREMENTS OF 250LBS.
 SEC.11-4.26.3(1)
 ****** THE NOTE ON SHEET A200 ADDRESSING THE GRAB BAR
 BACKING DOES NOT STATE WHAT TYPE OF MATERIAL WILL BE
 USED. WHAT IS THE GAUGE OF THE METAL STUD? WILL THERE
 BE ADDITIONAL WOOD BACKING? IF SO, STATE WHAT TYPE WILL
 BE USED.THE INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM ?LEGAL? OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 **NEW**
 A)THE SEAL ON THE ENERGY CALCULATIONS HAS BEEN
 OBSOLETE SINCE DECEMBER 31ST 2005. THE WORD
 ?CERTIFICATE? WAS CHANGED TO ?LICENSE?. THE ENGINEER
 NEEDS TO UP-DATE HIS SEAL. SEE F.A.C 61G15-23.001 NEW
 SEAL INFORMATION. THE INFORMATION IN THE PACKAGE SHALL
 MATCH WHAT IS ON THE PLANS IN REFERENCE TO THE WALLS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-10 Cont ID  
Sent By mjacobs Date 2007-08-10 Time 08:40 Rev Time 0.00
Received By mjacobs Date 2007-08-09 Time 18:05 Sent To  
Notes
2007-08-10 08:40:47BUILDING PLAN REVIEW
 PERMIT: 07060684
 ADD: 4047 OKEECHOBEE BLVD
 CONT: CB BOVENKAMP, INC.
 TEL: (305)233-4438
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. ****THE
 NOC HAS TO BE FILED AT THE COURT HOUSE AND THEN
 SUBMITTED TO OUR OFFICE. SEE NOC APPLICATION FORM IN
 PACKAGE.
  
 3)OK
  
 4)FBC EXISTING 301.5A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTION 303, 304 AND 305 OF THIS
 CODE.
 **** NOTE: ALTERATION LEVEL 2 INCLUDE THE
 RECONFIGURATION OF SPACE. IF ANY WALLS ARE REMOVED OR
 ADDED,THE SPACE IS CONSIDERED RECONFIGURED. SEE
 SHEET G100
  
 5)INDICATE THE TYPE OF BACKING FOR THE GRAB BARS
 WHICH WILL MEET THE REQUIREMENTS OF 250LBS.
 SEC.11-4.26.3(1)
 ****** THE NOTE ON SHEET A200 ADDRESSING THE GRAB BAR
 BACKING DOES NOT STATE WHAT TYPE OF MATERIAL WILL BE
 USED. WHAT IS THE GAUGE OF THE METAL STUD? WILL THERE
 BE ADDITIONAL WOOD BACKING? IF SO STATE WHAT TYPE WILL
 BE USED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 15:31 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 13:34 Sent To  
Notes
2007-06-30 15:31:40BUILDING PLAN REVIEW
 PERMIT: 07060684
 ADD: 4047 OKEECHOBEE BLVD
 CONT: CB BOVENKAMP, INC.
 TEL: (305)233-4438
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE/WITH 2006 REVISIONS.
  
 4)FBC EXISTING 301.5A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTION 303, 304 AND 305 OF THIS
 CODE.
  
 5)INDICATE THE TYPE OF BACKING FOR THE GRAB BARS
 WHICH WILL MEET THE REQUIREMENTS OF 250LBS.
 SEC.11-4.26.3(1)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-11-16 Cont ID  
Sent By btrobaug Date 2007-11-16 Time 09:04 Rev Time 0.00
Received By btrobaug Date 2007-11-16 Time 08:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-10-11 Cont ID  
Sent By btrobaug Date 2007-10-11 Time 12:11 Rev Time 0.00
Received By btrobaug Date 2007-10-11 Time 11:56 Sent To  
Notes
2007-10-11 12:08:46 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 SAME COMMENTS AS THE PREVIOUS REVIEW, 9/12/07, SEE FS
 552.80(2)(B), ATTACHED.
  
