Plan Review Details - Permit 07060640
Plan Review Stops For Permit 07060640
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By mjacobs Date 2007-07-19 Time 08:26 Rev Time 0.00
Received By mjacobs Date 2007-07-18 Time 14:29 Sent To PC
Notes
2007-07-19 08:26:26BUILDING PLAN REVIEW
 PERMIT: 07060640
 ADD: 1000 36TH ST.
 CONT: TREADSTONE CONSTRUCTION GROUP
 TEL: (954)584-0751
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)106.1.3THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT" "NO HAND WRITING ON PLANS"
  
 2)THERE IS CONFLECTING INFORMATION ON THE DRAWINGS IN
 REFERENCE TO THE SIZE OF THE TANKS. THE HAND WITTEN
 INFORMATION STATES 500 GALLONS AND THE GENERATOR
 CALCULATION INDICATE 550 GALLONS. CLARIFY.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLAACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION RREFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By dpalmer Date 2007-07-02 Time 13:20 Rev Time 0.00
Received By dpalmer Date 2007-07-02 Time 11:08 Sent To I
Notes
2007-07-02 13:20:302007-07-02 13:20:30
  
 *** UNSAT ***
  
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING: SOME
 ARE ALREADY SHOWN ON PLANS.
  
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2002 NFPA-110.
  
 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE
 SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER
 AND NO COST TO CONTRACTOR.
 PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY
 THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE.
  
 3) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE
 PREVIOUS EXPIRED PERMIT APPLICATION ADDRESSES THE
 LETTER TO A *MIKE HIRTANZO* AS THE ELECTRICAL PLAN
 REVIEWER. PLEASE SEE THE PREVIOUS REVIEW NOTES UNDER
 PREVIOUS APPLIED PERMIT WAS GIVEN BY MYSELF AND THE
 ABOVE PERSON DOES NOT WORK FOR THE CITY OF WEST PALM
 BEACH.
  
 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT WHICH INDICATE LISTINGS FROM A
 NRTL. THE LISTINGS AS SHOWN FOR THE GENERATOR AS
 SUBMITTED DO NOT MEET ANY NRTL AS LISTED.
 PLEASE SUBMIT THE SPECS FOR THE WP ENCLOSURE ETC.
 PLEASE COORDINATE ALL.
 PLEASE BE SURE TO HIGH-LIGHT ALL EQUIPMENT SPECIFIC TO
 WORK.
 NEC 110.3, 90.7 ETC
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE PLANS HAVE HAND-DRAWN CHANGES
 WHICH ARE NOT PERMITTED TO PLANS WHICH ARE SIGNED,
 DATED AND SEALED BY AN ENGINEER. FS 471.025
 PLEASE SEE 1 OF 1.
  
 6) NOTE: PLEASE SEE TWO DIFFERENT SIZE TANKS ARE BEING
 INDICATED ON PLANS. ONE 500 AND THE OTHER 550 GALS.
 PLEASE COORDINATE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE ADDRESS ON PLANS NEEDS TO
 COORDINATE WITH THE SITE. THE ADDRESS IS NOT NE 36TH
 ST.
 FA C61G1-16.004
  
 8) NOTE: PLEASE SEE MISSING MEANS OF DISCONNECT AT
 BUILDING. THE BREAKER DOES NOT MEET 702.11,
 225.31-225.39
 PLEASE KNOW THIS DISCONNECTING MEANS ONLY NEEDS TO BE
 RATED FOR THE LOAD SERVED AND DOES NOT NEED TO CONTAIN
 OCP AS THE BREAKER IN THE GENERATOR CONTAINS THE OCP.
  
 9) NOTE: PLEASE SEE PERMIT APPLICATION REQUEST TO
 PROVIDE IN DETAIL THE SCOPE OF WORK. PLEASE INCLUDE THE
 SIZE OF THE GENERATOR.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE RISER SHOWS THE CAPACITY PROVIDED
 AS 1041AMPS, YET THE GENERATOR ONLY INDICATES
 1000AMPS?
 PLEASE COORDINATE ALL EQUIPMENT, LOADS ETC.
  
 11) NOTE: PLEASE SEE SITE PLANS WHICH WERE SUBMITTED DO
 NOT SHOW ALL SETBACKS ELEVATIONS OF EQUIPMENT, FLOOD
 ZONES?
 PLEASE SEE COMMENTS FROM OTHER TRADES FOR THIS
 INFORMATION. IF IN A FLOOD ZONE, THE UNIT WILL NEED TO
 MEET HEIGHT AND A FLOOD CERTIFICATE WILL BE REQUIRED
 BEFORE FINAL.
  
 ** PLEASE KNOW THERE MAY BE NEW COMMENTS ONCE
 ADDITIONAL INFORMATION IS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-02 11:09:41PLANS REMOVED FROM INCOMING. WILL BE ROUTED BACK TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLTETED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 22:45 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 22:24 Sent To  
Notes
2007-07-26 22:36:47*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.NO ADDRESS SHOWN ON
 SITEPLAN AND ELEVATION SHEET.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA
 110.
  
 3.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE
 INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA
 704 LABELS WILL BE REQUIRED.
  
 4.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE GENERATOR
 AND ASSOCIATED EQUIPMENT.
  
