Plan Review Details - Permit 07060675
Plan Review Stops For Permit 07060675
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-16 Cont ID  
Sent By mjacobs Date 2007-07-16 Time 10:53 Rev Time 0.00
Received By mjacobs Date 2007-07-16 Time 10:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 08:11 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 06:34 Sent To  
Notes
2007-06-30 08:11:47BUILDING PLAN REVIEW
 PERMIT: 07060675
 ADD: 1801 S.FLAGLER DR.
 CONT: FINE DETAILS INC.
 TEL: (561)835-3519
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)SUBMIT A WALL DETAIL OF THE NEW WALLS INDICATING
 ALL MATERIALS.
  
 3)INDICATE ON THE DRAWINGS THE CODE WHICH THIS
 PROJECT IS DESIGN UNDER.ALL PLANS SUBMITTED AFTER
 OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004 FLORIDA BUILDING
 CODE/ 2006 REVISIONS.
  
 4)FBC EXISTING SEC. 301.5A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303/304 AND 305 OF THIS
 CODE.
  
 5)THE DRAWINGS ARE MISSING SOME DIMENTIONS.
 FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 TO SHOW SUFFICIENT CLARITY TO INDICATE THE
 LOCATION,NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIN THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE.
  
 6)A DETAIL SHOWING HOW THE DOME WILL BE SUPPORTED IS
 REQUIRED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 18:57 Sent To PC
Notes
2007-09-07 19:22:12REV OK, FOR UNIT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 19:06 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 18:48 Sent To PC
Notes
2007-08-27 19:06:552007-08-27 19:06:55
  
 *** DENIED REVIEW ***
  
 1) NOTE: PLEASE SEE THAT PLANS ARE BEING SUBMITTED WITH
 THE ADDITIONAL WHIRLPOOL CIRCUITS BEING ADDED TO UNIT
 AND PANEL SCHEDULE HOWEVER NO LOADS WERE INCREASED ON
 THE LOAD CALCULATIONS OR SERVICE. PLEASE KNOW THAT
 BASED ON THE EXISTING LOAD SHOWN THIS SERVICE PANEL,
 MAIN AND FEEDERS WILL BE OVER LOADED. PLEASE SUBMIT
 REVISED PLANS TO INCREASED THE SERVICE TO UNIT. PLEASE
 ALSO CONFIRM THE LOAD ON THE INSTA-HOT AS THIS OFFICE
 HAS NOT SEEN ONE AT 600VA. (PLEASE SUBMIT SPEC SHEETS)
 PLEASE SEE NEC 2005 AS THERE ARE TOO MANY SECTIONS TO
 LIST AL OF THE ITEMS FOR THE OVER LOADED SERVICE AND
 PANEL.
 220, 215.5, 240.4, 310.16, 220.83B,
 230.90,240.6,230.76,230.79,230.70, ETC.
  
 2) NOTE: PLEASE SEE THAT IN NO CASE MAY PLANS WHICH ARE
 SIGNED, DATED AND SEALED BY AN ARCHITECT OR ENGINEER
 HAVE HAND DRAWN CHANGES ON PLANS OR WHITE-OUT. THIS IS
 NOT PERMITTED EVEN WHEN PLANS ARE NOT SIGNED AND SEALED
 BY A DESIGN PROFESSIONAL.
 FS 481, 471,
 FBC 106.1.2, 106.3.1, ETC.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-12 Cont ID  
Sent By dpalmer Date 2007-07-12 Time 15:46 Rev Time 0.00
Received By dpalmer Date 2007-07-12 Time 15:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-24 Cont ID  
Sent By dpalmer Date 2007-06-24 Time 11:12 Rev Time 0.00
Received By dpalmer Date 2007-06-24 Time 10:42 Sent To  
Notes
2007-06-24 11:13:08*** UNSAT ***
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE
 INDICATE SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS
 THESE AS SMOKE DETECTORS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
  
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE COMPLETE PANEL SCHEDULE WITH THE
 CONDUCTOR SIZES PER 240.4, 310.16, 408.4.
  
 4) NOTE: PLEASE SEE THE WATER HEATER UNDER THE NEW 2005
 NEC IS REQUIRED TO BE SHOWN AT 125% IN LOAD
 CALCULATIONS.
 422.13
  
 5) NOTE: PLEASE SEE PLANS APPEAR TO BE MISSING THE
 RECEPTACLE LOCATION FOR THE DISHWASHER. PLEASE ALSO SEE
 THE 210.4B IF BOTH THE DISH/ DISP ARE BEING FED TO THE
 SAME YOKE WHICH WILL REQUIRE A 2-POLE BREAKER.
  
 6) NOTE: PLEASE SEE SOME RECEPTACLES MISSING PER 210.52
 FOR 2FT OR MORE OF WALL SPACE.
 PLEASE SEE REDLINED PLANS AS SOME OF THESE ARE SHOWN.
  
 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS SEEM TO BE
 MISSING THE DEDICATED LOAD FOR THE DISPOSAL.
 PLEASE ADJUST LOAD CALCULATIONS.
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE SEE THE OUTER BALCONY DOES NOT SHOW ANY
 GFI RECEPTACLE(S) OR LIGHTING. THIS IS ONLY NOTED AS
 THIS IS NOT REQUIRED BY CODE HOWEVER MAY BE PLACED ON
 PLANS IF ANY IS TO BE INSTALLED.
 ** ONLY NOTED **
  
 9) NOTE: PLEASE SEE ALL RECESSED LIGHTING LUMINARIES
 ARE REQUIRED TO MEET FBC 2004 13-606.1.ABC.1.2.4.
 PLEASE PLACE NOTE/INFORMATION FOR THIS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-13 Cont ID  
Sent By mwennerg Date 2007-07-13 Time 13:42 Rev Time 0.00
Received By mwennerg Date 2007-07-13 Time 13:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-07-02 Cont ID  
Sent By mwennerg Date 2007-07-02 Time 13:21 Rev Time 0.00
Received By mwennerg Date 2007-07-02 Time 13:21 Sent To  
Notes
2007-07-02 13:22:26SEPARATE SHOP DRAWINGS AND PERMITS MAY BE REQUIRED IF
 FIRE SPRINKLER OR FIRE ALARM SYSTEMS ARE IMPACTED BY
 THIS WORK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 10:46 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 10:46 Sent To E
Notes
2007-09-07 10:47:06TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 15:19 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 15:19 Sent To E
Notes
2007-08-27 15:19:25TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 08:35 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 08:35 Sent To  
Notes
2007-07-12 10:12:41TO "BOB"#4
2007-07-10 08:36:08WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-02 Cont ID  
Sent By mwennerg Date 2007-07-02 Time 14:25 Rev Time 0.00
Received By mwennerg Date 2007-06-22 Time 10:10 Sent To  
Notes
2007-06-22 10:14:18TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-02 Cont ID  
Sent By rregueir Date 2007-07-02 Time 14:26 Rev Time 0.00
Received By rregueir Date 2007-07-02 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-16 Cont ID  
Sent By jleech Date 2007-07-16 Time 07:37 Rev Time 0.00
Received By jleech Date 2007-07-16 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-07-02 Cont ID  
Sent By jleech Date 2007-07-02 Time 13:48 Rev Time 0.00
Received By jleech Date 2007-07-02 Time 13:48 Sent To  
Notes
***NONE***