 1} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEALACCEPTABLETO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME. SEE BUILDING REVIEW COMMENT. *SEE
 ENERGY CALCULATION CERTIFICATION SHEET.
  
 2} WHEN RESUBMITTING ASSEMBLE THE SETS TOGETHER. THE
 ELECTRICAL SHEETS WERE SEPARATE FROM THE REST OF THE
 RESUBMITTED SETS. PLEASE STAPLE BOTH SETS IN ORDER.
  
 ASIDE FROM THE OUTDATED SEAL ON THE COMPLIANCE FORM,
 THE ELECTRICAL PLANS ARE CODE COMPLIANT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-12 Cont ID  
Sent By btrobaug Date 2007-09-12 Time 16:44 Rev Time 0.00
Received By btrobaug Date 2007-09-12 Time 15:52 Sent To PC
Notes
2007-09-12 16:44:11 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEALACCEPTABLETO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME. SEE BUILDING REVIEW COMMENT.
  
 2} WHEN RESUBMITTING ASSEMBLE THE SETS TOGETHER. THE
 ELECTRICAL SHEETS WERE SEPARATE FROM THE REST OF THE
 RESUBMITTED SETS. PLEASE STAPLE BOTH SETS IN ORDER.
  
 ASIDE FROM THE OUTDATED SEAL ON THE COMPLIANCE FORM,
 THE ELECTRICAL PLANS ARE CODE COMPLIANT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-17 Cont ID  
Sent By btrobaug Date 2007-08-17 Time 12:00 Rev Time 0.00
Received By btrobaug Date 2007-08-17 Time 06:57 Sent To  
Notes
2007-08-17 11:56:08 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
 COMMENT TO THE RESPONSES DATED JULY 16, 2007: INDICATE
 COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR SPACE CONTROLS
 FOR LIGHTING." STANDARD SWITCHES ARE SHOWN ON THE PLAN.
 NOTE #1 ADDRESSING THIS ISSUE STATES THAT THE "SPACES
 LESS THAN 5000 SF". PLEASE SEE 13-101.1.4. S "SPACE" IS
 NOT A "BUILDING", THE "BUILDING" IS MORE THAN 5000 SF,
 THE "SPACE" MUST COMPLY.
  
 2} PAGE #2 OF THE ENERGY GAUGE INPUT DATA REPORT, DOES
 NOT INDICATE THE CORRECT NUMBER OF FIXTURES AS SHOWN ON
 THE PLAN, THE WATTAGES PER LUMINAIRE ARE INCORRECT, AND
 THE CONTROL TYPE MUST BE PER 13-415.1ABC.1.2. THIS
 REVIEW} THE CONTROL TYPE IS NOT IN COMPLIANCE, SEE
 COMMENT #1.
  
 3} PER 13-103.1.1, THE PERSON PREPARING THE COMPLIANCE
 CERTIFICATION MUST SIGN AND SEAL SAME.SEE SHEET #3.
 THIS REVIEW} SHEET #3 IS NOT SEALED.
  
 NEW COMMENT #4} THE WATTAGES GIVEN IN THE LIGHTING
 SECTION OF THE INPUT DATA REPORT, PAGES 2 AND 3, SEEM
 TO BE IN EXCESS OF THE ALLOWED WATTAGES. IG: TECH ROOM
 107 @ 285 SQ FT X 1.1 (ALLOWED TABLE 13-415.2B ENCLOSED
 SPACE) = 313.5. THE POWER GIVEN FOR THAT SPACE IS 510
 WATTS. PLEASEREVIEW THE CALCULATIONS
  
 NEW COMMENT #5} THIS REVIEW WAS DONE UNDER THESE
 CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1. PLEASE CORRECT SHEET G100.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By btrobaug Date 2007-06-27 Time 11:26 Rev Time 0.00
Received By btrobaug Date 2007-06-27 Time 07:49 Sent To  
Notes
2007-06-27 11:24:40 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 2} PAGE #2 OF THE ENERGY GAUGE INPUT DATA REPOR, DOES
 NOT INDICATE THE CORRECT NUMBER OF FIXTURES AS SHOWN ON
 THE PLAN, THE WATTAGES PER LUMINAIRE ARE INCORRECT, AND
 THE CONTROL TYPE MUST BE PER 13-415.1ABC.1.2..
  
