Plan Review Details - Permit 07060601
Plan Review Stops For Permit 07060601
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-26 Cont ID  
Sent By shill Date 2007-08-26 Time 16:21 Rev Time 0.00
Received By shill Date 2007-08-26 Time 16:20 Sent To  
Notes
2007-08-26 16:21:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE PREVIOUS LISTS.THE ANCHOR SPACING COLUMN WAS
 LEFT BLANK.THIS INFORMATION IS REQUIRED.
  
 2.)8" AND 9" SHUTTER GLASS SEPARATION IS NOT POSSIBLE
 WITH AN 8" BLOCK WALL.PLEASE REVISE.
  
 3.)8" AND "FLUSH" EDGE DISTANCE ARE NOT CORRECT.
 PLEASE SEE THE PRODUCT APPROVAL AND REVISE THE
 INSTALLATIN SCHEDULE.
  
 4.)SHUTTER MOUNTING CONNECTION TYPE SHOULD BE C1
 THROUGH C5, SEE SHEET 9 OF THE PRODUCT APPROVAL.NOTE
 THAT YOU SHOULD USE THE ANCHOR SCHEDULE ON SHEET 9 AS
 YOU HAVE STATED THAT THE SUBSTRATE IS BLOCK.
  
 5.)SPANS ON INTALLATION SCHEDULE ARE NOT CORRECT.
 THIS SHOULD BE THE BLADE LENGTH, WHICH SHOULD CORRELATE
 WITH THE SHUTTER HEIGHT.
  
 6)YOU'VE WRITTEN "NA" FOR WALL PRESSURES.WORST CASE
 FOR EXPOSURE B, ZONE 5, 10 SF IS -47.2.YOU MAY EITHER
 USE THE DESIGN PRESSURES IN THE BUILDING CODE FBC R301,
 OR USE THE ROW FOR -55PSF ON THE PRODUCT APPROVAL
 (WORST CASE FOR EXPOSURE B).
  
 7.)ANCHOR TYPE SHOULD CORRELATE WITH PRODUCT
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By shill Date 2007-06-26 Time 12:50 Rev Time 0.00
Received By shill Date 2007-06-26 Time 12:50 Sent To  
Notes
2007-06-26 12:51:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 _XX_2.TWO SETS REQUIRED.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.THE FORM WAS ONLY PARTIALLY
 COMPLETED.
  
 _XX_4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____5.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____6.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____7.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 09:36 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 09:36 Sent To B
Notes
2007-08-21 09:36:30TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-26 Cont ID  
Sent By shill Date 2007-06-26 Time 12:52 Rev Time 0.00
Received By shill Date 2007-06-20 Time 11:49 Sent To  
Notes
2007-06-20 11:49:39TO "MISC" BOX#1