 6.THE INSTALLATION AND/OR SCOPE OF WORK SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2007-07-22 Cont ID  
Sent By rregueir Date 2007-07-22 Time 10:50 Rev Time 0.00
Received By rregueir Date 2007-07-22 Time 09:51 Sent To  
Notes
2007-07-22 10:43:04-------------DENIED--------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SHEET 1 OF 1 INDICATES 500 GALLON TANK, SHEET E-1
 INDICATES 550 GALLONS. PLEASE COORDINATE DRAWINGS PER
 FBC 106.1.1.
  
 2. ABOVE GROUND STORAGE TANKS OF 550 GALLONS OR MORE
 REQUIRE APPROVAL BY PALM BEACH COUNTY DERM PRIOR TO
 PERMITTING BY THE CITY OF WEST PALM BEACH. FOR
 ADDITIONAL INFORMATION, PLEASE CONTACT DERM AT
 561-233-2400 OR WWW. PBCGOV.COM/ERM
  
 3.SHEET 1 OF 1 HAS BEEN MODIFIED BY HAND. SIGNED AND
 SEALED DRAWINGS SHALL NOT BE MODIFIED. FS 471.025
  
 4. ABOVE GROUND TANKS REQUIRE EMERGENCY RELIEF VENTING
 FOR FIRE EXPOSURE. PLEASE SHOW SITE SPECIFIC MEANS OF
 EMERGENCY RELIEF VENTING IN COMPLIANCE WITH NFPA 30-00
 SEC. 2.2.5.2. EMERGENCY RELIEF VENT PIPING SHALL BE IN
 CONFORMANCE WITH NFPA 30-00 CHAPTER 3.
  
 RONALD J REGUEIRO
 561.805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-07-17 Cont ID  
Sent By kstevens Date 2007-07-17 Time 07:11 Rev Time 0.00
Received By kstevens Date 2007-07-17 Time 07:11 Sent To  
Notes
2007-07-17 07:12:19MTS GENERATOR INDICATES A DIESEL GENERATOR

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 22:24 Rev Time 0.00
Received By mawillia Date 2007-06-21 Time 10:09 Sent To  
Notes
2007-07-09 14:03:20TO "COMM" BD#15
2007-06-21 10:10:27WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-22 Cont ID  
Sent By rregueir Date 2007-07-22 Time 09:50 Rev Time 0.00
Received By rregueir Date 2007-07-20 Time 17:00 Sent To  
Notes
2007-07-22 09:50:35--------------DENIED----------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 NFPA 37-02
  
 1. PROVIDE MANUFACTURER'S SPECS INDICATING MINIMUM
 REQUIRED CLEARANCES FOR MAINTENANCE; AIRFLOW FOR
 COMBUSTION, COOLING AND VENTILATION. NFPA 37-02 SEC.
 4.1.1
  
 2. PROVIDE INFORMATION ON WEATHERPROOF ENCLOSURE WHICH
 IS BEING PROVIDED AS INDICATED ON PLANS. NFPA 37-02 SEC
 4.1.4
  
 3. NO INFORMATION IS PROVIDED REGARDING GENERATOR
 EXHAUST. PLEASE SHOW COMPLIANCE WITH ALL APPLICABLE
 SECTIONS OF NFPA 37-02 CH. 8.
  
 4. PROVIDE INFORMATION RELATING TO WIND RESISTANCE IN
 ACCORDANCE WITH FBC,M 301.13 AND FBC CH.16. SEE
 BUILDING PLAN REVIEW COMMENT #4.
  
 RONALD J REGUEIRO
 561.805-6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-20 Cont ID  
Sent By bpowell Date 2007-07-20 Time 10:32 Rev Time 0.00
Received By bpowell Date 2007-07-20 Time 10:32 Sent To  
Notes
2007-07-20 10:38:461. TWO COPIES OF THE SURVEY SHALL BE PROVIDED WITH THE
 PERMIT APPLICATION.
  
 2. THE SITE PLAN SHALL BE DRAWN TO SCALE.
  
 3. PLEASE INDICATE THE LOCATION OF PARKING SPACES IN
 RELATION TO THE GENERATOR.
  
 4. THE TYPE OF HEDGES AND SHRUBS THAT ARE BEING
 PROPOSED TO BE PLACED AROUND THE GENERATOR SHALL BE
 SHOWN.
  
 5. THE DIMENSIONS OF THE GENERATOR FROM THE PROPERTY
 LINE SHALL BE CLEARLY DEFINED.PURSUANT TO SECTION
 94-305 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN
 FOUR FEET INTO ANY SETBACK.
  
 6. PLEASE PROVIDE DETAILS OF LANDSCAPING AROUND THE
 GENERATOR AS ALL LANDSCAPED AREAS AND PLANT MATERIALS
 WITHIN OR ADJACENT TO VEHICULAR USE AREAS SHALL BE
 PROTECTED FROM VEHICULAR ENCROACHMENT BY WHEEL STOPS,
 CURBS OR OTHER SIMILAR DEVICES, PER SECTION 94-442(4).
  
 FOR QUESTIONS OR COMMENTS PLEASE CONTACT:BOBBY
 POWELL, JR, PLANNER, [email protected], 822-1435