 3} PER 13-103.1.1, THE PERSON PREPARING THE COMPLIANCE
 CERTIFICATION MUST SIGN AND SEAL SAME. SEE SHEET #3.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-16 Cont ID  
Sent By mwennerg Date 2007-11-16 Time 11:09 Rev Time 0.00
Received By mwennerg Date 2007-11-16 Time 11:09 Sent To  
Notes
2007-11-16 11:11:37NEW SHEET A-100 STAMPED, DATED AND SIGNED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-07-02 Cont ID  
Sent By mwennerg Date 2007-07-02 Time 13:55 Rev Time 0.00
Received By mwennerg Date 2007-07-02 Time 13:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 16:40 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 16:40 Sent To  
Notes
2007-11-07 13:29:18TO "COMM" BD#36
2007-10-23 16:40:46WAITING FOR "COMM"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-19 Cont ID  
Sent By adarroug Date 2007-09-19 Time 09:53 Rev Time 0.00
Received By adarroug Date 2007-09-19 Time 09:53 Sent To  
Notes
2007-10-10 12:09:48TO "COMM" BD#49
2007-09-19 09:53:45WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 14:23 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 14:23 Sent To  
Notes
2007-09-06 11:11:54TO "COMM" BD#18
2007-08-27 14:23:51WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 15:27 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 15:27 Sent To  
Notes
2007-08-01 10:46:04TO "BOB"#1
2007-07-19 15:28:13WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-07-02 Time 11:18 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 13:46 Sent To  
Notes
2007-06-24 13:46:28TO "BOB"#17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-14 Cont ID  
Sent By tgordon Date 2007-11-14 Time 10:38 Rev Time 0.30
Received By tgordon Date 2007-11-14 Time 10:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By tgordon Date 2007-08-02 Time 09:36 Rev Time 0.25
Received By tgordon Date 2007-08-02 Time 09:36 Sent To  
Notes
2007-10-16 09:34:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE PLUMBING REVIEW NOTE REGARDING ENGINEER FRED D.
 GORDON'S SEAL, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By tgordon Date 2007-06-29 Time 08:20 Rev Time 0.45
Received By tgordon Date 2007-06-29 Time 08:20 Sent To  
Notes
2007-06-29 08:25:30*** DENIED ***
 1) SEE PLANS PAGE G100, CODES REFER TO 2003
 INTERNATIONAL BUILDING AND MECHANICAL CODES. PLEASE
 CORRECT PLANS TO THE 2004 FLORIDA BUILDING AND
 MECHANICAL CODES WITH THE 2006 REVISIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-11-30 Cont ID  
Sent By jleech Date 2007-11-30 Time 07:20 Rev Time 0.00
Received By jleech Date 2007-11-30 Time 07:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By jleech Date 2007-10-16 Time 09:18 Rev Time 0.00
Received By jleech Date 2007-10-16 Time 09:15 Sent To  
Notes
2007-10-16 09:21:01DENIED;
 THE ENGINEER'S SEAL IS OUT OF DATE. THE SEAL SHOULD SAY
 LICENSE NOT CERTIFICATE. SEE RULE 61G15-23.001(1).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-07-03 Cont ID  
Sent By jleech Date 2007-07-03 Time 10:09 Rev Time 0.00
Received By jleech Date 2007-07-03 Time 09:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-02 Cont ID  
Sent By choops Date 2007-08-02 Time 08:12 Rev Time 0.00
Received By choops Date 2007-08-02 Time 08:12 Sent To  
Notes
2007-08-02 08:13:00*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.